York TCHD18 THRU 60 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of York TCHD18 THRU 60, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of York TCHD18 THRU 60 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of York TCHD18 THRU 60. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of York TCHD18 THRU 60 should contain:
- informations concerning technical data of York TCHD18 THRU 60
- name of the manufacturer and a year of construction of the York TCHD18 THRU 60 item
- rules of operation, control and maintenance of the York TCHD18 THRU 60 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of York TCHD18 THRU 60 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of York TCHD18 THRU 60, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the York service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of York TCHD18 THRU 60.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the York TCHD18 THRU 60 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    TECHNICAL GUIDE HORIZONT AL DISCHARGE AIR CONDITIONERS 13 SEER – R-410A MODELS: TCHD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous pr oduct improvemen t, specifications are subject to change withou t notice. Visit us on the web at www .york.com Additional ra ting information can be found at www .ahridirectory .org W ARRANTY S tan[...]

  • Page 2

    556454-YTG-A-0210 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. . Physical and Electrical Dat a MODEL TCHD18 S41S3 TCHD24 S41S3 TCHD30 S41S3 TCHD36 S41S3 TCHD48 S41S3 TCHD60 S41S3 Unit Supply V oltage 208-230V , 1  60Hz Normal V [...]

  • Page 3

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 3 System Charge for V arious Matched Systems Out door Unit TCHD18S41S3 TCHD24S41S3 T CHD30S41S3 TCHD36S41S3 TCHD4 8S41S3 TCHD60S41S3 Required Ori fice or TXV 1 1TVM4F1 1TVM4F1 1TVM4G1 1TVM4G1 1TVM4J1 1TVM4K1 Factory Charge, lbs-oz 2 - 14 3 - 5 4 - 0 4 - 8 5 - 5 5 - 6 Indoor Coil 2,3 Additional Ch[...]

  • Page 4

    556454-YTG-A-0210 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing. 2. V erify the TXV and additional charge re quir ed for specific evaporator coil in the system using the above table. 3. Ad[...]

  • Page 5

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SEN S. 13 SEER AC WITH MV - V ARIABLE SPEED TCHD18S41S3 MV12B 17 FC/MC18B 600 18.0 12.3 14.05 1 1.85 MV12B 17 FC/MC24B 600 18.4 12.9 14.50 12.15 MV12B 17 FC/MC30B 6[...]

  • Page 6

    556454-YTG-A-0210 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / AHX / F*FP TCHD18S41S3 AHX18 17 – 630 18.2 13.1 14.25 1 1.75 AHX24 17 – 590 18.3 13.0 14.25 1 1.75 AHX30 17 – 610 18.6 13.3 14.50 12.00 F6FP018 17 – 600 17.9 12 .6 13.50 1 1.25 F6FP024 17 – 600 18.5 13 .1 14.00 1 1.50 F6FP030 17 – 620[...]

  • Page 7

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SEN S. TCHD18S41S3 450 - 750 14,17 FC/MC/PC24 600 18.0 12.6 13.00 1 1.00 450 - 750 14,17 FC/MC/PC30 600 18.0 12.6 13.0[...]

  • Page 8

    556454-YTG-A-0210 8 Johnson Controls Unitary Products COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 TCHD18S41S3 T*(8,L)X*A12 FC/MC/PC18A 14 540 17.7 12.4 14.00 1 1.50 T*(8,L)X*B12 FC/MC/PC18B 17 580 17.9 12.6[...]

  • Page 9

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 9 TCHD18S41S3 Y*9C*B12 HD36 17 635 18.5 12.9 14.75 12.35 Y*9C*C16 HD36 21 595 18.6 12.9 15.00 12.50 Y*(8,L)C*A12 UC18A 14 620 18.2 13.1 14.55 12.10 Y*(8,L)C*B12 UC18B 17 580 18.0 12.7 14.50 12.15 Y*9C*B12 UC18B 17 610 18.2 13.1 14.70 12.25 Y*(8,L)C*A12 UC24A 14 640 18.6 13.4 14.75 12.30 Y*(8,L)C*[...]

  • Page 10

    556454-YTG-A-0210 10 Johnson Controls Unitary Products TCHD24S41S3 T*9X*B12 HD36 17 790 23.0 17.0 14.00 1 1.75 T*(8,L)X*A12 UC24A 14 785 23.6 17.3 14.50 12 .00 T*(8,L)X*B12 UC24B 17 835 23.6 17.6 14.75 12 .00 T*9X*B12 UC24B 17 775 23.6 17.3 14.50 12.00 T*(8,L)X*A12 UC30A 14 785 23.6 17.3 14.50 12 .00 T*(8,L)X*B12 UC30B 17 835 23.6 17.6 14.75 12 .00[...]

  • Page 11

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 11 TCHD24S41S3 Y*(8,L)C*A12 HC30 14 775 23.4 17.2 14.10 12.00 Y*(8,L)C*B12 HC36 17 760 23.6 17.1 14.50 12.20 Y*9C*B12 HC36 17 815 23.8 17.6 14.35 12.15 Y*(8,L)C*C16 HC42 21 895 24.4 18.9 14.90 12.60 Y*(8,L)C*C20 HC42 21 760 24.0 17.5 15.05 12.70 Y*9C*C16 HC42 21 810 24.2 18.0 14.75 12.45 Y*9C*C20[...]

  • Page 12

    556454-YTG-A-0210 12 Johnson Controls Unitary Products TCHD30S41S3 T*(8,L)X*B12 FC/MC/PC43B 17 1 1 15 28.8 21.6 14.25 12 .25 T*(8,L)X*C20 FC/MC/PC43C 21 870 26.4 21.3 14.50 12 .50 T*9X*B12 FC/MC/PC43B 17 1095 28.8 21.6 14.25 12.25 T*9X*C16 FC/MC/PC43C 21 1055 28.8 21.1 14.25 12.25 T*(8,L)X*C20 FC/MC/PC48C 21 890 28.8 20.9 15.50 13 .50 T*9X*C16 FC/M[...]

  • Page 13

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 13 TCHD30S41S3 Y*(8,L)C*C16 HC42 21 990 29.0 21.8 15.35 13.60 Y*(8,L)C*C20 HC42 21 1000 29.0 21.8 15.40 13.65 Y*9C*C16 HC42 21 1030 28.8 21.8 14.80 13.15 Y*9C*C20 HC42 21 995 29.0 21.8 15.20 13.45 Y*(8,L)C*A12 HD36 14 1000 28.0 20.2 14.30 12.65 Y*(8,L)C*B12 HD36 17 985 28.0 20.4 14.65 13.00 Y*(8,[...]

  • Page 14

    556454-YTG-A-0210 14 Johnson Controls Unitary Products TCHD36S41S3 T*9X*D20 FC/MC/PC48D 24 1240 34.8 25.7 14.75 12.50 T*(8,L)X*A12 HD36 14 1270 33.2 24.2 13.40 1 1.75 T*(8,L)X*B12 HD36 17 1270 33.2 24.2 13.70 1 1.75 T*9X*B12 HD36 17 1270 33.4 24.4 13.85 1 1.75 T*(8,L)X*C16 HD48 21 1 120 34.2 24.9 14.00 12.50 T*(8,L)X*C20 HD48 21 1245 34.8 26.0 14.0[...]

  • Page 15

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 15 TCHD36S41S3 Y*(8,L)C*B12 HC36 17 1220 33.4 24.4 13.55 1 1.80 Y*9C*B12 HC36 17 1 190 33.2 24.0 13.60 1 1.75 Y*(8,L)C*C16 HC42 21 1205 34.6 25.4 14.75 12.75 Y*(8,L)C*C20 HC42 21 1 1 90 34.6 25.6 15.00 13.00 Y*9C*C16 HC42 21 1240 34.4 25.2 14.25 12.30 Y*9C*C20 HC42 21 1200 34.6 25.4 14.65 12.65 Y[...]

  • Page 16

    556454-YTG-A-0210 16 Johnson Controls Unitary Products TCHD48S41S3 T*9X*D20 HD48 24 1645 48.0 33.9 13.35 12 .00 T*(8,L)X*C16 UC48C 21 1640 45.5 32.8 13.00 1 1.00 T*(8,L)X*C20 UC48C 21 1515 45.0 31.6 13.05 1 1.50 T*9X*C16 UC48C 21 1565 45.0 32.8 13.00 1 1.00 T*9X*C20 UC48C 21 1615 45.5 32.8 13.00 1 1.25 T*9X*D20 UC48D 24 1635 45.0 32.8 13.00 1 1.00 [...]

  • Page 17

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 17 ACCESSORIES Refer to Price Manua l for specific model numbers. Hard St art Kit - Require d when using TXV indoor coil. Also, provides increased starting torque for areas with low voltage. Off Cycle Timer Delay - Provides a 5-minu te off cycle to pre- vent rapid recycling of the compressor . Th[...]

  • Page 18

    556454-YTG-A-0210 18 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe[...]

  • Page 19

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 19 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC18A 0.98 0.98 0.94 T*(8,L)X*B12 FC/MC/PC18B 0.99 1.00 0.93 T*9X*B12 FC/MC/PC18B 0.99 1.02 0.93 T*(8,L)X*A12 FC/MC/PC24A 1.03 1.05 0.94 T*(8,L)X*B12 FC/MC/PC24B 1.02 1.04 0.94 T*9X*B12 FC/MC/PC24B 1.03 1.05 0.94 T*(8,L)X*A12 FC/MC/PC30A 1.03 1.[...]

  • Page 20

    556454-YTG-A-0210 20 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe[...]

  • Page 21

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 21 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC24A 1.02 1.03 0.95 T*(8,L)X*B12 FC/MC/PC24B 1.03 1.05 0.94 T*9X*B12 FC/MC/PC24B 1.02 1.03 0.95 T*(8,L)X*A12 FC/MC/PC30A 1.02 1.02 0.95 T*(8,L)X*B12 FC/MC/PC30B 1.03 1.05 0.94 T*9X*B12 FC/MC/PC30B 1.02 1.02 0.93 T*(8,L)X*A12 FC/MC/PC32A 1.03 1.[...]

  • Page 22

    556454-YTG-A-0210 22 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe[...]

  • Page 23

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 23 Furnaces Co ils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC30A 1.01 1.02 0.97 T*(8,L)X*B12 FC/MC/PC30B 0.99 0.98 0.93 T*9X*B12 FC/MC/PC30B 1.01 1.02 0.97 T*(8,L)X*A12 FC/MC/PC32A 1.00 1.00 0.98 T*(8,L)X*B12 FC/MC/PC35B 1.01 1.04 0.95 T*(8,L)X*C16 FC/MC/PC35C 1.01 1.04 0.94 T*(8,L)X*C20 FC/MC/PC35C 0.9[...]

  • Page 24

    556454-YTG-A-0210 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe[...]

  • Page 25

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 25 Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 F C/MC/PC32A 0.96 0.95 0.98 T*(8,L)X*B12 F C/MC/PC35B 0.98 1.00 0.98 T*(8,L)X*C16 FC/MC/PC35 C 0.99 0.98 0.95 T*(8,L)X*C20 FC/MC/PC35 C 0.99 1.00 0.95 T*9X*B12 FC/MC/PC35B 0.98 1.00 0.98 T*9X*C16 F C/MC/PC35C 0.99 1.01 0.97 T*9X*C20 F C/MC/PC35C 0.99 0[...]

  • Page 26

    556454-YTG-A-0210 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe[...]

  • Page 27

    556454-YTG-A-0210 Johnson Controls Unitary Pro ducts 27 Furnaces Co ils T .C. S.C. KW T*(8,L)X*C16 FC/MC/PC48C 1.00 1.01 1.00 T*(8,L)X*C20 FC/MC/PC48C 1.01 1.02 0.99 T*9X*C16 FC /MC/PC48C 1.00 0.99 1. 00 T*9X*C20 FC /MC/PC48C 1.00 1.01 1. 00 T*9X*D20 FC /MC/PC48D 1.00 1.01 1. 00 T*(8,L)X*C16 FC/PC60C 0.99 0. 99 0.99 T*(8,L)X*C20 FC/PC60C 0.99 0. 99[...]

  • Page 28

    Subject to change without notice. Published in U .S.A. 556454-YTG-A-0210 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than [...]