American Water Heater (A)BCG38T500-8P manual
- Ver online ou baixar oubaixar o manual
- 40 páginas
- 3.88 mb
Ir para a página of
Manuais similares
-
Water Heater
American Water Heater NRXSS00109
2 páginas 0.29 mb -
Water Heater
American Water Heater ATO-305-P
36 páginas 0.51 mb -
Water Heater
American Water Heater BCG3
52 páginas 6.5 mb -
Water Heater
American Water Heater 40-42K BTU
24 páginas 1.38 mb -
Water Heater
American Water Heater VG6250T100
60 páginas 7.09 mb -
Water Heater
American Water Heater ATI-505-P
36 páginas 0.51 mb -
Water Heater
American Water Heater ABCG3
56 páginas 5.45 mb -
Water Heater
American Water Heater 395T2506NOX
32 páginas 4.43 mb
Bom manual de uso
As regras impõem ao revendedor a obrigação de fornecer ao comprador o manual com o produto American Water Heater (A)BCG38T500-8P. A falta de manual ou informações incorretas fornecidas ao consumidor são a base de uma queixa por não conformidade do produto com o contrato. De acordo com a lei, pode anexar o manual em uma outra forma de que em papel, o que é frequentemente utilizado, anexando uma forma gráfica ou manual electrónicoAmerican Water Heater (A)BCG38T500-8P vídeos instrutivos para os usuários. A condição é uma forma legível e compreensível.
O que é a instrução?
A palavra vem do latim "Instructio" ou instruir. Portanto, no manual American Water Heater (A)BCG38T500-8P você pode encontrar uma descrição das fases do processo. O objetivo do manual é instruir, facilitar o arranque, a utilização do equipamento ou a execução de determinadas tarefas. O manual é uma coleção de informações sobre o objeto / serviço, um guia.
Infelizmente, pequenos usuários tomam o tempo para ler o manual American Water Heater (A)BCG38T500-8P, e um bom manual não só permite conhecer uma série de funcionalidades adicionais do dispositivo, mas evita a formação da maioria das falhas.
Então, o que deve conter o manual perfeito?
Primeiro, o manual American Water Heater (A)BCG38T500-8P deve conte:
- dados técnicos do dispositivo American Water Heater (A)BCG38T500-8P
- nome do fabricante e ano de fabricação do dispositivo American Water Heater (A)BCG38T500-8P
- instruções de utilização, regulação e manutenção do dispositivo American Water Heater (A)BCG38T500-8P
- sinais de segurança e certificados que comprovam a conformidade com as normas pertinentes
Por que você não ler manuais?
Normalmente, isso é devido à falta de tempo e à certeza quanto à funcionalidade específica do dispositivo adquirido. Infelizmente, a mesma ligação e o arranque American Water Heater (A)BCG38T500-8P não são suficientes. O manual contém uma série de orientações sobre funcionalidades específicas, a segurança, os métodos de manutenção (mesmo sobre produtos que devem ser usados), possíveis defeitos American Water Heater (A)BCG38T500-8P e formas de resolver problemas comuns durante o uso. No final, no manual podemos encontrar as coordenadas do serviço American Water Heater na ausência da eficácia das soluções propostas. Atualmente, muito apreciados são manuais na forma de animações interessantes e vídeos de instrução que de uma forma melhor do que o o folheto falam ao usuário. Este tipo de manual é a chance que o usuário percorrer todo o vídeo instrutivo, sem ignorar especificações e descrições técnicas complicadas American Water Heater (A)BCG38T500-8P, como para a versão papel.
Por que ler manuais?
Primeiro de tudo, contem a resposta sobre a construção, as possibilidades do dispositivo American Water Heater (A)BCG38T500-8P, uso dos acessórios individuais e uma gama de informações para desfrutar plenamente todos os recursos e facilidades.
Após a compra bem sucedida de um equipamento / dispositivo, é bom ter um momento para se familiarizar com cada parte do manual American Water Heater (A)BCG38T500-8P. Atualmente, são cuidadosamente preparados e traduzidos para sejam não só compreensíveis para os usuários, mas para cumprir a sua função básica de informação
Índice do manual
-
Página 1
1 Service Handbook PRINTED IN THE U . S .A 0510 318664-000 SERVICING SHOULD ONL Y BE PERFORMED BY A QUALIFIED SER VICE AGENT . COMMERCIAL GAS W A TER HEA TERS INST ALLA TION CONSIDERA TIONS - PRE SERVICE CHECKS - W A TER HEA TER CONSTRUCTION - OPERA TION & SERVICE - TROUBLESHOOTING P.O. Box 1597 Johnson City, TN 37605 INST ALLA TION CONSIDERA T[...]
-
Página 2
2 Servicing should only be performed by a Quali fi ed Service Agent INTRODUCTION ............................................................3 Qualifications ........................................................... 3 Service W arning........................................................3 Service Reminder ......................................[...]
-
Página 3
3 Servicing should only be performed by a Quali fi ed Service Agent INTRODUCTION INTRODUCTION This Service Manual is designed to be an aid in servicing and troubleshooting American models (A)BCG385T500-8N/8P Series 120/121 commercial water heaters. The instructions and illustrations contained in this service manual will provide you with troublesho[...]
-
Página 4
4 Servicing should only be performed by a Quali fi ed Service Agent REQUIREMENTS REQUIREMENTS INSTRUCTION MANUAL Have a copy of the instruction manual that came with the water heater on hand for the model being serviced. Instruction manuals can be obtained at the American W ater Heaters web site (www .americanwaterheater .com) or by calling techni[...]
-
Página 5
5 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS INST ALLA TION CONSIDERA TIONS Installation information given in this service manual IS NOT a complete installation instruction. Installation information covered in this service manual has a limited focus as it applies to servicing. This service manu[...]
-
Página 6
6 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS AIR REQUIREMENTS Carefully review the requirements for combustion and ventilation air in the instruction manual that came with the water heater . Failure to meet these requirements when the water heater is installed or overlooking their importance wh[...]
-
Página 7
7 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS Insufficient Make-up Air , Negative Air Pressure, and Downdrafts A lack of combustion and ventilation air can create a negative ambient air pressure in the installed space. The vent system on one or more gas fired appliances can experience down draft[...]
-
Página 8
8 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS Make-up Air: Direct Communication with Outdoors A fresh supply of make-up air for combustion can be supplied to the water heater through make-up air ducts, which directly communicate with the outdoors. (Not Direct V ent.) T wo openings are required: [...]
-
Página 9
9 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS Contaminated Air Carefully review the warnings concerning contaminated combustion and ventilation air in the instruction manual that came with the water heater . Combustion air that is contaminated can greatly diminish the life span of the water heat[...]
-
Página 10
10 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS T able 2 MINIMUM CLEARANCES T O COMBUSTIBLE SURF ACES “A” - Right Side “B” - Left Side “C” - Back 5” (12.7 cm) 5” (12.7 cm) 5” (12.7 cm) A, B, and C clearances to non-combustible surfaces is “0” inches. A 20” clearance to cov[...]
-
Página 11
11 Servicing should only be performed by a Quali fi ed Service Agent INST ALLA TION CONSIDERA TIONS VENTING The (A)BCG385T500-8N/8P water heater is classified by ANSI as a Category I (non- condensing, negative pressure venting) appliance. It is approved for type B vent. The blower (draft inducer) does not pressurize the exhaust. NOTE: This section[...]
-
Página 12
12 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE OPERA TION AND SER VICE SEQUENCE OF OPERA TION 1. Call for heat is activated when temperature sensed from Thermistor Probes falls below the Thermostat setting. 2. Blower (Draft Inducer) is energized. 3. Ignition Control Board verifies that the Blower Prover[...]
-
Página 13
13 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE ELECTRICAL SEQUENCE 1. Switch Power on to unit. 2. Thermostat calls for heat. 3. Ignition Control Board performs diagnostic check on system components. 4. On completion of diagnostics check, the Ignition Control Board energizes the Blower (Draft Inducer). 5[...]
-
Página 14
14 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE WIRING DIAGRAM THERMOST A T IGNITION BOARD UPPER PROBE/ PROBE THERMOPLASTIC OR EQUIV ALENT . MUST BE REPLACED USE ONL Y TYPE 105 C IF ANY OF THE ORIGINAL WIRE AS SUPPLIED BOARD , DIGIT AL THERMOST A T AND CONTROLS. WHEN EQUIPPED WITH WHITE-RODGERS IGNITION [...]
-
Página 15
15 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE OPERA TING SEQUENCE - FLOW CHART Figure 1 1 Po wer On C a ll for Heat S elf diagnos t ic c hec k is perf ormed ( C orrec t s t at e of Bl ow er Prov er S w it c h and EC O i s v erif ied ) ( polari t y , eart h gr ound , and I gni ter pres enc e are v er if[...]
-
Página 16
16 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE GAS CONTROL V AL VE This gas valve is a 24 volt AC combination-step opening valve. It includes two valves assembled in parallel, connected by a wiring harness. Note that the valves have fixed pressure regulation and are not adjustable. However , the manifol[...]
-
Página 17
17 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE Manifold Pressure Adjustment The main gas regulators are found beneath the silver or black cap screws. (Natural Gas valves have silver caps; Propane valves have a black caps). Remove the caps to access the outlet (manifold) pressure adjustment screw . IMPOR[...]
-
Página 18
18 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE GAS CONTROL V AL VE/BURNER AREA VIEW Honeywell Gas Va l v e Main Burner Shield Rollout Shield Radiation Shield Main Burner with Hot Surface Igniter (HSI) mounted Figure 14 T able 3 HOT SURF ACE IGNITER (HSI) V olts AC Nominal 80 V AC Ohms Resistance 1 1.0 -[...]
-
Página 19
19 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE BLOWER PROVER SWITCH - SETTINGS V ent Connection Exhaust/Outlet Blower Prover Switch Blower (Draft Inducer) Optional Hot W ater Outlet Figure 15 T able 4 BLOWER PROVER SWITCH T ABLE Model Pressure Setting to Close Switch (Inches W .C.) (A)BCG385T500-8N/8P -[...]
-
Página 20
20 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE THERMOST A T AND IGNITION CONTROL BOARD VIEW Figure 16[...]
-
Página 21
21 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE WHITE RODGERS INTEGRA TED CONTROL - THERMOST A T Figure 17 WHITE RODGERS IGNITION CONTROL BOARD Figure 18 Display LED Label Display LEDs T o Upper T emp. Probe T o Ignition Control Board T o Lower T emp. Probe Fuse Pin Number Label 120 V AC from Ignition Co[...]
-
Página 22
22 Servicing should only be performed by a Quali fi ed Service Agent OPERA TION AND SERVICE PRE-SER VICE CHECKLIST Use the following checklist BEFORE you begin servicing the water heater . 1. Have you removed the cover from the controls? • Did you take notice of the status lights on the upper water heater control? • Did you take notice of the [...]
-
Página 23
23 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TROUBLESHOOTING IGNITION CONTROL BOARD: ERROR CODES The White Rodgers ignition control board will display a flashing error code with an LED light located on the upper left corner of the Ignition Control Board (Figure 18) when there is a problem. There is a distinc[...]
-
Página 24
24 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING 3 FLASHES Blower prover (air pressure) switch failed to close its normally open contacts after blower (draft inducer) was energized. Blower will run indefinitely , waiting for the blower prover switch circuit to close. 1 Check air pressure reading at blower prover[...]
-
Página 25
25 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING 4 Check molex plug connector between igniter/flame sensor assembly and control board; Also check flame sense (12 pin) plug connection at control board. 8 FLASHES Igniter not sensed and/or water heater not grounded. 1 T est igniter resistance. It should should be 1[...]
-
Página 26
26 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING INTEGRA TED HEA TER CONTROL: DISPLA Y LIGHTS Power Energy Cut Off Status Call for Heat Reset Status LED ST A TUS INDICA TION ACTION Calling for heat Normal status. No action required. The ECO (Energy Cut-Off) has opened. • Check for excessively hot water (203° [...]
-
Página 27
27 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 1: 120 V AC T O HEA TER CHECK Conditions: • No Green Display “Power” LED on. • Plugs are in receptacles. • Supply power breaker is not open. • On/Off heater switch is on. E2 Display LEDs Ignition Control Board Ground 120 V . (E14) From Heater Cont[...]
-
Página 28
28 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 2: POLARITY CHECK Conditions: No hot water • Green “Power” LED is on. • T ank is more than 5° F below temperature dial setting. • Red ignition control board diagnostic LED is flashing 6 times between pauses. • Red, diagnostic “Call for Heat” [...]
-
Página 29
29 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 3: CONTINUITY CHECK OF HIGH LIMIT (ECO) Conditions: Power On – No Hot W ater • Red, heater control “Call for Heat” LED – on • Red ignition control board diagnostic LED – 4 Flashes • Note LED Flash Code before resetting water heater control. ?[...]
-
Página 30
30 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 4: UPPER TEMPERA TURE PROBE CONTINUITY CHECK Conditions: Power On - W ater below temperature set point. • Red, water heater control “Reset Status” LED-OFF • “Call For Heat” LED off. • TEST 4 Upper T emperature probe continuity check Red wire to [...]
-
Página 31
31 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 5: CALLING FOR HEA T - NO BLOWER OPERA TION Conditions: Power on • Plugs in Receptacles • Red “ Call for Heat” LED - ON • Blower (Draft Inducer) off • Note flash code on ignition control board diagnostic LED. W ater Heater Control - Thermostat Ign[...]
-
Página 32
32 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 6: BLOWER ON, NO IGNITION Conditions: Power on • Plugs in receptacles • Blower (Draft Inducer) operating • No power to Hot Surface Igniter (HSI). Note LED flash code. • Blower Exhaust Blower Prover Switch Blower (Draft Inducer) Hot W ater Outlet Check[...]
-
Página 33
33 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 7: BLOWER ON, BLOWER PROVER SWITCH CLOSED, NO IGNITER OPERA TION Conditions: Power on, but no power to igniter • Plugs in receptacles • Blower (Draft Inducer) on • 24V at ignition board E1, Pin 10 • 1 2 3 4 E4 Plug Continuity T est Check E1 pin 10 - 2[...]
-
Página 34
34 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 8: IGNITER HEA TS, NO MAIN BURNER 24 V . E1 Plug to Pin 9 E1 Plug to Pin 12 Figure 27 TEST 8 IGNITER HEA TS......NO MAIN BURNER IF ......... then............ short heat up time of igniter check control box grounding. Normal warm up (Approximately 20 seconds) [...]
-
Página 35
35 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 9: IGNITER HEA TS, NO MAIN BURNER Conditions: T est 8 completed • T urn off power • Disconnect wires from gas valve • Inlet Outlet Manifold Pressure Ta p Measure Resistance Between Gas V alve T erminals (Main V alve Solenoid Connections) Manifold Pressu[...]
-
Página 36
36 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 10: MAIN BURNER IGNITION FOR LESS THAN FIVE SECONDS Conditions: Power On; plug connected • Main Burner ignites for approximately five seconds, then goes out. • T ests 8 and 9 completed • Note the flash code on the ignition board LED. Hot Surface Igniter[...]
-
Página 37
37 Servicing should only be performed by a Quali fi ed Service Agent TROUBLESHOOTING TEST 1 1: W A TER HEA TER SHUTTING OFF BELOW SETTING Conditions: Main burner ignited • Stored water is below temperature setting more than 5° F (T ank Average). • Power off • Plug disconnected from heater control board receptacle E3 and E4 • E3 E4 Figure [...]
-
Página 38
38 Servicing should only be performed by a Quali fi ed Service Agent NOTES[...]
-