Ir para a página of
Manuais similares
-
Uninterruptible power supply (
BlueWalker PowerWalker VFI 2000RM LCD
140 páginas -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 2000 LCD
141 páginas -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 2000RT LCD
44 páginas -
Uninterruptible power supply (
BlueWalker PowerWalker VI 1200
32 páginas -
Uninterruptible power supply (
BlueWalker VFI 1000R LCD
98 páginas -
Uninterruptible power supply (
BlueWalker VFI 1500R LCD
97 páginas -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 10000C LCD
16 páginas -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 3000 LCD
141 páginas
Bom manual de uso
As regras impõem ao revendedor a obrigação de fornecer ao comprador o manual com o produto BlueWalker 10120176. A falta de manual ou informações incorretas fornecidas ao consumidor são a base de uma queixa por não conformidade do produto com o contrato. De acordo com a lei, pode anexar o manual em uma outra forma de que em papel, o que é frequentemente utilizado, anexando uma forma gráfica ou manual electrónicoBlueWalker 10120176 vídeos instrutivos para os usuários. A condição é uma forma legível e compreensível.
O que é a instrução?
A palavra vem do latim "Instructio" ou instruir. Portanto, no manual BlueWalker 10120176 você pode encontrar uma descrição das fases do processo. O objetivo do manual é instruir, facilitar o arranque, a utilização do equipamento ou a execução de determinadas tarefas. O manual é uma coleção de informações sobre o objeto / serviço, um guia.
Infelizmente, pequenos usuários tomam o tempo para ler o manual BlueWalker 10120176, e um bom manual não só permite conhecer uma série de funcionalidades adicionais do dispositivo, mas evita a formação da maioria das falhas.
Então, o que deve conter o manual perfeito?
Primeiro, o manual BlueWalker 10120176 deve conte:
- dados técnicos do dispositivo BlueWalker 10120176
- nome do fabricante e ano de fabricação do dispositivo BlueWalker 10120176
- instruções de utilização, regulação e manutenção do dispositivo BlueWalker 10120176
- sinais de segurança e certificados que comprovam a conformidade com as normas pertinentes
Por que você não ler manuais?
Normalmente, isso é devido à falta de tempo e à certeza quanto à funcionalidade específica do dispositivo adquirido. Infelizmente, a mesma ligação e o arranque BlueWalker 10120176 não são suficientes. O manual contém uma série de orientações sobre funcionalidades específicas, a segurança, os métodos de manutenção (mesmo sobre produtos que devem ser usados), possíveis defeitos BlueWalker 10120176 e formas de resolver problemas comuns durante o uso. No final, no manual podemos encontrar as coordenadas do serviço BlueWalker na ausência da eficácia das soluções propostas. Atualmente, muito apreciados são manuais na forma de animações interessantes e vídeos de instrução que de uma forma melhor do que o o folheto falam ao usuário. Este tipo de manual é a chance que o usuário percorrer todo o vídeo instrutivo, sem ignorar especificações e descrições técnicas complicadas BlueWalker 10120176, como para a versão papel.
Por que ler manuais?
Primeiro de tudo, contem a resposta sobre a construção, as possibilidades do dispositivo BlueWalker 10120176, uso dos acessórios individuais e uma gama de informações para desfrutar plenamente todos os recursos e facilidades.
Após a compra bem sucedida de um equipamento / dispositivo, é bom ter um momento para se familiarizar com cada parte do manual BlueWalker 10120176. Atualmente, são cuidadosamente preparados e traduzidos para sejam não só compreensíveis para os usuários, mas para cumprir a sua função básica de informação
Índice do manual
-
Página 1
PowerW alker VFI 3/3 Series VFI 30000TP/40000TP 3/3 BE/BI 380/400/415V 50/60Hz (3-phase input/output) User Guide[...]
-
Página 2
[...]
-
Página 3
EN ©2013 BlueW alker GmbH All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to mak[...]
-
Página 4
4.1 De li v e ry ch e ck …………………………………………………… ………………… 4 .2 U n p ac k in g an d visual i ns p ec ti on … … ……… … …… … …… … ……… … …… 4. 3 P lann i n g be fo re install ati on ………………… …… ……… …… ……… ………… 4 .4 C a b inet i[...]
-
Página 5
EN R ec ycli n g th e us ed U PS o r ba tte ry …… ………… …… …… …… ………… …… Maint en an ce ………………… ………… ………… …………………… ………… …… P arall el syste ms … …… …… . … … …… …… …… ……… …… …… …… …… … …… 8. 9. 10. Elec t[...]
-
Página 6
1 1 Safety instructions W arning! Operations inside the UPS must be performed by a service engineer from the manufac- turer or from an agent authorised by the manufacturer . 1.1 Safety caution Use the optional Maintenance Bypass Switch (MBS) for service inside the UPS when in - stalled to the system. Remember to open battery cabinet(s) breaker . Al[...]
-
Página 7
2 EN 1.3 CE marking The product has the CE marking in compliance with the following European directives: L VD Directive (Safety) 2006/95/EEC EMC Directive 2004/108/EEC The only user operations permitted are: Start up and shut down the UPS, excluding the commissioning start-up.Use of the LCD con - trol panel and Emergency Power Off (EPO) switch.Use [...]
-
Página 8
3 1.5 Environment The UPS must be installed according to the recommendations in this manual.Under no cir - cumstances the UPS should be installed in an airtight room, in the presence of ammable gases, or in an environment exceeding the specication.Excessive amount of dust in the operating environment of UPS may cause damage or lead to malfunc[...]
-
Página 9
4 EN 2 Introduction 2.1 System description PowerW alker VFI 3/3 Series products are high-efficiency and high-performance, double conversion, pure-online and three phase input and three phase output UPS, with unit capacity ranging between 20KV A-40KV A. Categorized by capacity , the products can be further divided into 20KV A, 30KV A and 40KV A. Thi[...]
-
Página 10
5 2.2 Basic system conguration 2.3 Panel gure[...]
-
Página 11
6 EN 2.4 Exterior view ① AC: This light and inverter light will turn "green" when UPS is powered by Rectier Input; ② Inverter: This light will turn "green" when UPS load is through the inverter; ③ Battery: This light will turn "yellow" when UPS is powered by batteries; ④ Bypass: This light will turn "gr[...]
-
Página 12
7 CHGR F AN Front view(door open) Battery trays[...]
-
Página 13
8 EN W × D × H (mm) 3 T echnical data 3.1 Standards Product IEC62040-3:1999 and EN62040-3:2001 UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Safety IEC62040-1:2008,EN62040-1:2003 and EN60950-1:2005 EMC IEC62040-2:2006 and EN62040-2:2005 3.2 Environment 0 ℃ ~ +40 ℃ (with batteries) Working T emperature 0 ℃ ~ +40 ℃ Storage T emperatur[...]
-
Página 14
9 3.5 AC input 3.4 Characteristics VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Noise (ISO 7779) <57dB at 75% load Efciency-nominal load Up to 92% V oltage (L-N) 121V -274 V olts without using battery Rectier input 3 phases + N Bypass input 3 phases + N Frequency 40-70 Hz Rated input voltage 380V/400 V/415V Power factor 0.99 Input distortio[...]
-
Página 15
10 EN 3.7 AC output 3.8 Battery and Charger Internal battery package Panasonic LC-RW 1245W / CSB HR 1234WF2 Dimensions 94*151*64.5/pc(Panasonic) 94*151*65/pc(CSB) Strings 2 x 16 Charger Input Protection 8 A fuse Rated Charge V oltage ± 216V Default for Integrated bettery Initial Charging Current 4.5A Battery Leakage < 3.5mA Battery protection 1[...]
-
Página 16
11 4 Mechanical installation 4.1 Delivery check The UPS and accessories are delivered on a specically designed pallet that is easy to move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not stack the pallets. The UPS is delivered with the following items: 1. Winpower disc 2.RS-232 seri[...]
-
Página 17
12 EN Check the information on the type designation label of the equipment to verify that the unit is of the correct type. The type designation label includes ratings, a CE marking, a type code, a part number and a serial number . The serial number is important when making inquiries. It allows individual recognition of the equipment.[...]
-
Página 18
13 Preparation for installation. 1. A void extremes of ambient temperature; excessive dust, moisture or vibration; ammable gases; and corrosive or explosive atmospheres. 2.Altitude for normal UPS function should not exceed 1000m. 3.The battery cabinet should work within a temperature range from15 ℃ to 25 ℃ . 4.The maximum ambient temperature[...]
-
Página 19
14 EN Caution! UPS cabinet(s) can fall over if the installation brake pads are not used. Both rear and front pads must be used to secure the UPS cabinet to the oor . Use a 19mm wrench in clockwise direction to screw the brake pad down to the ground, keeping the machine from moving. 4.5 Maintenance Bypass Switch(MBS) The operation of the MBS is a[...]
-
Página 20
15 The normal positions of the MBS switches. The switching sequence for circuit breaker from normal position to maintenance position:[...]
-
Página 21
16 EN The maintenance positions of the MBS switches 2.Use LCD to turn the UPS from normal mode to bypass mode: Switch-off action (press ESC to exit above picture) T ransfer UPS from normal mode to maintenance bypass mode: 1.The normal start position should be following:[...]
-
Página 22
17 1)Switch-off picture 2)If it is in single machine mode, the following will appear Remember to verify the transfer before proceeding the next step. 3.Remove the locking plate of maintenance switch. 4.T urn OFF the Rectier Input switch and battery breaker. 5.T urn the Maintenance switch to “ MAINTENANCE ” side. 6.T urn OFF the Bypass Input [...]
-
Página 23
18 EN 7.UPS is now in the maintenance bypass mode, see below (Note: the Serv disconnect i.e. battery breaker must be turned off): T ransfer UPS from maintenance bypass mode to normal mode: 1.The normal start position should be following: When the LED of bypass turns green,the UPS enters into bypass mode. 3.T urn the Maintenance switch to “ UPS ?[...]
-
Página 24
19 Then the UPS turn to bypass mode. 4.T urn ON the Rectier Input switch and battery breaker. 5.Use LCD to turn the UPS from bypass mode to normal mode: Switch-off action (press ESC to exit above picture) 1)Switch-on picture 2)Press ENTER[...]
-
Página 25
20 EN 6.UPS is now in the normal mode,see below: 7.Remount the locking plate of maintenance switch to the position to prevent the use of it.[...]
-
Página 26
21 5 Electrical installation 5.1 Electrical Preparations The UPS unit has the following power connections: Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the rectier input. Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the bypass input ( N is INTERNALL Y common for rectier and b[...]
-
Página 27
22 EN 1.If UPS rectier input and bypass input are supplied from two mains: Connect the mains 1 supply cables to the UPS rectier input terminals L1, L2, L3, N and PE. Connect the mains 2 supply cables to the UPS bypass input terminals L1, L2, L3, N and PE. 8 blue wires (B14, B15, B16, and B18) for BA TN connection; 56 black wires (B1) with an [...]
-
Página 28
23 T erminal block diagram W arning! High touch current earth connection essential before connecting supply . 2.If UPS rectier input and bypass input are supplied from one mains only: Connect the mains supply cables to the UPS rectier input terminals L1, L2, L3, N and PE . The following three jumpers must be xed between the rectier and [...]
-
Página 29
24 EN The conductor cross sections apply for maximum currents: (1) For PVC-insulated copper cables (at 70 ℃ ) (2) When routed in conduits for electrical installations (3) When air temperature surrounding the conduits does not exceed 30 ℃ (4) For cable lengths up to 30 m Connect the Protective Earthing (PE) cable rst. Connect other cables as [...]
-
Página 30
25 Routing of communication cables or data lines should be kept separate from the UPS input, output, and external battery cables. Use cable cross section and protective device specication Model VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Rectier Input L1, L2, L3, N, Bypass Input L1, L2, L3, N, min. conductor cross section[mm ] 10 16 max. poss[...]
-
Página 31
26 EN Notice! The following label must be displayed on all switching devices installed in the same electrical system as the UPS, even when these are located at a distance from the area in which it is located (according to European standard EN 62040-1). W arning! ENSURE THA T THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLA TED BE - FORE WORKING ON THIS CI[...]
-
Página 32
27 Step1: Put batteries into the trays (see Fig. 2). Fig. 2 3. Assemble the battery packs.There are eight batteries in each battery pack, four packs in each shelf and total is four shelves. Step2: connect the wires between the batteries (see Fig. 3). Fig. 3 Front Back[...]
-
Página 33
28 EN Step3: Install the top tray downward, and fold both the top and bottom tray anges (see Fig 5). Fig. 5 Please refer to the following gure(Fig.4) for wire connections of the four battery packs. Fig. 4[...]
-
Página 34
29 Step4: T ape two sides (see Fig.6 ).Make sure the cable is placed between the tray edges during tape mounting. Fig. 6 Front Back Battery Pack Assembly Step5: Paste the labels to the battery packs (see Fig. 7). Fig. 7[...]
-
Página 35
30 EN 4. Put the battery packs into the enclosure from left to right and bottom to top and cover each shelf with a x-plate(see Fig. 9) (please refer to Fig.4 for correspending battery packs). Fig. 9 Make sure to paste the correct label to each battery pack and the battery packs are placed conformably with the labels, i.e. the battery terminals a[...]
-
Página 36
31 5. Connect the cables to each shelf respectively (see Fig. 10). REMARK: MAKE SURE TO CONNECT WIRES WITH THE SAME COLOR. Fig. 10[...]
-
Página 37
32 EN Fig.1 1 6. Secure each x-plate with four screws (see Fig. 1 1). 7. T ie up the wires properly(see Fig. 12). Fig.12[...]
-
Página 38
33 8. Reinstall the battery cover and secure it with the eighteen screws. 8 8[...]
-
Página 39
34 EN Notice! The most common battery type used in UPS installations is the valve regulated bat - tery . V alve regulated cells are not sealed. The amount of gas given off is less than for ooded cells, but when planning the battery installation, allowance must be made for adequate ventilation and heat dissipation. V alve regulat ed cells are not[...]
-
Página 40
35 5.6 Connections between battery cabinet and UPS Make sure the Protective Earthing (PE) connected rst. External Battery Cabinet Connections Notice! The requirements of the EC directives are satised when battery cabinet are used with original accessories. If alternative batteries are used, you must ensure that the appli - cable EC directives[...]
-
Página 41
36 EN Exchanging batteries W arning! If a battery cabinet has been disconnected and is to be reconnected, the battery isola - tor may only be reconnected after you have made certain that voltage with the correct polarity is present on both sides of isolating device. Connecting external battery cabinet W arning! Before replacing batteries, make sure[...]
-
Página 42
37 6 Software and connectivity The Series provide Intelligent Slot, Expanded Slot, P ARALLEL, AS400, EPO, RS485 and RS232 as well as SERVICE Supervising Communication Interface exclusively available to PowerW alker technical personnel. 2 6 8 1 5 P ARALLEL Intelligent slot Expanded slot AS400 EPO SERVICE RS485 RS232 3 4 7 P ARALLEL 1. Intelligent sl[...]
-
Página 43
38 EN RS232 port RS485 port[...]
-
Página 44
39 AS400 port Note! The UPS have to be manually reset if remote shutdown occurs.[...]
-
Página 45
40 EN 7 User operations 7.1 Single machine operation W arning! High touch current earth connection essential before connecting supply . The only user operations permitted are: Start up and shut down the UPS, excluding the commissioning start-up. Use of the LCD control panel and Emergency Power Off (EPO) switch. Use of optional connectivity modules [...]
-
Página 46
41 3)Press ESC to access or automatically within 1min with no button being pressed 4)Press ▼ to obtain the below informa - tion Remark: the following drawing takes PowerW alker VFI 30000TP 3/3 BE/BI as an example and statistics are only for reference. 1)Power on 2)Automatic access within about 4s 36 POWERWALKER VFI 3 0000TP 3/3[...]
-
Página 47
42 EN 5)Press ▼ again to obtain the below 6)Press ▼ again to obtain the below information information 7)Press ▼ again to obtain the below 8)Press ▼ again to obtain the below information information VFI 3 0000TP 3/3[...]
-
Página 48
43 1)Switch-on picture 2)Press ENTER 4. Start-up action (press ESC to exit the above picture) Note! If malfunction occurs, “x” will appear at the lower right corner of the display ,while a warning occurs, “ ” will appear at the same position (as illustrated in the below pic - ture with battery mode as an example).[...]
-
Página 49
44 EN 3)Select “Y es, Conrm” to switch on 4)Normal Switch-on the machine 5)Battery power supply (switch off line input switch)[...]
-
Página 50
45 3)If it is in parallel machine mode, the 4)Press ENTER following will appear 5. Switch-off action (press ESC to exit above picture) 1)Switch-off picture 2)If it is in single machine mode, the following will appear[...]
-
Página 51
46 EN 5)Select “Y es, Conrm” to switch of f 6)Normal Switch-off the machine Note! If you intend to switch off only one set of UPS among the parallel machine system, se - lect “single machine switch-off”; if switch-off is intended for the entire parallel machine system, select “parallel machine switch-off”. 6. Help 1)Help picture 2)Pr[...]
-
Página 52
47 3)Enter respective password 4)Select action item 8. The Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply . DC switch-on and off are available by following instruc - tions appearing in the pictures. 1)Action display (bypass power supply) 2) Press ▼ 7. Conguration (press ESC to[...]
-
Página 53
48 EN 9. Procedures of DC switch-on: Activate DC switch-on function set under UPS bypass mode Make sure that “+”, “-” and “N” wires of batteries are properly connected to UPS Switch on batteries Lightly touch ENTER Manually conduct switch-on order within about 1min after LCD self-inspection 7.2 Parallel machine operation Redundancy intr[...]
-
Página 54
49 Parallel machine wire connection drawing(one battery supply) Parallel machine wire connection drawing(separate battery supply)[...]
-
Página 55
50 EN Single machine wire connection drawing[...]
-
Página 56
51 PowerW alker VFI 30000TP , 40000TP 3/3 BE/BI requires minimum maintenance. 1. If battery is switched off, loaded equipments will not be covered for power-of f protection. 2. Make sure UPS vent are properly ventilated and clean side frames and fan vents from dusts every half a year (switch off AC, battery cabinet and internal battery fuse prior t[...]
-
Página 57
52 EN Remark: A. Prior to battery replacement, switch off UPS and remove it from AC and battery , take of f internal battery breaker . B. T ake off metallic articles such as rings and watches. C. Use screw drivers equipped with insulated handles and do not place tools or other metal - lic substances on the batteries. D. Short circuit or reverse con[...]
-
Página 58
53 8.2 Regular service/intervals The UPS requires very little maintenance if installed in an appropriate environment. In order to ensure maximum availability of the UPS, manufacturer recommends signing a proactive service agreement with a local authorised service provider . Batteries test 18 months Maintenance Interval Batteries change 3-5 years or[...]
-
Página 59
54 EN 9 Parallel systems Parallel is only connected to identical ports for the UPS of same models and kV A rating. 1) Follow installation instructions for general installation requirements. 2)V entilation spacing between machines should allow for service access. 3) Input wiring for each set of UPS should follow the requirements for that of single u[...]
-
Página 60
55 Note! Parallel signal cable should be connected as a loop.[...]
-
Página 61
56 EN 1 1 Display reference T able[...]
-
Página 62
57 Should any display or warning message excluded in the above table be found,please con - tact distributor or call PowerW alker Hot line for advice. ● Indicator light is on ★ Indicator light ashes Warning include one or more than one of these: 1.EPO active 2.Line loss 3.Neutral loss 4.Line phase error 5.Bypass loss 6.Bypass phase error 7.Ba[...]
-
Página 63
[...]
-
Página 64
614-01719-00[...]