3Com 6416SW инструкция обслуживания

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221

Идти на страницу of

Хорошее руководство по эксплуатации

Законодательство обязывает продавца передать покупателю, вместе с товаром, руководство по эксплуатации 3Com 6416SW. Отсутствие инструкции либо неправильная информация, переданная потребителю, составляют основание для рекламации в связи с несоответствием устройства с договором. В законодательстве допускается предоставлении руководства в другой, чем бумажная форме, что, в последнее время, часто используется, предоставляя графическую или электронную форму инструкции 3Com 6416SW или обучающее видео для пользователей. Условием остается четкая и понятная форма.

Что такое руководство?

Слово происходит от латинского "instructio", тоесть привести в порядок. Следовательно в инструкции 3Com 6416SW можно найти описание этапов поведения. Цель инструкции заключается в облегчении запуска, использования оборудования либо выполнения определенной деятельности. Инструкция является набором информации о предмете/услуге, подсказкой.

К сожалению немного пользователей находит время для чтения инструкций 3Com 6416SW, и хорошая инструкция позволяет не только узнать ряд дополнительных функций приобретенного устройства, но и позволяет избежать возникновения большинства поломок.

Из чего должно состоять идеальное руководство по эксплуатации?

Прежде всего в инструкции 3Com 6416SW должна находится:
- информация относительно технических данных устройства 3Com 6416SW
- название производителя и год производства оборудования 3Com 6416SW
- правила обслуживания, настройки и ухода за оборудованием 3Com 6416SW
- знаки безопасности и сертификаты, подтверждающие соответствие стандартам

Почему мы не читаем инструкций?

Как правило из-за нехватки времени и уверенности в отдельных функциональностях приобретенных устройств. К сожалению само подсоединение и запуск 3Com 6416SW это слишком мало. Инструкция заключает ряд отдельных указаний, касающихся функциональности, принципов безопасности, способов ухода (даже то, какие средства стоит использовать), возможных поломок 3Com 6416SW и способов решения проблем, возникающих во время использования. И наконец то, в инструкции можно найти адресные данные сайта 3Com, в случае отсутствия эффективности предлагаемых решений. Сейчас очень большой популярностью пользуются инструкции в форме интересных анимаций или видео материалов, которое лучше, чем брошюра воспринимаются пользователем. Такой вид инструкции позволяет пользователю просмотреть весь фильм, не пропуская спецификацию и сложные технические описания 3Com 6416SW, как это часто бывает в случае бумажной версии.

Почему стоит читать инструкции?

Прежде всего здесь мы найдем ответы касательно конструкции, возможностей устройства 3Com 6416SW, использования отдельных аксессуаров и ряд информации, позволяющей вполне использовать все функции и упрощения.

После удачной покупки оборудования/устройства стоит посвятить несколько минут для ознакомления с каждой частью инструкции 3Com 6416SW. Сейчас их старательно готовят или переводят, чтобы они были не только понятными для пользователя, но и чтобы выполняли свою основную информационно-поддерживающую функцию.

Содержание руководства

  • Страница 1

    ONcore ATM Switch/Control Module Installation and User's Guide Document Number: 17-00616-3 Printed March 1996 Model Number: 6416SW 3Com Corporation 118 Turnpike Road Southborough, MA 01772-1886 U.S.A. (508) 460-8900 FAX: (508) 460-8950[...]

  • Страница 2

    Federal Communication Commission Notice This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, u[...]

  • Страница 3

    This is to certify that the (6416SW) is shielded against radio interference in accordance with the provisions of Vfg 243/1991. The German Postal Services have been advised that this equipment is being placed on the market and that they have been given the right to inspect the series for compliance with regulations. Compliance with applicable regula[...]

  • Страница 4

    Fiber Cable Classification Use this equipment only with fiber cable classified by Underwriters Laboratories as to fire and smoke characteristics in accordance with section 770-2(b) and Section 725-2(b) of the National Electrical Code. UK General Approval Statement The ONline System Concentrator and the ONcore Switching Hub are manufactured to the I[...]

  • Страница 5

    The following terms are trademarks or service marks of the IBM Corporation in the United States or other countries: AIX, AIXwindows, IBM, NetView for AIX, Nways and RISC System 6000. XNS is a trademark and Ethernet is a registered trademark of Xerox Corporation. v[...]

  • Страница 6

    vi ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 7

    Contents Chapter 1. Introduction to ATM ..................... 1-1 3Com ONcore ATM Subsystem ...................... 1-2 ATM Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 ATM Switch/Control Module ....................... 1-6 ATM Subsystem Traffic Management ................ 1-11 ATM Subsystem Chassis Management ...........[...]

  • Страница 8

    Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 Before You Start ............................... 4-3 Entering 6416SW Commands ...................... 4-3 Keyboard Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 [...]

  • Страница 9

    Default Gateway (IP & LE) ....................... 5-21 ARP Server (IP only) .......................... 5-21 Community Table (IP & LE) ...................... 5-22 Alerts (IP & LE) ............................. 5-22 Setting the LECS ATM Address ..................... 5-23 Saving Configuration Settings and Logging Off ............ 5-25 Work[...]

  • Страница 10

    ONcore Cannot PING the ARP Servers and Vice-versa ...... 7-25 ONcore Hub Cannot PING an ARP Client .............. 7-27 ONcore LEC Cannot PING another Client and Vice-versa .... 7-28 ARP Client Cannot PING the ARP Server .............. 7-29 Two Devices Using IP Over a PVC Cannot Ping Each Other ... 7-30 ONcore LEC Cannot Initialize to the LES/BUS ..[...]

  • Страница 11

    Appendix D. Configuring AIX for Download and Upload Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1 Appendix E. ONcore ATM Address Formats ............. E-1 Network Prefix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-3 End System Part ............................. E-5 Appendix F. Technical Support[...]

  • Страница 12

    xii ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 13

    Figures 1-1. ATM Backplane in the 17-slot 3Com ONcore Hub ...... 1-3 1-2. Wiring Star Topology in ATM Backplane (17-slot model) ... 1-4 2-1. Installing the 6416SW Module in an ONcore Hub ....... 2-3 2-2. ONcore Module Ejectors ..................... 2-4 2-3. Attaching a Terminal to the 6416SW RS-232 Console Port . 2-6 2-4. Front Panel of 6416SW Modu[...]

  • Страница 14

    xiv ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 15

    Tables 1-1. ATM Connections Supported in ONcore Hubs ......... 1-7 1-2. Maximum PING and TELNET Message Lengths ...... 1-15 2-1. Meaning of the 6416SW LEDs ................. 2-10 2-2. RS-232 Console Port Pin Assignments (DB9) ........ 2-13 2-3. RS-232 Auxiliary Port Pin Assignments ............ 2-14 5-1. 6416SW Configuration Commands ..............[...]

  • Страница 16

    xvi ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 17

    How to Use This Guide This guide presents information on how to install and configure the 3Com ONcore ATM Switch/Control Module (Model Number 6414SW) in the 3Com ONcore Switching Hub. It describes how to diagnose and solve problems associated with the operation of the 6416SW module, and describes some of the principles of asynchronous transfer mode[...]

  • Страница 18

    Chapter 3, “ATM Addressing” describes the components of an ATM Campus network, guidelines for defining ATM addresses for the 6416SW, how to set up trunk connections within and between networks, and how to use Permanent Virtual Connections (PVCs). It also describes how to connect a console to the 6416SW module in order to perform configuration t[...]

  • Страница 19

    Appendix E, “ONcore ATM Address Formats” describes the ATM addressing formats. Appendix F, “Technical Support” describes the support services provided by 3Com Corporation. How to Use This Guide xix[...]

  • Страница 20

    Prerequisite Knowledge To understand the information presented in this guide you should be familiar with: Features and characteristics of the 3Com ONcore Switching hub, as described in 3Com ONcore Switching Hub Installation and Operation Guide , 17-00362. Principles of asynchronous transfer mode (ATM) technology ATM Forum UNI Specifications V3.0 an[...]

  • Страница 21

    Conventions Used in This Guide The following text conventions are used in this guide: Text Convention Meaning Example Bold Text emphasis Selective backpressure temporarily stops one virtual connection. Global backpressure temporarily stops an ATM link. Italics Special term This is known as a hot swap . Document titles Refer to the ATM User-Network [...]

  • Страница 22

    Related Documents This section provides information on supporting documentation, including: 3Com Documents Reference Documents 3Com Documents The following documents provide additional information on 3Com products: ONcore Switching Hub Installation and Operation Guide 17-00362 - provides information on the installation, operation, and configuration[...]

  • Страница 23

    Reference Documents The following documents supply related background information: Case, J., Fedor, M., Scoffstall, M., and J. Davin , The Simple Network Management Protocol, RFC 1157, University of Tennessee at Knoxville, Performance Systems International and the MIT Laboratory for Computer Science, May 1990. Rose, M., and K. McCloghrie, Structure[...]

  • Страница 24

    Service and Support 3Com Corporation is committed to providing our customers with a full range of support services to provide maximum network uptime. This section describes: Warranty Information Software Subscription Service Support Warranty Information 3Com products are covered under a limited factory warranty. This warrranty covers defects in the[...]

  • Страница 25

    Note: You can buy SSS for less that a full year period so that all software products have the same renewal date for your convenience. Support 3Com Corporation supports product-related questions through the Customer Support Organization (CSO). CSO is available Monday through Friday from 8:30 am to 8:00 pm, Eastern Time. Technical Support Engineers a[...]

  • Страница 26

    xxvi ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 27

    Chapter 1. Introduction to ATM This chapter presents an overview of the main principles and modes of operation of asynchronous transfer mode (ATM) technology on which the 3Com ONcore ATM Switch/Control (6416SW) module is based. It also describes how ATM is implemented in the 3Com ONcore Switching Hub and shows how an ONcore-based ATM campus network[...]

  • Страница 28

    3Com ONcore ATM Subsystem By interconnecting 3Com ONcore Switching hubs, you can build a private campus network that uses ATM to provide: The backbone structure, with possible extensions to the WAN New LAN capability for attaching workstations and servers with dedicated bandwidth and isochronous transmission. ATM is implemented in the ONcore hub to[...]

  • Страница 29

    ATM Backplane All data transmitted between modules in the ATM subsystem passes through the ATM backplane. Data is switched between ATM media modules in the ATM subsystem by a 6416SW module. 6416SW modules are installed in slot positions 9 and 10 in the ATM backplane of 10-slot models, and slot positions 9 and 10 and/or 11 and 12 in the ATM backplan[...]

  • Страница 30

    The major difference between the ATM backplane and other ONcore hub LAN backplanes is that each ATM media module has a dedicated set of connections to the 6416SW module. This set of dedicated connections constitutes a wiring star topology in which ATM media modules are at the tips of the star and the 6416SW module is at the center. The wiring topol[...]

  • Страница 31

    The main characteristics of the ATM backplane are as follows: Modular structure Full floating ATM media modules Support of two 6416SW modules for reliability and redundancy (in 17-slot models) Full coexistence with existing legacy LAN modules. ATM media modules can be hot-swapped into any open slot. Also, you can remove an ATM module and re-insert [...]

  • Страница 32

    ATM Switch/Control Module The ATM Switch/Contol Module (6416SW) module used in the ONcore hub consists of two cards packaged into a double-slot module: A base card (ATM Switch fabric) that switches cells from one ATM port to another ATM port or to another output link on the same module. ATM cell switching is carried out by means of the Switch integ[...]

  • Страница 33

    The 3Com ONcore Switch imbedded Control Point provides a complete set of functions to control an ATM campus network and to interconnect local ATM networks over ATM wide area networks. The Control Point supports an extensive set of ATM connections, including: Switched (SVC) and permanent (PVC) Point-to-point and point-to-multipoint Reserved Bandwidt[...]

  • Страница 34

    Each 3Com ONcore Switch/Control provides the following functions: Control plane: – Support of ATM signaling (SVCs) according to ATM Forum V3.0 and V3.1 specifications. – Switch-to-switch interface (SSI) based on an extension of the ATM Forum UNI V3.0 as stated in the ATM Forum P-NNI framework – Topology services and route computation based on[...]

  • Страница 35

    Management plane: – Full SNMP support (get, getnext, set, and traps) – MIB-II support – IETF AToMIB – Full Interim Local Management Interface (ILMI) support at UNI and from the network management station – OSPF MIB support for managing topology and route computation – 3Com extension — Hub-specific: switch, modules and ports — Enhanc[...]

  • Страница 36

    The SNMP ATM agent is a function of the Control program in the 6416SW module and implements the ATM MIB defined in the V3.0 UNI Specification of the ATM Forum. The AToMIB is defined by the IETF and by the 3Com extensions. It can be driven by SNMP managers, such as IBM NetView for AIX . The 3Com ATM management application, Transcend ONcore ATM Campu[...]

  • Страница 37

    ATM Subsystem Traffic Management High-speed ATM networks support a variety of applications with different traffic and quality of service (QOS) requirements. For example, multimedia and time critical data applications require guaranteed levels of delay and throughput, while other applications can tolerate variations in delay and throughput (LAN traf[...]

  • Страница 38

    ATM Subsystem Chassis Management Management of the ATM subsystem can be achieved in two ways: Via a Distributed Management Module (DMM) installed in the ONcore hub. Via the 6416SW module, which contains a subset of DMM, when the ONcore hub is only running ATM. (Check the Release Notes for the level of 6416SW code required). Note: If a DMM module is[...]

  • Страница 39

    ATM Switch/Control Redundancy By installing a second 6416SW in a 17-slot hub, a backup to the active 6416SW is provided (check the Release Notes for the level of 6416SW and the level of code required). If the active 6416SW fails, the standby will take over control. The active 6416SW continually updates the tables in the standby 6416SW to ensure tha[...]

  • Страница 40

    Benefits of Using ATM in the ONcore Hub The use of ATM in the ONcore hub offers the following benefits: Use of ATM in local and wide area networks, and in both private and public networks ATM support for multimedia applications and mixed traffic, such as voice, video, and data Extension of current application solutions by providing bandwidth on dem[...]

  • Страница 41

    LAN Emulation Client (LEC) The 6416SW contains an integrated ‘lite’ LEC that provides basic LAN emulation client functions for use by an SNMP agent or for Internet FTP functions. Such functions include Netview, TELNET, and TFTP. The LEC implementation is fully ATM Forum compliant. The maximum length of PING and TELNET messages depends on the ma[...]

  • Страница 42

    1-16 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 43

    Chapter 2. Installation This chapter describes how to install the 6416SW module. Before you unpack the module, please follow the precautions in “Before You Start.” Before You Start Take the following precautions before unpacking the 6416SW module: Do not remove the 6416SW module from its anti-static shielding bag until you are ready to insert i[...]

  • Страница 44

    Unpacking the Module To unpack the 6416SW module, follow these steps: 1. Remove the 6416SW module from the shipping carton. 2. Remove the 6416SW module from the anti-static bag and inspect it for damage. Always handle the module by the faceplate being careful not to touch the internal components. If the module appears damaged, put it back in the an[...]

  • Страница 45

    Installing the 6416SW Module To install a 6416SW module in the ONcore hub, follow these steps: 1. Install the ONcore hub in its rack or on a desktop by following the instructions in the 3Com ONcore Hub Installation Guide (17-00362). 2. Insert the 6416SW module into slots 9 and 10 (or slots 11 and 12 in A17 models) of the hub by matching the top and[...]

  • Страница 46

    4. Close the top and bottom ejectors simultaneously. Figure 2-2. ONcore Module Ejectors 2-4 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 47

    5. Fasten the spring-loaded screws on the front panel of the module to the hub using your fingers. Do not over-tighten. 6. (optional) Press the LED Test button on the Controller module to verify that all LEDs are functional. 7. If you want to use a local console to configure (out-of-band) the ATM subsystem, you must attach an ASCII-type terminal to[...]

  • Страница 48

    STAT STAT RESET RESET MODULE RESET MODULE RESET ACTIVITY ACTIVITY PORT 1 PORT 1 1 1 2 2 3 3 4 4 PORT 2 PORT 2 PORT 3 PORT 3 PORT 4 PORT 4 RS-232 Console port Figure 2-3. Attaching a Terminal to the 6416SW RS-232 Console Port 9. Attach cables to the ATM media modules and ATM user devices you want to use. Then enter 6416SW commands from the console ([...]

  • Страница 49

    Verifying Normal 6416SW Operation After installing the 6416SW module, you can verify that it is operating properly by checking the status of the LEDs and the message displayed on the console screen. The position of the LEDs is shown in Figure 2-4 on page 2-9. The RUNNING LED on the module should light (yellow). The ACTIVE LED should light (yellow) [...]

  • Страница 50

    Front Panel The front panel of the 6416SW module contains: Seven LEDs that show the operating state of the module 9-pin RS-232 Console port 9-pin RS-232 Auxiliary port (reserved for 3Com service personnel) ATM Reset button that resets all ATM modules (6416SW and ATM media) in the ONcore hub. The position of these components on the front panel is sh[...]

  • Страница 51

    Active LED Error LED RS-232 Console Port RS-232 Auxiliary Port Standby LED Maintenance LED Reset LED A TM Reset button (resets all A TM modules and A TM traffic) Running LED RS-232 CONSOLE RS-232 AUXILIARY Wrong Slot LED WRONG SLOT STBY RUNNING ACTIVE MAINT RESET ATM RESET ERROR Figure 2-4. Front Panel of 6416SW Module 2-9[...]

  • Страница 52

    Meaning of the LEDs Table 2-1 shows the meaning of each LED on the front panel of the 6416SW module. Table 2-1 (Page 1 of 2). Meaning of the 6416SW LEDs LED Name Color State Meaning Active Yellow OFF 6416SW module is not able to control ATM traffic and ATM media modules. ON 6416SW module is able to control ATM traffic and ATM media modules. Standby[...]

  • Страница 53

    Table 2-1 (Page 2 of 2). Meaning of the 6416SW LEDs LED Name Color State Meaning Maintenance (MAINT) Yellow OFF 6416SW module is functioning properly. ON Maintenance mode is active. Reset Yellow OFF 6416SW module is functioning properly. ON 6416SW and ATM media modules in hub are being reset. Wrong Slot Yellow OFF Normal operation. ON 6416SW module[...]

  • Страница 54

    ATM Reset Button The ATM Reset button resets the 6416SW and all ATM media modules in the ONcore hub. All data traffic and connections in the ATM subsystem are stopped. Press this button when instructed after you correct an error condition. Before pressing it, be sure to save any configuration settings entered in the current session with the SAVE co[...]

  • Страница 55

    RS-232 Console Port The 9-pin RS-232 Console port (the topmost RS-232 port on the front panel) is a DTE male connector (DB-9) to which a console or modem is connected in order to: Initialize the 6416SW module at installation. Enter 6416SW network management commands (described in the ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide ).[...]

  • Страница 56

    RS-232 Auxiliary Port The 9-pin RS-232 Auxiliary serial port (the bottommost RS-232 port on the front panel) is also a DTE male connector (DB-9). The RS-232 Auxiliary port is reserved for 3Com service engineers. No device should be connected to it during normal hub operation. Table 2-3. RS-232 Auxiliary Port Pin Assignments Pin Number Signal Name 1[...]

  • Страница 57

    Chapter 3. ATM Addressing This chapter describes: The components of an ATM Campus Network Guidelines for defining an ATM Address for the ATM Switch/Control How to set up trunk connections within and between subnetworks How to use Permanent Virtual Connections (PVCs). ATM Campus Networks The purpose of an ATM network is to set up connections between[...]

  • Страница 58

    Figure 3-1. Components of an ATM Campus Network 3-2 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 59

    Network Components The various parts of the ATM address form a hierarchy of network components, as shown in Figure 3-2. Figure 3-2. ATM Address Hierarchy For a full description of the ATM address formats supported by the 6416SW, see Appendix E, “ONcore ATM Address Formats” on page E-1. The terms used to describe the components of an ATM Campus [...]

  • Страница 60

    ATM Subnetwork One or more ATM clusters interconnected using NNI interfaces. An ATM subnetwork is identified by: The first 9 bytes of the network prefix, which are the same for all subnetworks in a Campus Network, plus A 2-byte routing domain number ( RDN ), which is unique within the ATM Campus Network. ATM Cluster One or more ATM subsystems inter[...]

  • Страница 61

    An ATM User Device is identified by: The first 13 bytes of the network prefix, which are the same for all user devices attached to an ATM subsystem, plus A 6-byte End System Identifier ( ESI ), unique within the ATM Subsystem, plus A 1-byte Selector field that may be used by the user device. The 6416SW passes the network prefix of an ATM address to[...]

  • Страница 62

    Network Interfaces ATM standards define three protocols used across the interfaces connecting the components of an ATM campus network: UNI Defines the interface between an ATM User Device (such as a terminal, router, bridge, server, workstation, or concentrator equipped with an ATM adapter) and the ATM network. The ATM subsystem supports the privat[...]

  • Страница 63

    Defining the ATM Address of the 6416SW A default ATM address is provided with the 6416SW. You can continue to use this default address only if you use your 6416SW as a stand-alone ATM switch. If you want to connect the 6416SW to other ATM subsystems, the ATM address must be defined as follows: AFI-RDN The first (leftmost) 11 bytes of the Network Pr[...]

  • Страница 64

    Setting-Up ATM Trunk Connections To configure a trunk between two ATM subnetworks or two ATM clusters in the same subnetwork over a virtual path (VP) service provider, you must configure a logical link between a pair of ATM ports. The ATM ports must both use a network-to-network (NNI) interface and be on the boundary hub of each subnetwork or clust[...]

  • Страница 65

    You can configure multiple logical links over the same physical port. However, you can only configure one logical link (using one pair of ATM ports) for each ATM cluster-to-cluster or subnetwork-to-subnetwork connection. Using Static Routes In an ONcore/CELLplex 4000 ATM network, you can only set a logical link to a cluster number (ACN) that is def[...]

  • Страница 66

    Trunks Between Subnetworks In order to define a logical link between switches in different subnetworks, you must also use the SET STATIC_ROUTE command to associate the address of the boundary hub in the remote cluster with a locally defined ACN. The SET LOGICAL_LINK command then uses this ACN to establish the logical link with the remote cluster. 3[...]

  • Страница 67

    Example: Configuring a Connection Between User Devices When configuring a connection between two ATM user devices attached to different subnetworks (for example, between Workstation D and Workstation E in Figure 3-4 on page 3-12), you must: Configure the route between the clusters in the first subnetwork; for example, between Clusters A and B in su[...]

  • Страница 68

    4. From hub H (boundary hub), enter the SET LOGICAL_LINK command with the ACN for Cluster A. The ATM address of Workstation D is known in Cluster A by the TRS updates. Figure 3-4. Using Static Route Mappings to Connect User Devices Across Subnetworks 3-12 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 69

    Using Permanent Virtual Connections Permanent virtual connections (PVCs) for virtual channel and virtual path connections are created via the SET PVC command. See the ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide for details. 3-13[...]

  • Страница 70

    3-14 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 71

    Chapter 4. Setting-Up and Using a Configuration Console This chapter describes: How to enter commands and get help on the 6416SW configuration console How to set up the 6416SW configuration console in Normal (ASCII) mode How to set up the 6416SW configuration console via a SLIP protocol connection How to access the 6416SW from a remote console via [...]

  • Страница 72

    SLIP mode In SLIP mode, commands are entered via a TELNET session between an IP workstation and the 6416SW. If your workstation supports TFTP, it can also be used as a TFTP server to perform DOWNLOAD and UPLOAD operations between your workstation and the ONcore. (See “Uploading and Downloading Operations” on page 6-5.) Note: If no activity take[...]

  • Страница 73

    Before You Start The following section describes keystrokes and the command syntax to use to enter 6416SW commands from a configuration console. For a complete description of all 6416SW configuration commands, see the ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide . Entering 6416SW Commands By entering commands at the prompt on the [...]

  • Страница 74

    Keyboard Functions When entering 6416SW commands the following keyboard functions are available: Keystroke Function BS or Backspace Moves the cursor one space backward and deletes the character. Enter Runs the command or prompts you to enter missing parameters. Space bar Types the complete 6416SW command. Ctrl + C Cancels the command that is curren[...]

  • Страница 75

    Getting Help To get help on available 6416SW commands, type ? on the command line and press Enter. For example, to see what commands start with the word SAVE , you would enter: @ ONcoreATM > save ? [ ENTER ] The following response is displayed: @ Possible completions: alert all community device lan_emul module_port static_route terminal tftp If [...]

  • Страница 76

    Command Completion The 6416SW management command line accepts abbreviated command input with a facility called command completion . Command completion lets you enter a command and its parameters by typing the minimum number of characters to uniquely identify the command or a parameter. For example, to enter the SAVE command, you only need to type S[...]

  • Страница 77

    Setting Up a Configuration Console in Normal (ASCII) Mode The following procedure sets up the configuration console in Normal mode and logs you on as the system administrator with full access to all 6416SW commands: 1. Connect an ASCII-type terminal to the RS-232 console port on the front panel of the 6416SW. 2. In the terminal’s user guide, loca[...]

  • Страница 78

    Setting Up a Configuration Console in SLIP Mode The procedure that follows sets up the configuration console in SLIP mode and logs you on as the system administrator with full access to all 6416SW commands. Note: A typical workstation includes two serial ports (COM1, COM2): One dedicated to an ASCII-terminal emulator, The other dedicated to an IP s[...]

  • Страница 79

    7. Configure the IP stack SLIP with the IP address of the 6416SW and verify the 6416SW-to-workstation connectivity by issuing a PING request. @ C: ping 9.1 .86.138 [ ENTER ] 8. Start a TELNET session to the 6416SW. @ ONcoreATM > telnet 9.1 .86.139 [ ENTER ] 9. Logon as administrator. The Welcome screen is displayed: @ Password: Welcome to syst[...]

  • Страница 80

    SLIP Support The SLIP function is supported on: TCP/IP for AIX version 3.2.5 TCP/IP V2.1.2 for IBM DOS V7 (no TFTP support) TCP/IP V2.0 for OS/2 V3 (WARP) ChameleonNFS V4.0 for Windows Using TCP/IP for AIX version 3.2.5 1. Enter smitty mkinet 2. Enter serial line INTERNET Network Interface 3. Configure the local and remote IP addresses 4. The mask [...]

  • Страница 81

    Using TCP/IP V2.0 for OS/2 V3 (WARP) 1. Configure the SLIP connection using the TCPIPCFG icon then SLIP. 2. Enable the SLIP interface on the correct COMM port. 3. Keep VJ compression off and use 1000 as MTU size. 4. Configure the local and remote IP addresses. 5. The mask is not required. 6. Configure FTFP server using TCPIPCFG icon thru AUTOSTART [...]

  • Страница 82

    TELNET Sessions Via a Remote Switch The 6416SW’s remote login feature allows you to log on to an 6416SW from a remote configuration console or network workstation that supports the TELNET protocol. You can remotely log on to only one 6416SW at a time. Minimum Local Configuration Before you can log on to the 6416SW from a remote switch, you must p[...]

  • Страница 83

    Logon Procedure You specify the 6416SW by entering its IP address with the TELNET command: @ C: telnet 123.94.2 2.9 [ ENTER ] Once you are connected to the remote switch, you must log on by entering the correct password. Afterwards all the commands you enter are run on the remote module as if entered from a local 6416SW session. To log off from a[...]

  • Страница 84

    Figure 4-1 shows an example of an 6416SW remote login. Note that once you are connected to 6416SW A, you can remotely log on and manage the 6416SW modules in either hub B or hub C. Note: The TELNET protocol is not routable. Modem Modem Hub B Hub C Hub A RS-232 Console Port of a 6416SW Module Figure 4-1. Working in Remote 6416SW Sessions You can set[...]

  • Страница 85

    Reconfiguring 6416SW Configuration Console Settings Carry out the procedures in this section only if you need to connect another device (besides the 6416SW configuration console) to the 6416SW, and if the other device runs at a slower baud rate, uses a different parity, or has a different data bit value than the 6416SW's pre-configured factory[...]

  • Страница 86

    Automatic Modem Hangup If you use a modem to connect to the 6416SW, you can use the SET TERMINAL HANGUP command to automatically hang up the modem connection when you log off the 6416SW. If you do not hang up the modem connection, an unauthorized user can pick up your open session and work in it. The following command shows what to enter to automat[...]

  • Страница 87

    Chapter 5. Configuring the ATM Switch/Control Module This chapter describes: How to enter the commands needed to configure the 6416SW module How to save, modify and revert configuration settings How to use 6416SW commands for fault management. Before beginning the procedures listed below, make sure that: 1. You have installed the 6416SW module corr[...]

  • Страница 88

    Configuration Summary To configure the 6416SW, follow the steps listed below. Each of these steps is described in a subsequent section of this chapter. 1. Set the 6416SW user and administrator passwords. 2. Set the internal clock. 3. Set the local 6416SW parameters such as: Switch name Switch location Service contact information Console prompt Cons[...]

  • Страница 89

    9. If you want external LAN Emulation Configuration Server (LECS) support, configure the LECS ATM address or fixed PVC, depending on the configuration requirements of the LECS and external LECs (workstations, bridges, and so on). 10. Save all the configuration settings for the 6416SW. Some of these procedures are mandatory ; others are recommended.[...]

  • Страница 90

    Table 5-1 (Page 1 of 2). 6416SW Configuration Commands Procedure 6416SW Command Priority Set user and administrator passwords SET DEVICE PASSWORD Mandatory Set the internal clock SET CLOCK Recommended Set 6416SW name SET DEVICE NAME Recommended Set hub location SET DEVICE LOCATION Recommended Set contact information SET DEVICE CONTACT Recommended S[...]

  • Страница 91

    Table 5-1 (Page 2 of 2). 6416SW Configuration Commands Procedure 6416SW Command Priority Set SNMP parameters - Classical IP SET DEVICE IP_ADDRESS SET DEVICE DEFAULT_GATEWAY SET DEVICE ARP_SERVER SET COMMUNITY SET ALERT Mandatory to manage the 6416SW from a Classical IP subnetwork Set SNMP parameters - LAN emulation SET DEVICE LAN_EMULATION_CLIENT S[...]

  • Страница 92

    Setting 6416SW Passwords It is necessary to set two levels of 6416SW passwords: Administrator password that provides access to all 6416SW commands with read-write (configuration) access User password that provides access to a subset of 6416SW commands including most SHOW commands, PING and TELNET. See the ONcore Switching Hub/CELLplex 4000 ATM Comm[...]

  • Страница 93

    @ ONcoreATM > save device Then press Enter. You will need to enter the new administrator password the next time you log on to the 6416SW. Note that you have only ten seconds to enter a password when the Password prompt is displayed. If you do not enter a password, a Timeout message is displayed. To redisplay the Password prompt and start again, [...]

  • Страница 94

    User Passwords 1. Log on to 6416SW using the administrator password. 2. At the management prompt, type the SET DEVICE PASSWORD USER command: ONcoreATM > set device password user Then press Enter. 3. In the next three fields displayed, enter the administrator password and the new user password (up to fifteen characters) twice as shown here: Enter[...]

  • Страница 95

    Setting the Internal Clock You need to set the 6416SW's 24-hour internal clock only once, when you install the 6416SW. When you set the internal clock, you establish a starting time, date, and day. To set the internal clock, enter the SET CLOCK command and specify the time and date parameters. Then press Enter. For example, the following comma[...]

  • Страница 96

    Setting Local 6416SW Parameters The 6416SW is pre-configured with default settings that may need to be changed before you can use the switch. To modify these 6416SW parameters, you must log on using the system administrator password. Then use the SET command to change the values for any of the following: 6416SW name Contact name and location Consol[...]

  • Страница 97

    Service Contact Information After installing and logging on to the 6416SW, you should enter the location of the 6416SW and the name of the appropriate person to contact in case of a failure in the ATM subsystem or with the 6416SW To do so, enter the following commands: SET DEVICE LOCATION to specify where the 6416SW is installed SET DEVICE CONTACT [...]

  • Страница 98

    Console Timeout The TERMINAL TIMEOUT parameter is a safety precaution that lets you specify how long you can remain logged on to the 6416SW console without entering any data from the keyboard. This prevents unauthorized users from accessing the 6416SW if you forget to log off the system. If no keystroke is entered for the time period specified by S[...]

  • Страница 99

    Setting the ATM Address of the 6416SW A default ATM address is provided with the 6416SW. You can use this default address only for a stand-alone (isolated) 6416SW. For all other 6416SW configurations, a new ATM address must be defined. See “Defining the ATM Address of the 6416SW” on page 3-7 for more information. To set the ATM address for the [...]

  • Страница 100

    Connecting ATM media Modules After setting the ATM address, you must connect the ATM media modules to the network. This is necessary because the factory default setting isolates them from receiving network traffic. To connect an ATM media module, you use the SET MODULE command: @ ONcoreATM > set module 3 connected [ ENTER ] Afterwards, you can e[...]

  • Страница 101

    Enabling ATM Ports and Interfaces Before you can use the devices attached to the ATM media ports in the 6416SW, you must enable each port and configure the type of interface used by the port to receive and transmit ATM data. For example, to enable port 2 (‘slot’ 1) as a UNI port: @ ONcoreATM > set port 1.2 enable uni [ ENTER ] You can set a [...]

  • Страница 102

    Setting Up Trunks (Logical Links) To connect the 6416SW to another ATM switch, you must create a trunk using the SET LOGICAL_LINK command. See “Setting-Up ATM Trunk Connections” on page 3-8 for a description of the strategy for setting up trunk links in an ATM network. The ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide also give[...]

  • Страница 103

    Setting SNMP Parameters Carry out the procedures in this section only if you want to manage your ATM subsystem from an SNMP workstation. If you want to manage the ATM subsystem in the 6416SW from an SNMP workstation, you may access the 6416SW through either a Classical IP subnetwork or a LAN Emulation subnetwork. The steps required to set the SNMP [...]

  • Страница 104

    IP Address and Subnetwork Mask (IP only) In order for SNMP to run properly, every device in the network must have a unique IP address and subnetwork mask. In a classical IP subnetwork, you must use the SET DEVICE IP_ADDRESS command to assign a unique IP address and subnetwork mask to the 6416SW For example, the following command sets a unique IP ad[...]

  • Страница 105

    LAN Emulation Client (LE only) In order for SNMP to run properly, every device in the network must have a unique IP address and subnetwork mask. In a LAN emulation subnetwork, you must use the SET DEVICE LAN_EMULATION_CLIENT command to assign a unique IP address and subnetwork mask to the 6416SW. To configure the LEC, use the SET DEVICE LAN_EMULATI[...]

  • Страница 106

    @ ONcoreATM > set device lan_emulation_client eth ip_address 9.1 .2 .55 [ ENTER ] Client starting. ONcoreATM > After the eth parameter, the other parameters may be entered in any order. The first time the SET DEVICE LAN_EMULATION_CLIENT ETH is used, you must configure all four parameters before saving the configuration settings (no default va[...]

  • Страница 107

    Default Gateway (IP & LE) The default gateway is the IP address of the gateway that will receive and forward packets whose addresses are unknown to the ATM subnetwork. The default gateway is useful when sending 6416SW alert packets to a management workstation that is on a different network and is accessible via a router. For example, the follow[...]

  • Страница 108

    Community Table (IP & LE) The Community table defines which SNMP stations in the network can access information from the 6416SW, and which station(s) will receive a trap from the 6416SW when the detects an error. To create an entry in the Community table, you use the SET COMMUNITY command. For example, the following command specifies that a com[...]

  • Страница 109

    Setting the LECS ATM Address To set the ATM address of the LAN emulation configuration server (LECS) enter the SET LAN_EMUL CONFIGURATION_SERVER command. This is to support LECs which get their associated LES ATM address from a LECS. LECs have three possible ways to establish a connection to the LECS: During ILMI, the LEC gets the unicast ATM addre[...]

  • Страница 110

    ACTIVE_WKA The LECS address table is to contain an ATM address to be substituted to the well known address (WKA). There can be only one ACTIVE_WKA entry in the LECS table. The ATM address you specify will be the one selected to be substituted with the WKA (WKA active). If an ACTIVE_WKA entry already exists in the LECS address table, it will no long[...]

  • Страница 111

    Saving Configuration Settings and Logging Off Use the SAVE command to save the last configuration changes made to any of the following parameters: Alert All Community Device LAN_emul Module_port Static_route Terminal TFTP. When you make changes with the SET command, they are activated immediately but are not saved permanently. You must use the SAVE[...]

  • Страница 112

    To save the changes made to an individual parameter, enter the parameter name in the SAVE command. For example, if you changed the type of interface used on an ATM port, you would save this setting as follows: @ ONcoreATM > set port 1.3 enable UNI [ ENTER ] Port set ONcoreATM > save module_port [ ENTER ] ONcoreATM > Note that if you change[...]

  • Страница 113

    When all your configuration changes are saved, log off the console by entering the LOGOUT command and pressing Enter. The system prompts you when you are logged off: @ ONcoreATM > logout [ ENTER ] Bye If, when logging off, you have changed 6416SW configuration parameters but forgotten to save them, the following message appears: @ ONcoreATM >[...]

  • Страница 114

    Working With Configuration Settings The following sections describe how to: Revert to previously saved configuration settings Display the current configuration settings Modify the current configuration settings. Reverting Configuration Changes Use the REVERT command to restore the configuration parameters that were active at the time of the last SA[...]

  • Страница 115

    @ atm2: revert terminal [ ENTER ] Reverting terminal configuration. ONcoreATM > Note that when you enter the REVERT TERMINAL command, you revert all TERMINAL parameters, such as BAUD, DATA_BITS, HANGUP, PARITY, STOP_BITS, and TIMEOUT. Displaying Configuration Settings The 6416SW lets you display your currently configured settings for: Alerts ATM[...]

  • Страница 116

    To do so, use the SHOW command. For example, to view information on the status of the ports in the hub, use the SHOW MODULE ALL command: ONcoreATM > show module all [ ENTER ] Slot Install Connect Operation General Information ---------------------------------------------------------------- 1 Y n n - 2 n n n - 3 n n n - 4 Y Y Y ONcore ATM 1 Mbps [...]

  • Страница 117

    ONcoreATM > show module 4 verbose [ ENTER ] Slot Install Connect Operation General Information -------------------------------------------------- 4 Y Y Y ONcore ATM 1 Mbps Module status: connected / hardware OK enable / normal P/N: F 4FFFF EC level: G 4GGG Manufacture: I 41 Operational FPGA version : 7 Backup FPGA version : 7 Type Mode Status --[...]

  • Страница 118

    Modifying Configuration Settings Using the SET command, you can change the configuration settings for any of the following parameters: Alert ATM_ESI Clock Community Device LAN_emul Logical_link Module Static_route Port PVC Terminal TFTP Trace. Important: Remember that (except for SET CLOCK, ATM_ESI, PVC, TRACE, and LAN_EMUL CONFIGURATION_SERVER) th[...]

  • Страница 119

    Isolating and Reconnecting ATM Media Modules Use the SET MODULE command to: Isolate and reconnect ATM media modules to the ATM network. Enable and disable ATM media modules that are connected to the network. When you isolate an ATM media module from the network, it remains in Reset mode and no activity takes place on it. Its current configuration s[...]

  • Страница 120

    As another example, to display the complete status of ATM port 10, enter: ONcoreATM > show port 1.1 verbose [ ENTER ] 1.1 :SSI enabled UP-OKAY SSI Bandwidth : 25 kbps Connector : RJ45 Media : none Remote device is active IX status : IX OK Port speed : 25 kbps ONcoreATM > 5-34 ONcore ATM Switch/Control Module: Installation and User's Guid[...]

  • Страница 121

    Chapter 6. Network and Switch Management This chapter gives an overview of the management options for the ONcore hub: The three methods for managing the ATM Switch/Control Guidelines for SNMP network management Procedures for uploading and downloading operations. Managing the ATM Subsystem You can manage the ATM subsystem in any of the following wa[...]

  • Страница 122

    SNMP Support In a campus environment managed by the Simple Network Management Protocol (SNMP), the 6416SW module acts as an SNMP agent allowing you to configure all ATM modules in the hub using SNMP. 6416SW software contains a community table with up to ten IP addresses. Each IP address has one of the following access attributes assigned: Read-only[...]

  • Страница 123

    Accessing MIB Files For information on the commands that can be used to manage the ATM subsystem from SNMP via a 6416SW module, refer to the Management Information Base (MIB) documents for ATM. MIB documents are available over Internet and intended to help you with Configuration and Performance management. MIBs are stored in files on an anonymous F[...]

  • Страница 124

    Security Control To prevent unauthorized access to an ATM subsystem, the 6416SW module provides two password levels to protect against network tampering and unauthorized access to the 6416SW console. The administrator password allows full use of all 6416SW commands; the user password allows use of a limited set of 6416SW commands that does not let [...]

  • Страница 125

    Uploading and Downloading Operations The picocode or microcode for your 6416SW and ATM media modules can be upgraded by inband, manual, and out-of-band operations. Data such as error logs, traces, and dumps can also be uploaded to the host. These operations are shown in Figure 6-1. For more information on the commands used to start these operations[...]

  • Страница 126

    Inband Operations To upgrade ATM microcode, ATM network administrators perform inband operations from a server connected to a ONcore hub, using a workstation connected to the 6416SW module as the 6416SW console. After locating the directory where the microcode updates are stored, log on using the administrator password and perform one of the follow[...]

  • Страница 127

    Upgrading FPGA Picocode in ATM Modules To upgrade hardware picocode in the FPGA of 6416SW and ATM media modules, enter the following commands at the directory prompt: 1. SET TFTP SERVER_IP_ADDRESS (to define the server where the picocode is stored) 2. SET TFTP FILE_NAME (to define the file on the server) 3. SET TFTP FILE_TYPE (to specify FPGA) 4. S[...]

  • Страница 128

    Uploading Traces To upload a trace log to the host, enter the following 6416SW commands at the directory prompt: 1. SET TRACE (to enable and disable trace recording) 2. SET TFTP SERVER_IP_ADDRESS (to define the server connected to the 6416SW module) 3. SET TFTP FILE_NAME (to define the path name of the file on the host) 4. SET TFTP FILE_TYPE (to sp[...]

  • Страница 129

    Out-of-band Operations ATM network administrators can upgrade 6416SW microcode (but not ATM media modules) using an out-of-band operation with an RS-232 plug. To do this, you must attach a workstation with an emulated VT100 protocol to the 6416SW module. After locating the directory where the microcode updates are stored, use the workstation as the[...]

  • Страница 130

    6-10 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 131

    Chapter 7. Troubleshooting This chapter describes how to diagnose and solve problems associated with the installation and operation of the 6416SW and ATM media modules. Troubleshooting operations are described according to the phase in which they are necessary. Phase 1 Problems that occur during installation, after turning ON the hub, and after res[...]

  • Страница 132

    Phase 1: Installation and Power Problems This section describes the troubleshooting operations for problems that occur after you turn ON the ONcore hub and wait for the 6416SW ACTIVE LED to light ON (yellow). “Verifying Normal 6416SW Operation” on page 2-7 describes the other LED conditions. Phase 1 problems concern the installation tasks descr[...]

  • Страница 133

    Prerequisites for ATM Troubleshooting In order to determine the cause of a problem during installation of 6416SW and ATM media modules or after turning ON the hub: The correct microcode must be installed. 6416SW LEDs must function properly. 6416SW and ATM media modules must be plugged into the hub. To ensure that these conditions are satisfied, fol[...]

  • Страница 134

    Diagnosing Problems from the ATM Media LEDs The following section details problems that can occur with ATM media modules. WRONG SLOT LED is ON. Explanation: Either the ATM backplane is not installed in the ONcore or the ATM media module has been inserted in an incorrect slot. Steps to Take: 1. Check that the backplane is installed (in the upper par[...]

  • Страница 135

    4. Check that the power of the slot has not been disabled. Issue the command SHOW POWER SLOT ALL to determine if that is the real cause. If this is the cause, issue the SET POWER SLOT n ENABLE command. If a DMM module is installed, this command must be issued from the DMM console. 7-5[...]

  • Страница 136

    Diagnosing Problems from the 6416SW LEDs After installing the 6416SW module, the following should occur when you turn ON the ONcore hub: All seven LEDs on the front panel light (ON) and then turn OFF, except for the RUNNING LED. The RUNNING LED stays lit (yellow). After 7 seconds, the ACTIVE LED lights up and stays lit (yellow). If the diagnostics [...]

  • Страница 137

    Power is ON but the RUNNING LED does not light (yellow). Steps to Take: 1. Press the TEST LED button on the power supply module to verify that the RUNNING LED is not burned out. 2. Verify that the 6416SW module has been installed correctly by following the installation procedure in Chapter 2, “Installation” on page 2-1. 3. Press the ATM Reset b[...]

  • Страница 138

    5. Press the ATM Reset button on the 6416SW module. 6. If the ACTIVE LED still does not light, call your 3Com dealer or your 3Com representative. MAINT LED is lit and you have not entered the MAINTAIN command. Steps to Take: 1. Make sure that the console cable is plugged into the topmost RS-232 port on the front panel of the 6416SW module. 2. Enter[...]

  • Страница 139

    Diagnosing Problems with the Power Supply If, during installation or after turning ON the hub, you suspect that power is not reaching all ATM modules in the hub, see if the problem is caused by one of the conditions described below. If you cannot solve the problem and if the 6416SW ACTIVE LED does not light ON, contact an 3Com service representativ[...]

  • Страница 140

    Phase 2: Problems During ATM Configuration The problems in this phase occur after you turn ON the ONcore hub and the 6416SW ACTIVE LED lights ON (yellow). This indicates that the 6416SW module is ready to control the ATM subsystem. Phase 2 problems concern the configuration tasks described in Chapter 5, “Configuring the ATM Switch/Control Module?[...]

  • Страница 141

    Diagnosing Problems Concerning the 6416SW Console The following section describes the problems that may arise after attaching the local console to the 6416SW module through the RS-232 Console port. If you find that the problem does not concern the 6416SW console, continue troubleshooting with “Diagnosing Problems with ATM Modules” on page 7-14.[...]

  • Страница 142

    Characters appear on the screen but they are not legible. Steps to Take: 1. Make sure that the attached console is an ASCII terminal. 2. Check the terminal parameters, especially the baud-rate, parity, and data bits. The default parameters are: 9600 bauds, 8 data bits, 1 stop bit, no parity. If these values do not work, try different settings until[...]

  • Страница 143

    The passwords do not work or you forgot a password. Steps to Take: 1. Enter force at the password prompt. Then press the ATM Reset button on the front panel of the 6416SW module within 3 seconds. This will reboot the 6416SW to the factory default settings. When you turn ON the hub, your last configuration settings are not loaded. A different config[...]

  • Страница 144

    Diagnosing Problems with ATM Modules If the cause of a Phase 2 problem is not due to the 6416SW console connection, make sure that all ATM modules are operational by following these steps: 1. Enter the SHOW MODULE ALL command as described in the ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide . 2. Check that each module is installed,[...]

  • Страница 145

    Diagnosing Problems with ATM Ports If all ATM modules are operational ( connected , hardware okay , and normal displayed with SHOW MODULE VERBOSE), the cause of the problem may be due to an inoperational ATM port. To see if the ATM ports on a given module are functioning correctly, use the SHOW MODULE and SHOW PORT commands to display port status. [...]

  • Страница 146

    Status: Error Explanation: An internal error is detected on the port. Steps to Take: 1. Reset the ATM media module using the RESET MODULE command. 2. If the problem persists, replace the ATM media module. Status: No Activity Explanation: No physical layer activity is detected (either there is no cable/fiber attached, or there is no signal on the Re[...]

  • Страница 147

    Status: Not In Service (UNI port) Explanation: Physical layer activity is detected (there is a receive signal on the Receive fiber/cable) but the remote device is not responding to ILMI polling. Steps to Take: 1. See if the port is enabled by entering the SHOW PORT command. 2. If the port is not enabled, use the SET PORT command to set the mode par[...]

  • Страница 148

    Status: Not in Service (SSI Port) Steps to Take: 1. Use the command SHOW PORT slot.port VERBOSE command to determine the problem. 2. There may be a problem of bandwidth availability on the module. Spread the SSI ports over several modules. If, after trying to solve the problem, the status of ATM media ports does not change to OKAY , perform the Wra[...]

  • Страница 149

    Phase 3: Problems on ATM Media Ports Without ATM Traffic The problems in this phase occur after the status of all ATM media ports is NO ACTIVITY and ATM devices have been attached to ATM media ports. No ATM traffic is started in the hub. Phase 3 problems occur because one or more ATM media ports are not functioning properly. The aim of the troubles[...]

  • Страница 150

    Diagnosing Problems with ATM Ports Attached to ATM Devices After you attach ATM devices to ATM media ports, the status of the ports may still not change to OKAY (ready for ATM traffic). To diagnose this type of Phase 3 problem, follow these steps: 1. Use the SHOW PORT VERBOSE command (described in the ONcore Switching Hub/CELLplex 4000 ATM Command [...]

  • Страница 151

    For SSI ports, the bandwidth allocated must be the same at both ends of the trunk. 5. If the status of an SSI port is ACN mismatch , make sure that the hub belongs to the same ATM cluster as the attached device. Enter the SHOW DEVICE command to check the configured ATM address. 6. If the status of an SSI port is Misconfigured , make sure that the d[...]

  • Страница 152

    Checking ATM Address Registration If you suspect that a Phase 3 problem is due to faulty ATM address registration between a ONcore hub and an attached ATM device, follow these steps: 1. Enter the SHOW PORT command to make sure that the ATM media port is configured with a UNI interface. If not, enter the SET PORT command and specify uni for the inte[...]

  • Страница 153

    Diagnosing Problems in the Hardware Configuration If you suspect that a Phase 3 problem is due to a problem in your hardware configuration (for example, using a LAN Emulation server, ONsemble ATM 25 Mbps Concentrator, 25Mbps client, and so on), check the following: If the attached device is an ONsemble ATM 25 Mbps Concentrator, enter the SHOW PORT [...]

  • Страница 154

    Phase 4: Problems with Normal ATM Operation The problems in this phase occur after ATM traffic is started in the network between ATM devices attached to ATM media ports. The ATM port status is OKAY . Important: Problems in the normal operation of your ATM subnetwork may occur when the maximum number of virtual connections (VCs) allowed on a ONcore [...]

  • Страница 155

    ONcore Cannot PING the ARP Servers and Vice-versa Use the SHOW DEVICE command and look at the Q2931 cause: Cause Code: 31 Explanation: The IP address of the hub is not in the same IP subnet as the ARP server. Steps to Take: 1. Change the IP address or IP subnet mask of the ONcore hub. Cause Code: 1 Explanation: A wrong ARP server address was entere[...]

  • Страница 156

    Cause Code: 3 Steps to Take: If the ARP-server is in another cluster (NNI links): 1. The NNI network-side/user-side definition rules have not been applied. Check that one side of the NNI link is defined as user, and that the other side is defined as network. 2. No logical-link has been defined for the NNI port. Define the logical link, using the SE[...]

  • Страница 157

    ONcore Hub Cannot PING an ARP Client Steps to Take: Check if the ONcore hub can ping the ARP server. If not, then see “ONcore Cannot PING the ARP Servers and Vice-versa” on page 7-25. If it can ping the server: 1. The port of the ARP client is not OKAY. Check that the port of that ARP client is enabled. If it is enabled, and not OKAY, then the [...]

  • Страница 158

    ONcore LEC Cannot PING another Client and Vice-versa Steps to Take: 1. Check that the port of the LEC is enabled. If it is enabled, and not OKAY, then the problem comes from the LEC or from the cable attached to it. 2. The LEC does not support the same Ethernet type as the ONcore LEC. Check that the LEC is emulating IEEE 802.3 Ethernet frames. 3. I[...]

  • Страница 159

    ARP Client Cannot PING the ARP Server Steps to Take: 1. The IP address of the client is not in the same subnet as the ARP server. Re-define the IP address of the ARP client so that it is in the same subnet as the ARP server IP address. 7-29[...]

  • Страница 160

    Two Devices Using IP Over a PVC Cannot Ping Each Other Steps to Take: 1. If the PVC is not active, make sure that the PVC is 'in-service' from ATMC or 'active' (from the terminal). If not, then try to re-enable that PVC. 2. The hardware connections may be failing, in which case replug the cables attached to the devices. 3. If th[...]

  • Страница 161

    ONcore LEC Cannot Initialize to the LES/BUS Use the SHOW DEVICE command and look at the subnet lan emulation status message: Abnormal Termination: LES connection cleared. ATM Forum cause xx: The LEC automatically tries to reconnect to the LES/BUS when the connection is lost. It will try to reconnect every 5 seconds, 5 times, and thereafter every 1 [...]

  • Страница 162

    If the LE server is in another cluster (NNI links): 1. The NNI network-side/user-side definition rules have not been applied. Check that one side of the NNI link is defined as user, and that the other side is defined as network. 2. No logical-link has been defined for the NNI port. Define the logical link, using the SET LOGICAL_LINK command. 3. The[...]

  • Страница 163

    LAN Emulation JOIN failed. ATM Forum LE status xx: When this message occurs, the LEC is stopped. To restart the LEC, enter the SET DEVICE LAN_EMULATION_CLIENT ETH command (the additional parameters will automatically retain their previous values). For more information, see the ONcore Switching Hub/CELLplex 4000 ATM Command Reference Guide . Cause C[...]

  • Страница 164

    Administrative Problems (Netview/SNMP/Telnet) This section details problems occuring during the administration of your ONcore hub (PING,Telnet,TFTP,SNMP/ATMC). PING: Your ONcore hub cannnot ping your management station. Steps to Take: 1. Since all the management services are running over IP, you have to ensure that your ONcore hub can ping the dest[...]

  • Страница 165

    When an upload fails, an error code is returned. That error code can be different between the terminal dialog and the ATMC/MIB browser, which is why both return codes are documented. Note: When the upload fails from the terminal dialog (console or Telnet), check the return code by using the SHOW TFTP command. Steps to Take: 1. Messages: Error/gener[...]

  • Страница 166

    4. Message: File not found/file-not-found . You tried to upload without specifying the name of the file to be uploaded. Specify the name of the file. 5. Message: File too big/file-too-big . There is no space left on the server. Check that space is made available before retrying the upload. TFTP: Download Inband fails from your ONcore hub Explanatio[...]

  • Страница 167

    2. Message: Cannot connect to Host/no-repsonse-from-host . Check that you can ping the host from the ONcore hub. If the ping fails, see the previous sections on ping failures. 3. Message: Connection lost/connection-lost . The SVC connection between the ONcore hub and the host has been cleared during the file transfer. Retry the download. Look at al[...]

  • Страница 168

    either get a new source (re-install the source file from your installation package), or, if it fails again, contact your 3Com Service or 3Com representative. 8. Message: Flash memory failure/hardware-error . Try to download several times. If it always fails, contact your 3Com representative. 9. Message: Target Blade Mismatch . You tried to download[...]

  • Страница 169

    Communication Problems in an IBM LAN Emulation Environment This section details the problems that may occur during the setup of the IBM LAN emulation environment. Such an environment may include concentrators (ONsemble ATM Workgroup Concentrator) and bridges (4404B), the external IBM LAN Emulation Server (LES), workstations (WS), ATM Workgroup Swit[...]

  • Страница 170

    LES Monitor Statistics: Default Vccs counter oscillating, too few registered workstations. Steps to Take: Explanation: The workstation knows its ATM address, but that address has been de-registered at the Switch/Control-point level. This happens when the workstation is behind a concentrator (ONsemble ATM Workgroup Concentrator) that has been discon[...]

  • Страница 171

    originating ATM station. In a network where the number of ATM stations exceeds 256, which is the maximum number of SVCs per 4404B, some stations will not be able to connect until the bridges clear their SVCs that are unused (aging out process). Steps to Take: 1. Wait up to 4 minutes (aging time on the 4404B bridge), or avoid parallel bridging. LES [...]

  • Страница 172

    LES Monitor: Bridge is on General Multicast Tree, but not on Bridge Multicast Tree. (valid only for IBM proprietary LAN emulation). Explanation: The bridge did not send its route descriptors to the LES. Steps to Take: 1. The bridge is faulty. Contact your 3Com representative. At workstation reboot: the ATM adapter initialization failed. Explanation[...]

  • Страница 173

    No Traffic in a Client Environment. Steps to Take: 1. Make sure that each LES client does not have more than 12 virtual connections. Problems between two LAN-emulated stations, or between a LAN-emulated station and a LAN station located behind a bridge (valid only for IBM proprietary LAN emulation). Steps to Take: 1. For performance problems, first[...]

  • Страница 174

    Other Problems Cannot create a PVC between two ONcore hub/CELLplex 4000s located in different clusters. Explanation: This is normal. The ONcore hub/CELLplex 4000 does not allow the creation of PVCs over network-to-network (NNI) links. You have created two different PVCs, each one ending at the NNI port. Note: Make sure that the VPI used by the PVC [...]

  • Страница 175

    at a time until the Telnet session gives a normal response time. The last port that you disabled should be the one through which the congesting calls were coming. 2. If you can be in front on the ONcore hub/CELLplex 4000, log on to the console, make sure that the trace is not active, then if the ATM switch is an ONcore, look at the traffic LEDs and[...]

  • Страница 176

    REPLY_MODE ENABLE. Your NNI port is now redirecting Received Cells to the transmit side. Now, from the ATM Analyzer, generate traffic on the VCI=5, and compare the outgoing cells with the incoming cells. If some cells are lost or corrupted, contact your public network provider. When you are finished, enter the command WRAP slot.port REPLY_MODE DISA[...]

  • Страница 177

    ATM Connection Problems No Connection between Two ATM Hub in the Same Cluster Steps to Take: 1. Use the SHOW PORT command to: Make sure that the ATM media port at each end of the connection is configured with an SSI interface. If not, use the SET PORT command and specify SSI a s the interface parameter. Make sure that the the status of each port is[...]

  • Страница 178

    No Connection Between Two ATM Clusters in the Same Subnetwork Steps to Take: 1. Use the SHOW PORT command to: Make sure that the ATM media port at each end of the connection is configured with an NNI interface. If not, use the SET PORT command and specify NNI a s the interface parameter. Make sure that the status of each port is OKAY . If not, foll[...]

  • Страница 179

    No Connection Between Two ATM Subnetworks Steps to Take: 1. Use the SHOW PORT command to: Make sure that the ATM media port at each end of the connection is configured with an NNI interface. If not, use the SET PORT command and specify NNI a s the interface parameter. Make sure that the status of each port is OKAY . If not, follow the procedure des[...]

  • Страница 180

    Using 6416SW Trap Messages A trap message is sent to the 6416SW local console when a configuration change is made or when an error occurs in the ATM subsystem. For example, if an ATM module is removed from a ONcore hub, a message describing this change is sent to the console. A sample message is shown here: @ Change trap on module 2 The first field[...]

  • Страница 181

    Contacting Your 3Com Service Representative To get technical help to solve installation and operation problems with the ATM subsystem in a ONcore hub, call your local 3Com Customer Support center. Depending on the phase in which the problem occurs, an 3Com service engineer will ask you to write down all or parts of the information listed in the fol[...]

  • Страница 182

    Troubleshooting Phase 3 Problems To troubleshoot Phase 3 problems, an 3Com service engineer needs the information listed in this section. In order to record trace information, follow these steps: 1. Use a TFTP file server in IP over ATM or LAN emulation mode. 2. Reproduce the problem and activate the trace by entering set trace main_trace on or set[...]

  • Страница 183

    Troubleshooting Phase 4 Problems To troubleshoot Phase 4 problems, an 3Com service engineer needs the information listed in this section. Note that in order to record trace information, perform dumps, and upload the error log, you must use a TFTP file server in IP over ATM or LAN emulation mode. For information on how to record trace information, s[...]

  • Страница 184

    – atmfAtmAddressTable from the ILMI MIB Q.2931 error code for the clear cause in the SVC. 7-54 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 185

    Appendix A. Technical Specifications General Specifications Connectors One RS-232 DB-9 connector (topmost on front panel) for Console port connections. One RS-232 DB-9 connector (bottommost on front panel) for Auxiliary port connections. Processors MC 68EC040 and MC 68EN360 used in companion mode. Memory 32 Kbytes nonvolatile RAM 256 Kbytes static [...]

  • Страница 186

    Electrical Specifications Power consumption 45W @ + 5V 3.5W @ + 12V Fuses Two 1A ( + 12V) for the Switch/Control cards (one for each card). Two 7A ( + 5V) for the Switch/Control cards (one for each card). Environmental Specifications Operating Temperature 0° to 50° C (32° to 122° F) Humidity Less than 95% (non-condensing) BTU/hr 55. Mechanical [...]

  • Страница 187

    Appendix B. RS-232 Cable and Modem Requirements This appendix describes: How to attach a console, modem, or server to the 6416SW module RS-232 cable pin assignments used for connecting a console, modem, or server to the 6416SW module. Requirements for using a modem with the 6416SW module. Attaching a Console, Modem, or Server When attaching a conso[...]

  • Страница 188

    RS-232 Cable Requirements RS-232 Connector The RS-232 connector is the 9-pin female connector on the 6416SW that attaches to an EIA 232 cable. Table B-1 lists the signal name associated with each pin on this connector, and Figure B-1 shows how the pins are numbered. Table B-1. EIA 232 Connector-Pin Signal Assignments Pin Number Signal Name Descript[...]

  • Страница 189

    9-Pin/9-Pin Cable Figure B-2 shows the pin assignments for the 9-pin to 9-pin RS-232 cable used to attach a console to the 6416SW Console port: 6416SW 9-pin Console port Console 9-pin Port NOT USED CD1 1 CD RD2 2 RD TD 3 3 TD DTR 4 4 DTR GND 5 5 GND DSR 6 6 DSR RTS 7 7 RT S CTS 8 8 CTS 9 9 Figure B-2. Console Attachment: 9-pin to 9-pin RS-232 Cable[...]

  • Страница 190

    9-Pin/25-Pin Cable Figure B-3 shows the pin assignments for the 9-pin to 25-pin RS-232 cable used to attach a console to the 6416SW Console port. A-C PSW 9-p i n Co nso l e p o rt Co nso l e 25-p in Port RD 2 TD 3 RTS 7 CT S 8 DT R 4 DSR 6 CD 1 GND 5 2 T D 3 R D 5 CT S 4 R TS 8 CD 6 DSR 20 DT R 7 GND Figure B-3. Console Attachment: 9-pin to 25-pin [...]

  • Страница 191

    Null-Modem Interposer Figure B-4 shows the pin assignment of the interposer (null modem) used for a console attachment. The RS-232 interposer is shipped with the ONcore hub. Figure B-4. Pin Assignment: RS-232 Interposer After attaching a console to the 6416SW RS-232 Console port, make sure that the console is set up for asynchronous serial communic[...]

  • Страница 192

    Modem Attachment Figure B-5 shows the pin assignment for the RS-232 cable used to attach a modem to the 6416SW Console port. 5 1 9 14 1 13 6 25 Female (6416SW Console Port) Male (Modem) Pin 5 2 3 8 7 4 1 6 Pin 7 3 2 5 4 20 8 6 T ransmitted Data Request to Send DTR Received Data Clear to Send Carrier Detector Data Set Ready 0 V olt IBM IBM Figure B-[...]

  • Страница 193

    Modem Requirements The 6416SW module supports the use of dial-in modems with the following requirements: The modem must be 100% Hayes-compatible. Any valid baud rate (300, 1200, 2400, 4800, 9600, 19200) may be used. 2400 and 9600 are recommended. The modem must be set to Dumb/Auto Answer mode. Modem Configuration To configure a modem, enter the fol[...]

  • Страница 194

    DTE Interface Data Type Idle/Data ASYNC Async Format.8N1 XmitClock 7855 Async DTE Speed DTS Speed..TELCO Connect Char.YES Async Data Path Direct Path...NO Escape Sequence Asynchronous <ESC>...YES <ESC>... 43 <ESC>(/5 )... 5 Signals 7855 to DTE RFS(1 6) RFS On....ALWAYS RLSD(1 9) RLSD On...ALWAYS DSR(1 7)PSN DSR On....ALWAYS DTR(1 [...]

  • Страница 195

    Appendix C. Error and Information Codes This appendix contains explanations of the error and information codes displayed for the Q.2931 protocol, the codes issued from Maintenance Mode, and the IBM LAN Emulation Server error codes. C-1[...]

  • Страница 196

    Q.2931 Error Codes for Clear Causes Table C-1 lists the error codes from the Q.2931 protocol for clear causes generated by ONcore hubs and other ATM devices in an ONcore-based ATM network. For a detailed explanation of each cause, see the ATM User-Network Interface Specification - Version 3.0 and Version 3.1 . The decimal and hexadecimal values of [...]

  • Страница 197

    Table C-1 (Page 2 of 3). Q.2931 Error Codes for Clear Causes in ONcore-based ATM Networks Error Code (decimal) Error Code (hex) Meaning of Clear Cause 35* 0x23* Requested VPI/VCI is unavailable. 36 0x24 VPI/VCI assignment failed (on user side) (UNI 3.1). 37 0x25 User cell rate not available (UNI 3.1). 38* 0x26* Network is out of order. 41* 0x29* Te[...]

  • Страница 198

    Table C-1 (Page 3 of 3). Q.2931 Error Codes for Clear Causes in ONcore-based ATM Networks Error Code (decimal) Error Code (hex) Meaning of Clear Cause 89* 0x59* Invalid end-point reference. 91 0x5B Invalid transit network selection. 92* 0x5C* Too many pending add-party requirements. 93* 0x5D* AAL parameters cannot be supported. 96* 0x60* Mandatory [...]

  • Страница 199

    Maintenance Codes The following table explains the prompts that can be displayed in Maintenance Mode. Table C-2. Maintenance Codes and Meanings Code Meaning >> 0020 >> The NVRAM diagnostics failed, the battery may be low. >> 0021 >> Bad checksum, the loading or de-compression of the operational code failed. >> 0023 >[...]

  • Страница 200

    IBM LAN Emulation Server Error Codes Table C-3. IBM LAN Emulation Server Error Codes Error Code Meaning 1 Network cause 2 Internal cause 3 Memory exhausted 4 Network is down C-6 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 201

    Appendix D. Configuring AIX for Download and Upload Operations If you are uploading or downloading ATM software to or from a server running AIX, you must first configure AIX for the TFTP file transfer before entering the DOWNLOAD INBAND or UPLOAD command. To do so, follow these steps: 1. Log on as a root user. 2. Edit the /etc/inetd.conf file that [...]

  • Страница 202

    D-2 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 203

    Appendix E. ONcore ATM Address Formats The ONcore ATM subsystem supports the addressing scheme defined by the ATM Forum for addressing end-points in private ATM networks. The scheme is modeled after the format of the OSI Network Service Access Point (NSAP) as specified in ISO-8348 (CCITT X.213). As shown in Figure E-1 on page E-2, the 6416SW suppor[...]

  • Страница 204

    Figure E-1. NSAP Address Formats Supported in the ONcore ATM Subsystem E-2 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 205

    Network Prefix The fields that make up the Network Prefix part of an ATM address include: AFI The one-byte AFI identifies the authority allocating the portion of the address that follows. It defines the structure of the NSAP format. The AFI values accepted by the ONcore ATM subsystem are as follows: 39 (ATM format of the Domain-Specific Part) 45 (A[...]

  • Страница 206

    E.164 E.164 IDI (8 bytes) Specifies the international addressing format used by B-ISDN public transport providers and is up to 15 digits long (BCD syntax). This field is padded with leading '0000' semi-bytes to reach the maximum length. A closing semi-byte '1111' is used to obtain an integral number of bytes. This code is handle[...]

  • Страница 207

    End System Part The fields that make up the End System part of an ATM address are: ESI End System Identifier (6 bytes) Identifies an end system unique within an area or within any larger addressing structure such as the IEEE MAC address space. Not used for routing within the ATM network. SEL SELector (1 byte) Has local significance only within the [...]

  • Страница 208

    E-6 ONcore ATM Switch/Control Module: Installation and User's Guide[...]

  • Страница 209

    Appendix F. Technical Support 3Com provides easy access to technical support information through a variety of services. This appendix describes the following services: Online Technical Support Support from Your Network Supplier Support from 3Com Returning Products for Repair Accessing the 3Com MIB 3Com Technical Publications F-1[...]

  • Страница 210

    Online Technical Support 3Com offers worldwide product support through the following online systems: E-mail Technical Support World Wide Web Site E-mail Technical Support You can contact the Integrated Systems Division (formerly Chipcom) on the Internet for technical support using the e-mail address: techsupp@3com.com. World Wide Web Site You can a[...]

  • Страница 211

    Support from Your Network Supplier If additional assistance is required, contact your network supplier. Many suppliers are authorized 3Com partners who are qualified to provide a variety of services, including network planning, installation, hardware maintenance, application training, and support services. When you contact your network supplier for[...]

  • Страница 212

    Support from 3Com If you are unable to receive support from your network supplier, technical support contracts are available from 3Com. For direct access to customer service for Integrated Systems Division products in: U.S.A. and Canada - call (800) 724-2447 Asia Pacific - call (508) 787-5151 Europe - refer to the table below. For European countrie[...]

  • Страница 213

    Returning Products for Repair A product sent directly to 3Com for repair must first be assigned a Return Materials Authorization (RMA) number. A product sent to 3Com without an RMA number will be returned to the sender unopened, at the sender's expense. To obtain an RMA number for Integrated Systems Division products (formerly Chipcom), use th[...]

  • Страница 214

    Accessing the 3Com MIB and atswitch.mib The 3Com Management Information Base (MIB) for the Integrated Systems Division describes commands that enable you to manage 3Com SNMP-based products. The MIB is available over the Internet on an anonymous FTP server. Updates to these MIBs are released as new 3Com products are introduced. To access Internet ve[...]

  • Страница 215

    Index Numerics 6416SW module accessing MIB files 6-3 alerts 5-22 ATM address 5-13 ATM connections 1-7 ATM Reset button 2-12 base card functions 1-6 cabling B-2 clock 5-9 configuration 5-1, 5-32 connectors A-1 console, attaching 2-5, 6-1 default settings 5-10 dimensions A-2 displaying configuration 5-29 distributed control functions 1-7 gateway conf[...]

  • Страница 216

    ARP client 7-27, 7-29 ARP server 5-18, 5-21, 7-25, 7-29 ATM Forum specifications 1-8 Auxiliary port 2-14 Available Bit Rate 1-7, 1-9 B backplane in ATM subsystem 1-3 baud rate, configuring 4-7, 4-15 best effort data transmission 1-11 boot software 6-6 boundary hub 3-8, 5-16 C cabling 2-5 console attachment B-2 for RS-232 ports B-2 modem attachment [...]

  • Страница 217

    console attaching to RS-232 port B-1 cabling B-2 configuration 4-7, 5-32 default settings 2-5, 4-7 displaying configuration 5-29 entering 6416SW commands 4-3 installation message 2-7 logging off 5-12, 5-26 modem configuration B-7 RS-232 port attachment 2-5, 2-13 sending alerts 5-22 setting prompt 5-11 setting timeout 5-12 SNMP traps 7-50 troublesho[...]

  • Страница 218

    isolated mode 5-33 K keystroke functions for 6416SW commands 4-4 L LANs, interconnecting via ONcore ATM hub 1-2 LE client 7-28 LE server 7-31 LEDs error conditions 7-4, 7-6 module and port status 2-10 normal 6416SW operation 2-7, 7-6 on front panel 2-8 location of 6416SW 5-11 logging off 4-12, 4-14, 5-26 logging on 4-12, 5-11, 5-12 logical links 5-[...]

  • Страница 219

    ports (continued) configuring logical links 3-8, 5-16 Console port 2-13 displaying configuration 5-29 status displayed by LEDs 2-10 troubleshooting 7-15, 7-19, 7-20 using NNI interface 3-8, 5-16 power supply problems 7-2, 7-9 problem determination See troubleshooting prompt, configuring 5-11 Q Q.2931 error codes C-2 protocol 1-9 quality of service [...]

  • Страница 220

    SET LOGICAL_LINK command 3-8, 5-16 SET MODULE command 5-32, 5-33 SET PORT command 5-15, 5-32 SET STATIC_ROUTE command 5-16 SET TERMINAL HANGUP command 4-16 SET TERMINAL PROMPT command 5-11 SET TERMINAL TIME_OUT command 5-12 SHOW MODULE command 5-29 SHOW PORT command 5-29 slot positions for 6416SW module 1-5 slot positions in hub 2-3 SMIT facility 7[...]

  • Страница 221

    troubleshooting (continued) LAN emulation 7-39 other problems 7-44 ping operation 7-25, 7-27, 7-28, 7-29, 7-31 power supply 7-9 using RS-232 ports 2-14 using trap messages 7-50 U UNI See user-to-network interface unpacking 2-2 upgrading 6416SW microcode 2-13, 6-6 FPGA picocode 6-7 UPLOAD command D-1 upload operations configuring AIX for TFTP D-1 du[...]