Mitsubishi Electronics PKH36FK Bedienungsanleitung
- Schauen Sie die Anleitung online durch oderladen Sie diese herunter
- 89 Seiten
- 2.26 mb
Zur Seite of
Ähnliche Gebrauchsanleitungen
-
Air Conditioner
Mitsubishi Electronics PKA-A24KA4.TH
32 Seiten 3.12 mb -
Air Conditioner
Mitsubishi Electronics MUZ-FD12NA
36 Seiten 0.88 mb -
Air Conditioner
Mitsubishi Electronics MSH-18NV
80 Seiten 3.19 mb -
Air Conditioner
Mitsubishi Electronics AG-150A
16 Seiten 0.44 mb -
Air Conditioner
Mitsubishi Electronics PEFY-P-VMS-E
15 Seiten 0.74 mb -
Air Conditioner
Mitsubishi Electronics PUY-A42NHA2-BS
120 Seiten 10.58 mb -
Air Conditioner
Mitsubishi Electronics PSA-RP-GA
22 Seiten 1.21 mb -
Air Conditioner
Mitsubishi Electronics PEH-10MYA
116 Seiten 2.01 mb
Richtige Gebrauchsanleitung
Die Vorschriften verpflichten den Verkäufer zur Übertragung der Gebrauchsanleitung Mitsubishi Electronics PKH36FK an den Erwerber, zusammen mit der Ware. Eine fehlende Anleitung oder falsche Informationen, die dem Verbraucher übertragen werden, bilden eine Grundlage für eine Reklamation aufgrund Unstimmigkeit des Geräts mit dem Vertrag. Rechtsmäßig lässt man das Anfügen einer Gebrauchsanleitung in anderer Form als Papierform zu, was letztens sehr oft genutzt wird, indem man eine grafische oder elektronische Anleitung von Mitsubishi Electronics PKH36FK, sowie Anleitungsvideos für Nutzer beifügt. Die Bedingung ist, dass ihre Form leserlich und verständlich ist.
Was ist eine Gebrauchsanleitung?
Das Wort kommt vom lateinischen „instructio”, d.h. ordnen. Demnach kann man in der Anleitung Mitsubishi Electronics PKH36FK die Beschreibung der Etappen der Vorgehensweisen finden. Das Ziel der Anleitung ist die Belehrung, Vereinfachung des Starts, der Nutzung des Geräts oder auch der Ausführung bestimmter Tätigkeiten. Die Anleitung ist eine Sammlung von Informationen über ein Gegenstand/eine Dienstleistung, ein Hinweis.
Leider widmen nicht viele Nutzer ihre Zeit der Gebrauchsanleitung Mitsubishi Electronics PKH36FK. Eine gute Gebrauchsanleitung erlaubt nicht nur eine Reihe zusätzlicher Funktionen des gekauften Geräts kennenzulernen, sondern hilft dabei viele Fehler zu vermeiden.
Was sollte also eine ideale Gebrauchsanleitung beinhalten?
Die Gebrauchsanleitung Mitsubishi Electronics PKH36FK sollte vor allem folgendes enthalten:
- Informationen über technische Daten des Geräts Mitsubishi Electronics PKH36FK
- Den Namen des Produzenten und das Produktionsjahr des Geräts Mitsubishi Electronics PKH36FK
- Grundsätze der Bedienung, Regulierung und Wartung des Geräts Mitsubishi Electronics PKH36FK
- Sicherheitszeichen und Zertifikate, die die Übereinstimmung mit entsprechenden Normen bestätigen
Warum lesen wir keine Gebrauchsanleitungen?
Der Grund dafür ist die fehlende Zeit und die Sicherheit, was die bestimmten Funktionen der gekauften Geräte angeht. Leider ist das Anschließen und Starten von Mitsubishi Electronics PKH36FK zu wenig. Eine Anleitung beinhaltet eine Reihe von Hinweisen bezüglich bestimmter Funktionen, Sicherheitsgrundsätze, Wartungsarten (sogar das, welche Mittel man benutzen sollte), eventueller Fehler von Mitsubishi Electronics PKH36FK und Lösungsarten für Probleme, die während der Nutzung auftreten könnten. Immerhin kann man in der Gebrauchsanleitung die Kontaktnummer zum Service Mitsubishi Electronics finden, wenn die vorgeschlagenen Lösungen nicht wirksam sind. Aktuell erfreuen sich Anleitungen in Form von interessanten Animationen oder Videoanleitungen an Popularität, die den Nutzer besser ansprechen als eine Broschüre. Diese Art von Anleitung gibt garantiert, dass der Nutzer sich das ganze Video anschaut, ohne die spezifizierten und komplizierten technischen Beschreibungen von Mitsubishi Electronics PKH36FK zu überspringen, wie es bei der Papierform passiert.
Warum sollte man Gebrauchsanleitungen lesen?
In der Gebrauchsanleitung finden wir vor allem die Antwort über den Bau sowie die Möglichkeiten des Geräts Mitsubishi Electronics PKH36FK, über die Nutzung bestimmter Accessoires und eine Reihe von Informationen, die erlauben, jegliche Funktionen und Bequemlichkeiten zu nutzen.
Nach dem gelungenen Kauf des Geräts, sollte man einige Zeit für das Kennenlernen jedes Teils der Anleitung von Mitsubishi Electronics PKH36FK widmen. Aktuell sind sie genau vorbereitet oder übersetzt, damit sie nicht nur verständlich für die Nutzer sind, aber auch ihre grundliegende Hilfs-Informations-Funktion erfüllen.
Inhaltsverzeichnis der Gebrauchsanleitungen
-
Seite 1
TECHNICAL & SER VICE MANUAL SPLIT -TYPE,HEA T PUMP AIR CONDITIONERS CONTENTS 1. FEA TURES ···········································2 2. SPECIFICA TIONS·································5 3. DA T A ····································[...]
-
Seite 2
2 1 FEA TURES 1. COMP ACT DESIGN The PK series models have been downsized and now require such minimal wall space that they can even be installed above windows. For the PKH18/24FK, 13in of wall space between the ceiling and the window allows “above window” installation (14.5in for the PKH30/36FK) 2. A FURTHER REFINEMENT OF COMFORT WITH NOISE SU[...]
-
Seite 3
3 5. ADV ANCED MICROPROCESSOR (1) Easy to Use Microprocessor 1) Ultra-Thin Remote Controller The streamlined, square controller is designed to blend with any kind of interior and the adoption of a sophisticated microprocessor allows you to carry out a wide range of operations easily . 2) Ultra-Thin Remote Controller Units operation mode, set temper[...]
-
Seite 4
4 7. HIGH RELIABILITY AND EASY SERVICING In addition to the self-diagnostic function, units are also equipped with a 3-minute time delay mechanism (cooling), an auto restart function, an emergency operation function, a test run switch, etc., to assure high reliability and easy servicing. 8. FOUR-W A Y PIPING ACCESS MAKES INST ALLA TION LA YOUT EASY[...]
-
Seite 5
5 Capacity Moisture removal Power Consomption EER SEER HSPF COP INDOOR UNIT MODELS External finish Power supply Max.fuse size (time dalay) Min.ampacity Fan motor Booster heater Airflow Hi-Lo Sound level Hi-Lo Cond. drain connection OD Dimensions Weight OUTDOOR UNIT MODELS External finish Power supply Max.fuse size (time dalay) Min.ampacity Fan moto[...]
-
Seite 6
6 Models Models Outdoor intake air DB temperature ( ˚F ) PKH18FK 71 67 63 62.5 60 59 71 67 63 62.5 60 59 71 67 63 62.5 60 59 71 67 63 62.5 60 59 TC 21.0 19.5 18.2 18.1 17.2 16.8 27.9 26.1 24.3 24.1 23.0 22.5 34.9 32.6 30.4 30.2 28.8 28.2 39.8 37.1 34.7 34.4 32.8 32.2 SHC 14.4 16.0 17.4 15.5 15.1 14.5 16.1 18.5 20.5 18.0 17.6 17.0 21.5 24.5 26.9 23[...]
-
Seite 7
7 Models Models Outdoor intake air WB temperature ( ˚F ) PKH18FK 75 70 65 75 70 65 75 70 65 75 70 65 CA 12.1 12.4 12.7 16.3 16.6 17.0 21.5 21.9 22.5 24.7 25.3 25.9 PC 1.20 1.16 1.1 1 1.82 1.76 1.69 2.32 2.24 2.15 2.71 2.62 2.53 CA 14.1 14.4 14.7 18.9 19.4 19.8 25.0 25.5 26.1 28.7 29.4 30.1 PC 1.34 1.29 1.24 2.03 1.96 1.89 2.59 2.50 2.40 3.04 2.93 [...]
-
Seite 8
8 SHF=0.71V Does not include booster heater (1.9kW) T otal power consumption (kW) T otal capacity (x10 3 Btu/h) 30 35 24 18 12 3.0 2.5 2.0 1.5 15 25 35 45 55 65 T otal power consumption (kW) T otal capacity (x10 3 Btu/h) Outdoor intake air DB temperature ( F) Outdoor intake air WB temperature ( F) 36 30 24 18 12 3.0 2.5 2.0 1.5 63 67 71 63 67 71 0 [...]
-
Seite 9
9 NOTES : A point on the curve shows the reference point. PKH30FK COOLING CAP ACITY PKH30FK HEA TING CAP ACITY PKH36FK COOLING CAP ACITY PKH36FK HEA TING CAP ACITY 71 67 63 71 67 63 42 36 30 24 4.0 3.5 3.0 2.5 2.0 SHF=0.75 Total capacity(x10 Btu/h) 3 Total power consumption(kW) Outdoor intake air DB temperature( ¡ F) 0 23 32 35 45 55 65 (67) 75 85[...]
-
Seite 10
10 3. CONDENSING PRESSURE AND SUCTION PRESSURE Data is based on the condition of indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. <Cooling mode> PKH18FK PKH18FK PKH18FK PKH18FK Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point. <Heating m[...]
-
Seite 11
11 Data is based on the condition of indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. <Cooling mode> PKH24FK PKH24FK PKH24FK PKH24FK Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point. <Heating mode> 360 350 340 330 320 310 300 290 280 [...]
-
Seite 12
12 Data is based on the condition of indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. <Cooling mode> PKH30FK PKH30FK PKH30FK PKH30FK Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point. <Heating mode> 350 340 330 320 310 300 290 280 270 [...]
-
Seite 13
13 Data is based on the condition of indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. <Cooling mode> PKH36FK PKH36FK PKH36FK PKH36FK Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point. <Heating mode> 350 340 330 320 310 300 290 280 270 [...]
-
Seite 14
14 4. ST ANDARD OPERA TION DA T A Models Item Electrical circuit Refrigerant circuit Indoor side Outdoor side V oltage Frequency T otal input Indoor fan current Booster heater current Outdoor fan current Comp. current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp.shell bottom temperature [...]
-
Seite 15
15 Condition Standard temperature Maximum temperature MInimum temperature Maximum humidity Standard temperature Maximum temperature MInimum temperature 80 95 67 80 70 80 70 67 71 57 75 60 67 60 95 1 15 23 80 47 75 17 75 — — 75 43 65 15 Function Cooling Heating Model Airflow ( CFM ) Air speed ( ft/sec ) Coverage range ( ft ) PKH18FK PKH24FK PKH3[...]
-
Seite 16
16 9-1/4 1-25/32 9-1/4 1-25/32 9-1/4 9-1/4 1-25/32 1/2 13-3/8 7-3/4 Top Front Right side Left side 55-1/8 42-15/16 Air intake 9-1/4 C Knock out hole for right piping Refrigerant pipe. Drain pipe Knock out hole for left piping Drain hose for left-hand side piping Drain hose Lower side Auto vane (Gas pipe) Drain hose Bolt Gas pipe 19/32 Terminal bloc[...]
-
Seite 17
17 66-5/32 9-1/4 53-15/16 Alr Intake Front Knock out hole Right side 9-1/4 7-3/4 C for right piping B A A B C 4-1/32 Liquid pipe 1/2F Gas pipe Sleeve > < 1 > < 1 Sleeves are availaable on the market. Through hole 3-1/2 3-1/2~ 4 3/4F Bolt 19/32 or less T erminal block for remote controller 4-3/8 2-5/32(Gas pipe) T erminal block for contr[...]
-
Seite 18
18 Unit : mm 4.2. Outdoor Unit PUH18EK T er minal block f or indoor and outdoor unit connection T er minal block f or power line Ground terminal Handie for moving Service panel Refrigerant pipe (Flared) 5/8 Knock out hole for front piping 4-3/4 (refrigerant. drainage and wiring) 4-1/8 Drain hole Drain hole 2-U-shaped notched holes 1-5/8 1-3/4 1/5/1[...]
-
Seite 19
19 Unit : mm Outdoor Unit PUH24EK T er minal block f or indoor and outdoor unit connection T er minal block f or power line Ground terminal Handie for moving Service panel Refrigerant pipe (Flared) 5/8F Knock out hole for front piping 4-3/4 (refrigerant. drainage and wiring) 4-1/8 Drain hole Drain hole 2-U-shaped notched holes 2-1/16 2-1/4 1/9/16 B[...]
-
Seite 20
20 T erminal block for indoor and outdoor unit connection T erminal block for power line Ground terminal Handie for moving Service panel Refrigerant pipe (Flared) (PUH30/36EK) 3/4 (PUH42EK)7/8F Knock out hole for front piping 4-3/4 (refrigerant. drainage and wiring) 4-1/8 Drain hole Drain hole 2-U-shaped notched holes 2-1/16 2-1/4 1/9/16 Bottom pip[...]
-
Seite 21
21 F F HR AIR SWEEP TIMER OFF AUTO STOP AUTO ST AR T • CENTRALL Y CONTROLLED • ST AND BY DEFROST CHECK SET TEMP HEA T AUTO COOL/DR Y TEMPERA TURE WARMER COOLER AUTO DRY HEA T COOL ON CHECK TEST RUN LOW HIGH ON/OFF POWER — SET 3-5/8 3-5/8 5/8 2-3/4 TIMER MODE HOURS F AN SPEED LOW/HIGH AIR UP/DOWN SWING/STOP DISCHARGE CHECK TEST RUN 4-3/4 4-3/[...]
-
Seite 22
22 5 WIRING DIAGRAM NOTES : 1. Since the indoor fan motor (MF) is connected with 230V power , using 208V power will require a setting change of the dip switch (SW7<I.B>) on the indoor con- troller board as shown in fig : w 1. Indoor fan motor (MF) for 208V . 2. Since the indoor transformer (T) is connected with 230V power if 208V power is use[...]
-
Seite 23
23 Main function of LED(when both Nos.1 and 2 of are "OFF") How to use SW1 and 2 ● Pressing erases the past check contents loaded on the microcomputer . ● The output display (light) remains during opera- tion but pressing displays the past check contents in flashing mode. Pressing the switch again retums to output display (light). NOT[...]
-
Seite 24
24 NOTES : Symbols used in wiring diagram above are. / :T erminal block, ¤¤¤ :Connector , ¤ :PC board insertion tab. ● The connector marked s — ¤ — is to turn the compressor ON-OFF during servicing. The compressor stops by disconnecting the white connector as shown at the right. ● Since LD8 lights when normal power is turned "ON&q[...]
-
Seite 25
25 REFRIGERANT SYSTEM DIAGRAM 6 Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor coil thermistor RT2 Distributor Restrictor valve Capillary tube ( { 0.126x { 0.071x15.7) ( { 0.126x { 0.071x9.8) PKH30FK( { 0.157x { 0.079x1 1.4) PKH36FK( { 0.157x { 0.079x1 1.4) Capillary tubesize:(ODxIDxLength) The symbol { indicates [...]
-
Seite 26
26 7 OPERA TION FLOW-CHART START Power circuit breaker Check SW ON twice Operation SW ON “OFF” timer “ON” timer STOP Set time complete Set time complete 1 NO NO NO NO NO NO NO NO NO NO NO NO YES YES YES YES YES YES YES YES YES YES YES YES w 1 w 2 w 3 w 4 w 5 w 7 w 6 PROTECTION DEVICE SELF HOLD RELEASE Remote controller indicator lamp OFF Tr[...]
-
Seite 27
27 COOL operation Four-way valve/OFF Initial COOLING NO NO NO NO NO NO YES YES YES YES YES YES NO YES YES YES YES YES YES YES YES YES YES YES NO NO NO NO YES NO NO NO NO NO NO NO NO NO w 8 w 9 Vane intial setting Vane 60 deg downward angle 70 deg downward angle Fan speed LOW Downward discharge 1 hour Vane setting notch Vane horizontal airflow Compr[...]
-
Seite 28
28 Heat operation Intial HEATING Vane setting notch Vane intial setting Defrosting Heating area Defrost release Defrost 30 min. elaspe Outdoor unit trouble Four-way valve ON Hor adjust in process Compressor ON Compressor thermostat ON Allowance cancel Indoor piping -5 ¡ F or lower Outdoor unit trouble FAN SPEED Very low airflow Compressor OFF 1 3 [...]
-
Seite 29
29 w 8 ~ 9 Refer to page 35. w 12 When room temperature is 4°F or below , the compressor cannot operate. When room temperature rises over 64°F , the compressor starts after a 3-minute time delay . w 13 Compressor ON time is decided by room temperature. Refer to page 35. w 14 In dry operation, compressor ON makes the fan speed LOW and compressor O[...]
-
Seite 30
30 8 MICROPROCESSOR CONTROL ● Compressor and outdoor fan : ON- OFF ● Operation mode change :COOL- HEA T . 1.OUTLINE OF MICROPROCESSOR CONTROL ● OFF-ON switching. ● COOL/DRY -AUTO-HEA T selector switching. ● Thermostat setting. ● TIMER mode selector-switching and T imer setting. ● HIGH-LOW fan speed switching. ● AUT O V ane selector [...]
-
Seite 31
31 Minimum 3 minutes 1 ON Thermostat Indoor fan Auto vane Booster heater Compressor ON LOW or HIGH Initally 10 degrees (Changeable by remote controller setting) LOW or HIGH ON ON OFF OFF CLOSE CLOSE OFF OFF OFF Operation starts by POWER button ON. Operation stops by POWER button OFF. The room temperature displayed on Remote controller becomes equal[...]
-
Seite 32
32 (1) Compressor control 1 3-minute time delay T o prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature displayed on remote controller is higher than set temperature. The compressor stops when the room temperature displayed on remote controller is equal to or lower than the se[...]
-
Seite 33
33 (3) Auto vane control Auto vane position is set to 10degrees discharge at the start-up of COOL operation. It can then be changed by the remote controller . (a) Stop mode (fixed operation) ( ! ) At start-up of COOL operation, the auto vane is set to 10 degrees discharge direction. ( @ ) Discharge direction can be changed with AIR DISCHARGE UP/DOW[...]
-
Seite 34
34 <Auto vane drive> (a) The vane is driven by DC12V motor . (b) Air discharge direction is selected depends on the number of pulse were sended. (c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each air discharge. (d) The speed of the auto vane drive for both open and close are setted a[...]
-
Seite 35
35 <DR Y operation time chart> Minimum 3 minutes 1 ON 30 Thermostat Indoor fan Auto vane Booster heater Compressor ON Initally 10 degrees discharge ( Changeable by remote controller setting ) LOW speed LOW speed ON ON OFF OFF CLOSE CLOSE OFF OFF OFF Operation starts by POWER button ON. Operation stops by POWER button OFF. 30 The room temperat[...]
-
Seite 36
36 Minimum 3 minutes 2 ON Thermostat Indoor fan Auto vane Booster heater Compressor Power ON lamp STAND BY lamp ON ON LOW or HIGH LOW or HIGH ON OFF OFF OFF OFF ON OFF ON OFF ON OFF Extra LOW 1 Extra LOW 1 Hot adjustment 10 ¡ Close 10 ¡ Close From POWER ON until warm begins to blow Hot adjustment Depends on remote controller setting Depends on re[...]
-
Seite 37
37 (1) Compressor control 1 3-minute time delay T o prevent overload, the compressor will not start within 6, minutes after stop. 2 The compressor runs when the the room temperature displayed on remote controller is lower than the set temperature. The compressor stops when the the room temperature displayed on remote controller is equal to or highe[...]
-
Seite 38
38 (3) Auto vane control (a) ST OP mode (fixed operation) ( ! ) The discharge direction at the start-up of HEA T operation is the same as that of the previous operation. ( @ ) The discharge direction can be charged by the remote controller setting. In the following cases, discharge direction becomes 10° regardless of the remote controller setting.[...]
-
Seite 39
39 (6) Indoor coil thermistor abnormality detection An abnormality can be detected during compressor ON, except for the following. ● For the first 30 minutes after the temperature dif ference between the indoor coil temperature and room temperature enters the RANGE C. ● When the temperature difference enters the RANGE C until it moves to the RA[...]
-
Seite 40
40 (1) Initial mode 1 When AUTO operation starts after unit OFF . ● If the room temperature displayed on remote controller is higher than the set temperature, operation starts in COOL mode. ● If the room temperature displayed on remote controller is equal to or lower than the set temperature, operation starts HEA T mode. 2 When AUTO operation s[...]
-
Seite 41
41 <How to operate> T o change the air flow direction, press AIR DISCHARGE UP/DOWN button. 1 10° 2 30° 3 60° 4 70° (1) COOL/DR Y operation At the start-up of COOL or DRY operation, the discharge direction in automatically set to 10°. After , it can be changed to another direction with AIR DISCHARGE UP/DOWN button on the remote controller[...]
-
Seite 42
42 MITSUBISHI ELECTRIC -CENTRALLY CONTROLLED- STAND BY DEFROST ON CHECK DRY COOL HEAT CHECK SET TEMP TIMER OFF AUTO STOP AUTO START F HR F LOW HIGH AUTO RETURN CHECK TEST RUN POWER ON/OFF HEAT SET TEMPERATURE AUTO COOL/DRY COOLER WARMER TIMER MODE HOURS FAN SPEED LOW/HIOGH AIR DISCHARGE UP/DOWN SWING STOP CHECK TEST RUN <T imer function> AUTO[...]
-
Seite 43
43 (1) Indoor coil temperature code During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEA T operation. (2) T rouble during test run ● If the unit malfunctions during th[...]
-
Seite 44
44 2-9 Interlock with ventilation system (LOSSNA Y) Mr . SLIM/LOSSNA Y interlock operation is available by using the optional parts listed below . (1) System organization NOTE: For further information, refer to the LOSSNA Y technical & service manual. (2) Required parts are: ● Relay box (PZ-12RB-E) ••• Contact capacity 10A ● Remote di[...]
-
Seite 45
45 2-10 Dip switch and jumper connector functions Each figure shows the initial factory setting. 1 On remote controller board (1) SW17(Address selector) SW17-1 ~ 6) For address setting SW17-7) When two remote controllers are used, this switch sets the controller function. OFF: The remote controller is set as a main controller . ON: The remote contr[...]
-
Seite 46
46 Nomal operation For emergency cooling For emergency heating 2 4 OFF: 208V ON : 230V ) ( 1 2 3 4 5 6 ON OFF 1 2 ON OFF 1 2 ON OFF 1 2 ON OFF 1 2 3 4 ON OFF J1-7) Switch for fan speed during thermostat OFF in HEA T operation Provided : EXTRA LOW Not provided : LOW J1-8) Switch for fan speed during thermostat OFF in HEA T operation. Provided : EXTR[...]
-
Seite 47
47 3. OUTDOOR UNIT CONTROL 3-1 Outdoor fan control The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air tempera- ture. 3-2 Outdoor unit control The outdoor uni[...]
-
Seite 48
48 (1) Start conditions A. When all of the following conditions are satisfied, defrosting will start. However , when the bypass valve turns OFF , defrosting starts 10 minutes later . (a) More than seven minutes have passed since the compressor start-up. (b) The outdoor coil thermistor reads 23˚F or below . (c) The outdoor fan motor output step is [...]
-
Seite 49
49 (3) Defrost interval The defrost interval time is determined as follows. ● Initial defrost interval is 50 minutes. ● The defrost interval after defrosting depends on the preceding defrosting time as shown below . NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes. NOTE2:If a protection function works for[...]
-
Seite 50
50 3-7 Service functions (1) Compulsory defrositng 1 When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting. ● During HEA T mode ● The compressor is ON. ● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF , SW3-2 : ON) ● The outdoor coil thermi[...]
-
Seite 51
51 TROUBLESHOOTING 9 Symptom Cause Check points The display “CENTRALL Y CONTROLLED” on remote controller does not disap- pear . 1) W rong address setting of remote con- troller/indoor controller board. 2) T imer adapter is connected to the remote controller . 3) Signal transmission error between indoor unit and remote controller . 1) Check the [...]
-
Seite 52
52 2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER 2-1 When malfunction occurs during operation When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote controller . (A) ON the set temperature display part, “CHECK” appears, and the unit address and the check code are displayed alt[...]
-
Seite 53
53 Check code Diagnosis of malfunction Cause Check points EO Signal transmitting/receiving error (Indoor controller does not respond to remote controller signal.) During individual unit control 1) Bad contact of transmission wire 2) Signal transmitting/receiving cir- cuit is abnormal. 1) Check the transmission wire. 2) Check with another remote con[...]
-
Seite 54
54 3.SER VICE DA T A INDICA TION BY SWITCHES ON OUTDOOR CONTROLLER BOARD Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code. Output state is shown by LED lighting, and check code by blinking. SW1 : T urning SW1 ON clears the check code. If SW1 is turned ON while the check code is blin[...]
-
Seite 55
55 3-1 Outdoor coil temperature T o obtain data on the outdoor coil tempera- ture, add the number of bits of lighting LEDs, and see the graph below to find the temperature. 3-2 Fan output step T o obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan rotational frequency . 3-3 T otal ti[...]
-
Seite 56
56 Blinking LED Diagnosis of malfunction Cause Check point LD1 Reversed phase Phases A 1 , A 2 , and A 3 are con- nected improperly . Check the power supply connection. LD2 Open phase ● Phase A 2 is open. ● Contact of protector , such as thermal switch, opened when power was turned on. ● Check the power supply . ● Check each protector . LD3[...]
-
Seite 57
57 6. WRONG WIRING ON SITE 6-1 Between remote controller and indoor unit If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard. 6-2 Phenomenon due to wrong wiring between indoor and outdoor units Wrong wirin[...]
-
Seite 58
58 Symptom LOSSNA Y control switch does not work. LOSSNA Y air speed can not be controlled in interlock opera- tion. LOSSNA Y control switch can not work during interlock operation. LOSSNA Y control switch is effective only while Mr . SLIM is not operat- ing. LOSSNA Y fan speed is fixed to HIGH during interlock operation. LOSSNA Y fan speed LOW/HIG[...]
-
Seite 59
59 SYSTEM CONTROL 10 1 Group control with a single remote controller (See page 59.) Unit Remote controller Unit Unit Many units, installed at different locations, can be started and controlled with a single remote controller . The remote controller can be mounted in a different location using a non-polar two-wire cable, which can be extended up to [...]
-
Seite 60
60 2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER A maximum of 50 units can be started in order according to the dip switch settings 2-1 How to wire (1) Connect the remote controller to the double terminal block on the indoor controller board of the master unit (No.0 unit). (See Figure 1.) (2) Connect the double terminal block of the master unit [...]
-
Seite 61
61 4. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS This method is auailable to control one unit or any number of units. The following operations are available by connecting a relay , a timer adapter (P AC-SA89T A-E), and a remote ON/OFF switch to the system. T imer adapter is an optional part. Other parts are available on the market. (A) T o start [...]
-
Seite 62
62 NOTE1 : Install the relay box where it can be serviced easily . NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control circuit. NOTE3 : When the power supply of the control circuit is 220/240V AC, ● Do not connect the control circuit wire to the remote controller cable directly [...]
-
Seite 63
6. MUL TIPLE REMOTE CONTROL DISPLA Y Y ou can control serveral units with a multiple remote control display ,by wiring an optional multipe display adapter (P AC-SA88HA-E) with relays and lamps on the market. 6-1 How to wire (1) Connect the multipe display adapter to the connector CN51 on the indoor controller board. (2) Wire three of the five wires[...]
-
Seite 64
64 1 1 DISASSEMBL Y INSTRUCTIONS OPERA TING PROCEDURE PHOTOS&ILLUSTRA TION Metal fixture Screws 1. Removing the lower side of the indoor unit from the instal- lation plate (1) Remove the 2 screws. Hang the indoor unit hangers to the catches on the instal- lation plate. Hanger of indoor unit Catch of installation plate 2. Removing the right side[...]
-
Seite 65
65 OPERA TING PROCEDURE PHOTOS&ILLUSTRA TION (8) Remove the screws of the indoor controller board case, and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced. 5. Removing the vane motor (1) Remove the right side panel. (2) Remove the screw of the electrical parts box cover , and remove t[...]
-
Seite 66
66 OPERA TING PROCEDURE PHOTOS 8. Removing the lineflow fan and the fan motor (1) Remove the left and right side panels. (2) Remove the grills. (3) Remove the electrical parts box. (4) Remove the drain pan. (5) Loosen the screw that fixes the lineflow fan to the fan motor . (See Photo 7. ) (6) Remove the 4 screws of the motor fixture, and remove th[...]
-
Seite 67
67 OPERA TING PROCEDURE PHOTOS 1. Electrical parts (1) Remove top panel (3 screws in front, 2 screws in rear) (2) Remove cover panel (1 screw). The panel is anchored by clicks to the side panel. Remove by pulling towards you. (3) Remove cover panel (1 screw). The panel is anchored by clicks on the right and left sides. After removing the screw , pu[...]
-
Seite 68
68 OPERA TING PROCEDURE PHOTOS 3. Heat Exchanger , Compressor (1) Remove the rear panel (2 screws in front, 1 screw on the side, 3 screws in the rear). Remove the valve bed, and open the rear panel to the rear to remove. NOTE : All panels are clasped, and must be removed by shifting up and down. (2) Remove right side panel (4 screws). (3) Remove re[...]
-
Seite 69
69 OPERA TING PROCEDURE PHOTOS 1. Electrical parts (1) Remove top panel (3 screws in front, 2 screws in rear) (2) Remove cover panel (1 screw). The panel is anchored by clicks to the side panel. Remove by pulling towards you. (3) Remove cover panel (1 screw). The panel is clasped on the right and left sides. After remov - ing the screw , pull the p[...]
-
Seite 70
70 OPERA TING PROCEDURE PHOTOS 3. Heat Exchanger , Compressor (1) Remove the rear / right side panel (2 screws in front, 1 screw on the side, 3 screws in the rear). Remove the electrical box, valve bed, and open to the rear to remove (anchors attached). (2) Remove right side panel (4 screws). (3) Remove rear guard (3 screws). (4) Remove separator s[...]
-
Seite 71
71 P ART LIST 12 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH 24FK 30FK 18FK Part number that are circled not shown in the figure. 1 2 3 4 5 6 7 8 9 10 R01 12G 661 R01 12G 662 R01 12G 691 R01 16G 692 R01 12G 500 R01 12G 811 R01 16G 811 R01 12G 812 R01 16G 812 R01 12G 641 R01 16G 641 R01 12G[...]
-
Seite 72
72 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH 24FK 30FK 18FK 1 2 3 4 5 6 FAN MOTOR RUBBER MOUNT RIGHT LINEFLOW FAN LEFT LINEFLOW FAN SLEEVE BEARING 1 2 1 1 1 1 1 2 1 1 1 1 1 2 1 1 1 1 36FK 1 2 1 1 1 1 MF MF T7W BOO 762 T7W B01 762 R01 12G 105 R01 16G 105 R01 12G 115 R01 16G 115 R01 12G 11[...]
-
Seite 73
73 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH 24FK 30FK 18FK 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 BEARING MOUNT DRAIN PAN VANE MOTOR AUTO VANE CENTER COVER JOINT SHAFT DRAIN HOSE HEAT EXCHANGER CONTROLLER BOARD FUSE TERMINAL BLOCK RUN CAPACITOR [...]
-
Seite 74
74 PUH18EK FUNCTIONAL P ARTS OC120--3.qxp 24/6/97 1:01 AM Page 74[...]
-
Seite 75
75 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PUH 18EK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 PROPELLER FAN MOTOR OUTDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK CONTACTOR FAN CAPACITOR TRANSFORMER COMPRESSOR CAPACITOR OUTDOOR COIL THERMISTOR OVERC[...]
-
Seite 76
76 PUH24EK FUNCTIONAL P ARTS OC120--3.qxp 24/6/97 1:02 AM Page 76[...]
-
Seite 77
77 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PUH 24EK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 PROPELLER FAN MOTOR OUTDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK CONTACTOR FAN CAPACITOR TRANSFORMER COMPRESSOR CAPACITOR OUTDOOR COIL THERMISTOR COMPRESS[...]
-
Seite 78
78 PUH30/36EK FUNCTIONAL P ARTS 36 37 36 37 6 3 4 8 12 5 23 33 1 1 24 2 28 17·18 19·20 7 27 33 29 32 16 21 22 34 35 15 13·14 30·31 9 10·1 1 OC120--3.qxp 24/6/97 1:02 AM Page 78[...]
-
Seite 79
79 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set 30EK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 PROPELLER FAN MOTOR OUTDOOR CONTROLLER BOARD FUSE TERMINAL BLOCK CONTACTOR COMPRESSOR CAPACITOR FAN CAPACITOR TRANSFORMER COMPRESSOR CRANKCA[...]
-
Seite 80
80 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PUH 18EK 1 2 3 4 5 6 7 8 9 FRONT PANEL SERVICE PANEL SIDE PANEL FAN GUARD TOP PANEL PANEL COVER BASE ASSEMBLY REAR PANEL REAR GUARD 1 1 1 1 1 1 1 1 1 OUTDOOR FUNCTION R01 A08 668 R01 A08 661 R01 A08 662 R01 A00 675 R01 A00 641 R01 A00 658 R01 A00 [...]
-
Seite 81
81 PUH24EK STRUCTURAL P ARTS No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PUH 24EK 1 2 3 4 5 6 7 8 9 TOP PANEL FRONT PANEL FAN GUARD SERVICE PANEL SIDE PANEL (LEFT) REAR PANEL PANEL COVER REAR GUARD BASE ASSEMBLY 1 1 2 1 1 1 1 1 1 R01 A00 641 R01 A11 668 R01 A00 675 R01 A11 661 R01 A11 662 R01 [...]
-
Seite 82
82 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PUH 30EK 1 2 3 4 5 6 7 8 9 TOP PANEL FRONT PANEL FAN GUARD SERVICE PANEL SIDE PANEL (LEFT) REAR PANEL PANEL COVER REAR GUARD BASE ASSEMBLY 1 1 2 1 1 1 1 1 1 36EK 1 1 2 1 1 1 1 1 1 R01 A14 641 R01 A14 668 R01 A00 675 R01 A14 661 R01 A14 662 R01 A14[...]
-
Seite 83
83 OPTIONAL P ARTS 13 Note 1. How to connect refrigerant pipes. Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the connection takes no more than 5 minutes, no air will enter , and there will be no need for air purging. Remove the blind caps and make the connections within 5 minutes. [...]
-
Seite 84
84 ORN 1 2 3 BRN RED 3. TIMER ADAPTER This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page 57. Part No. P AC-SA89T A-E MITSUBISHI ELECTRIC SET MONITOR SMTWTFS GET BACK SET/MONITOR BACK AHEAD ON DAILY TIMER BACK SET BACK ON OFF OFF DEGREE SET BACK WEERLY TIMER TODAY CLOCK AHEAD Re[...]
-
Seite 85
85 1 2 3 4 5 BRN RED ORN YLW GRN BACK ACTIVE BYPASS POWER ON/OFF DUAL CENTRAL AHEAD MITSUBISHI ELECTRIC ENGAGED GROUP ACTIVE BYPASS GROUP SELECTION PROGRAM TIMER CONTROLLER OPERATION DUAL CENTRAL 1234567891 0 117 117 BACK ACTIVE BYPASS POWER ON/OFF DUAL CENTRAL AHEAD ENGAGED GROUP ACTIVE BYPASS GROUP SELECTION PROGRAM TIMER CONTROLLER OPERATION DUA[...]
-
Seite 86
86 A N E T (Y) (W) (R) (O) (BR) 5A A POWER SUPPLY N E Fuse(5A) Tie-wrap Wiring has to be changed when a 200,230 or 240V power is used. Tie-wrap TRANSFORMER Transmission TERMINAL-BLOCK FOR TRANSMISSION TERMINAL-BLOCK OF POWER SUPPLY 200 220 230 240 BACK ACTIVE BYPASS POWER ON/OFF DUAL CENTRAL AHEAD ENGAGED GROUP ACTIVE BYPASS GROUP SELECTION PROGRAM[...]
-
Seite 87
87 6. PROGRAM TIMER ADAPTER This adapter is needed when a program timer(P AC-SK65PT)or a centralized remote controller(P AC-805RC)is used. 6-2 Connection method Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out the work. 6-1 Parts included Part No. P AC-825AD (2) When the centralized re[...]
-
Seite 88
New publication, effective Jun. 1997 Specifications subject to change without notice c Copyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD. Issued in Jun. 1997. No. OC120 5020 OC120--3.qxp 24/6/97 1:05 AM Page 88[...]
-
Seite 89
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications are subject to ch ange without no tice.[...]