Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit manual
- Consulta online o descarga el manual de instrucciones
- 28 páginas
- 0.57 mb
Ir a la página of
manuales de instrucciones parecidos
-
Air Conditioner
Goodman Mfg 2- to 5-Tone Packaged Air Conditioner
24 páginas 0.57 mb -
Air Conditioner
Goodman Mfg Air Handler with Painted Cabinet
8 páginas 0.69 mb -
Air Conditioner
Goodman Mfg CKLB30-1
8 páginas 0.37 mb -
Air Conditioner
Goodman Mfg SS-DSZC18
32 páginas 0.93 mb -
Air Conditioner
Goodman Mfg ARUF363616CA
10 páginas 0.25 mb -
Air Conditioner
Goodman Mfg ARUF486016CA
10 páginas 0.25 mb -
Air Conditioner
Goodman Mfg CPC180
40 páginas 0.93 mb -
Air Conditioner
Goodman Mfg Split System Air Conditioner
20 páginas 0.53 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit debe contener:
- información acerca de las especificaciones técnicas del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
- nombre de fabricante y año de fabricación del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
- condiciones de uso, configuración y mantenimiento del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico Goodman Mfg en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual Goodman Mfg Light Commercial Self-Contained Packaged Heating & Cooling Unit. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR L IGHT C OMMERCIAL S ELF -C ONT AINED P ACKAGED H EA TING & C OOLING U NIT 3 T ON - 6 T ON CPC/CPH S ERIES Goodman Manufacturing Company , L.P . IO-399B 5151 Felipe, Suite 500, Houston, TX 77056 7/12 www .goodmanmfg.com www .amana-hac.com ©[...]
-
Página 2
2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the whit[...]
-
Página 3
3 T HIS UNIT MU ST NOT BE USED AS A “ CONST RUC TION HEATE R ” DURING THE FINISHING PHAS ES OF CONST RUC TION ON A NEW STRUCT UR E . T HIS TYPE OF USE MA Y RESU LT IN PREMAT UR E FAILURE OF THE UNIT DUE TO EXT REME LY LOW RETURN AIR TEMP ERAT URES AND EXPO SURE TO CORR OSIVE OR VER Y DIRT Y ATMO SPHE RES . W ARNING HI G H VO L T A G E ! D ISCO [...]
-
Página 4
4 a. Original Bill of Lading, certified copy , or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade and other discounts or reductions. d. Copy of the inspection report issued by carrier representative at the time damage is reported to the carrier . The carrier is[...]
-
Página 5
5 R OOF C URB I NSTALLATIONS O NLY : Curb installations must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association. Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prio[...]
-
Página 6
6 ROOF CURB POST -INST ALLA TION CHECKS After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly . Gasket should be firmly applied to the top of the curb perimeter , duct flanges and any exposed duct con- nection frame. If gasket is loose, reapply using strong weather resi[...]
-
Página 7
7 Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end. T o assist in determining rigging requirements, unit weights are shown as follows: A B C D CG SUPP LY RETURN EV APORA TOR COIL CONDENSER COIL COMPRESSOR Y X CORNER & CENTER OF GRAVITY LOCATIONS AB CD CP[...]
-
Página 8
8 T O PRE VENT SEVE RE DAMAG E TO THE BOTTOM OF THE UNIT , DO NOT FORK LIFT UNIT AFTER WOOD STRUT S HAVE BEEN REMOV ED . CAUTION Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a r[...]
-
Página 9
9 LOW VOLT AGE BLOCK MA IN PO WER LOW VO L T AGE ENTRANCE POWER THRU THE CURB CONTROL BOX F AILU RE OF UNIT DUE TO OPERATION ON IMP ROPER LINE VOLTAGE OR WITH EXC ESSI VE PHAS E UNBAL ANC E CONSTITUTES PRODUCT ABUSE AND WILL VO I D YO U R WARRANT Y AND MA Y CAUSE SEVE RE DAMAG E TO THE UNIT ELECTR ICAL COMPONE NTS . W ARN I NG Areas Without Conveni[...]
-
Página 10
10 CIRCULA TING AIR AND FIL TERS D UCTWORK The supply duct from the unit through a wall may be installed without clearance. However , minimum unit clearances must be maintained (see “Clearances” section). The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger . A cover sh[...]
-
Página 11
11 T OOLS R EQUIRED Refrigeration gauge and manifold V oltmeter Clamp-on ammeter Ohmmeter T est lead (Minimum #16 A WG with insulated alligator clips) Air temperature measuring device General refrigeration mechanics’ tools T EMPORARY H EATING O R C OOLING If the unit is to be used for temporary heating or cooling, a “S tartup, Adjustments, and [...]
-
Página 12
12 t = Span length, inches C = Center distance, inches D = Larger sheave diameter , inches d = Smaller sheave diameter , inches h = Deflection height, inches DRIVE BELT TENSION ADJUSTMENT BE L T DR IV E Use d Ne w A , A X Sta nda r d 3.0 to 4 .0 4. 2 ± .5 5. 5 ± . 5 0. 313 DE F L ECT I O N (in) DE F L ECT I O N FO RCE ( lbs) SH EA VE DIAM E T E R[...]
-
Página 13
13 1 1. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor , blower and fan should now be running with the reversing valve in the de-energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air . 12. If [...]
-
Página 14
14 E V A P O R A T O R COOLI NG SERV I C E VALVE SERVICE PO RT REVERSI NG VALVE C O N D E N S E R SERV I C E PORT COM PRES S OR SERV I C E PORT ACCUMULAT O R EXPANSION D EVI C E CH ECK VALVE ORI FI CE SERV I C E VALVE CHECK VA LVE ORIFI CE IN DO O R COI L DI ST RIBUTOR OUTD OOR CO I L E V A P O R A T O R HEAT I NG SERV I C E VALVE SERV I C E PORT R[...]
-
Página 15
15 DRIVE ADJUSTMENTS MOTOR SHEA VE ADJUSTMENTS V L , V M , & 2 VP V ARIABLE P ITCH K EY T YPE M OTOR S HEAVES The driving and driven motor sheaves should be in align- ment with each other and the shaft s parallel. V L & V M S HEAVES A DJUSTMENT 1. Loosen set screw “B” using a 5/32" Allen key . 2. Making half or full turns from clos[...]
-
Página 16
16 L UBRICATION The fan shaft bearings, the 1 to 2 HP supply fan motors the condenser fan motors and compressors are permanently lu- bricated. F UNCTIONAL P ARTS Refer to the unit Parts Catalog for a list of functional p arts. Parts are available from your distributor . SERVICE THE FOLLOWING INFORMA TION IS FOR USE BY QUALI- FIED SERVICE AGENCY ONL[...]
-
Página 17
17 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T ATIC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1287 1 .66 3 50 770 0. 20 1233 1 .63 3 42 815 0. 30 1176 1 .59 3 32 858 0. 40 1107 1 .55 3 20 891 0. 50 1044 1 .51 3 12 924 0. 60 965 1 .45 2 96 957 0. 1[...]
-
Página 18
18 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T ATIC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1602 2 .48 5 28 835 0. 20 1538 2 .37 5 06 878 0. 30 1474 2 .26 4 84 921 0. 40 1390 2 .15 4 60 950 0. 50 1306 2 .04 4 36 979 0. 10 1805 2 .84 6 20 935 0. [...]
-
Página 19
19 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 DOWN SHOT SP EED TAP E XTE RNAL S T ATIC PR E SSU R E ( ESP ) in w . c . S T ANDAR D CF M AM P S W ATTS R P M 0. 10 1 334 1.6 5 180 62 7 0. 20 1 286 1.7 5 192 66 5 0. 30 1 212 1.8 3 202 71 5 0. 40 1 144 1.9 4 216 75 9 0. 50 1 077 1.9 9 222 79 2 0. 60 1 039 2.1 0 238 83 0 0. 70 [...]
-
Página 20
20 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 HORIZONT AL SP EED TAP E XTE RNAL S T AT IC PR E SSU R E ( ESP ) in w . c . STANDAR D CF M AMP S W AT T S R PM 0. 10 1 355 1.57 174 59 9 0. 20 1 281 1.66 182 65 1 0. 30 1 235 1.76 196 69 3 0. 40 1 168 1.81 202 72 6 0. 50 1 118 1.94 218 77 5 0. 60 1 049 2.03 232 81 9 0. 70 9 82 [...]
-
Página 21
21 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD DOWN SHOT CP C/H0 36 ST AND AR D BEL T DR I VE DO W N SHO T CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 2 1 42 4 0. 3 0 1 2 39 0. 2 3 0. 4 152 0 0. 39 1 292 0.2 9 10 73 0 .22 77 9 0 .14 0. 6 14 39 0 .40 119 2 0. 30 9 44 0. 2 1 6 19 0 .1 2 0. 8 1 350 0. 4 2 11 01 0 . 31 86 4[...]
-
Página 22
22 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC DOWN SHOT CP C/H036 HI G H S T AT I C BE L T DRI V E DOWN S HOT CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 16 9 2 0 . 54 1 44 9 0. 4 1 1 1 73 0. 2 9 0. 8 167 8 0. 58 1 397 0.4 4 11 07 0 .3 1 85 4 0 .21 1. 0 16 81 0 . 65 138 1 0. 49 1 078 0. 3 4 7 94 0 .2 2 1. 2 1 681[...]
-
Página 23
23 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD HORIZONT AL CP C/H036 STAND ARD BE L T DRI VE HORI Z O NT AL CFM BHP C FM BHP CF M BH P C FM B HP C FM BHP CFM BH P 0. 2 1 65 8 0. 3 5 1 4 89 0. 2 8 0. 4 1 560 0. 3 6 13 39 0 . 28 112 9 0 .21 0. 6 16 82 0 .47 143 6 0. 36 1 196 0.2 7 9 49 0 .19 0. 8 1 581 0.5 0 13 54 0 .38 109 6 0. 28 8 2[...]
-
Página 24
24 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC HORIZONT AL CP C/H036 HI G H S T AT I C BE L T DRI V E HORIZO NTAL CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 1 74 2 0. 5 0 1 4 31 0. 3 6 0. 8 16 2 6 0 . 52 1 35 7 0. 3 9 1 0 78 0. 2 7 1 161 1 0. 56 1 31 5 0.4 2 10 11 0 . 28 1. 2 16 05 0 . 62 129 9 0. 46 9 76 0. 3 1 [...]
-
Página 25
25 APPENDIX B ELECTRICAL DA T A MIN. M AX . Q TY RLA LRA QTY H P R LA H P FLA 20 8 /2 3 0- 60 - 1 18 7 2 53 1 1 6. 6 7 7 9 1 1 / 4 1. 4 0 DD S T D S T A T I C 1 / 3 2. 5 DD S TD S TA T I C 1 / 3 2.5 BD ST D ST A T I C 1. 0 3 .8 46 0- 60 -3 41 4 5 06 1 5 .7 7 3 8. 0 1 1 / 4 0. 8 0 BD ST D S T A T I C 1 . 0 1. 9 57 5- 60 -3 51 8 6 33 1 3. 8 3 7. 0 1 [...]
-
Página 26
26 A TTENTION INST ALLING PERSONNEL Use only the heater kit specified for each model as dict ated by the table above. APPENDIX B ELECTRICAL DA T A UNIT HE AT ER KIT MO DE L NU M B ER MI N I MU M C F M EH K *-1 0 1 2 5 0 EH K *-1 5 1 2 5 0 EH K *-1 0 1 3 0 0 EH K *-1 5 1 4 0 0 EH K *-1 8 1 4 0 0 EH K *-1 0 1 7 0 0 EH K *-1 5 1 7 0 0 EH K *-2 0 1 8 0[...]
-
Página 27
27 APPENDIX C UNIT DIMENSIONS HORIZONTAL DISCHARGE VERTICAL DISCHARGE NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package. RETURN SUPPL Y 12” 17” 7 3/ 8” 11 ?[...]
-
Página 28
28 Goodman Manufacturing Company , L.P . 5151 Felipe, Suite 500, Houston, TX 77056 www .goodmanmfg.com www .amana-hac.com © 2010,2012 Goodman Manufacturing Company , L.P .[...]