Liebert GXT2-10000RT208 manual
- Consulta online o descarga el manual de instrucciones
- 56 páginas
- 2.51 mb
Ir a la página of
manuales de instrucciones parecidos
-
Power Supply
Liebert NfinityTM
44 páginas 2.28 mb -
Power Supply
Liebert NX UPS System
88 páginas 5.24 mb -
Power Supply
Liebert 300
7 páginas 0.28 mb -
Power Supply
Liebert GXT2 - 3X1
42 páginas 0.81 mb -
Power Supply
Liebert S3 Options
61 páginas 0.93 mb -
Power Supply
Liebert Ship-Ahead Input/Output Cabinet NXL
20 páginas 0.97 mb -
Power Supply
Liebert 350
2 páginas 0.89 mb -
Power Supply
Liebert 600T
129 páginas 3.14 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones Liebert GXT2-10000RT208. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica Liebert GXT2-10000RT208 o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual Liebert GXT2-10000RT208 se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales Liebert GXT2-10000RT208, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones Liebert GXT2-10000RT208 debe contener:
- información acerca de las especificaciones técnicas del dispositivo Liebert GXT2-10000RT208
- nombre de fabricante y año de fabricación del dispositivo Liebert GXT2-10000RT208
- condiciones de uso, configuración y mantenimiento del dispositivo Liebert GXT2-10000RT208
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de Liebert GXT2-10000RT208 no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de Liebert GXT2-10000RT208 y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico Liebert en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de Liebert GXT2-10000RT208, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo Liebert GXT2-10000RT208, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual Liebert GXT2-10000RT208. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
AC P ow er For Bu siness -Critical C ontin uit y™ Li eber t ® GXT2-10000R T208 ™ Us er Man ual–10kV A, 60 Hz, 120/208/240V DISCONTINUED PR ODUCT[...]
-
Página 2
DISCONTINUED P R O D U C T[...]
-
Página 3
i T ABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTI ONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 I NTRODUCTION AND S YSTEM D ESCRIPTION . . . . . . . . . . . . . [...]
-
Página 4
ii 8.3 Configuration Program—Installa tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 8.4 Establishing Communica tion Link with the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 8.5 Configuration Program—Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .[...]
-
Página 5
iii 11 . 0 C OMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 11.1 Communications Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 11.1.1 DB-9 Interface Port . . . . . . . . . . . . . . . . . . . . . . . . . .[...]
-
Página 6
iv FIGURES Figure 1 10 kVA Dual Inverter Liebert GXT2- 10000RT208, fron t and rear views . . . . . . . . . . . . . . . . . . . . 7 Figure 2 Internal battery pack and connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 3 Hardwire te rminal blocks . . . . . . . . . . . . . . . . . . . .[...]
-
Página 7
1 I MPORT ANT S AFET Y I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual co ntains important safety instructions. R ead all safety, instal lation and operat ing instructions befo re operating th e Uninterruptible P o wer System (UPS). Adhere to all warn ings on the unit and in this manual. Fol low all operating and user instructions. Indiv iduals w[...]
-
Página 8
2 When replacing batteries, replace with the same Li ebert authorized replacement battery kits. When replacing the power module, replace it with the sa me Liebert authoriz ed replacement power module kit. ! CAUTION Do not dispose of battery or batterie s in a fire. The battery may explode. Do not open or mutilate the battery or batteries. Released [...]
-
Página 9
Glossary of Symbols 3 1.0 G LOSSARY OF S YMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Battery[...]
-
Página 10
Introduction and System Descriptio n 4 2.0 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert G XT2-10000RT20 8 Uninterruptible Power Supply (UPS). It provides conditioned power to microcomp uters and other sensitive e lectronic equipment. Upon generation, AC power is clea n and stable. However, during transmission[...]
-
Página 11
System Description 5 3.0 S YSTEM D ESCRIPTION 3.1 T ransient V olt age Surge Suppr ession (TVSS) and EMI/RFI Filters These UPS components provide surge protection and filter both electroma gnetic interference (EMI) and radio frequency interference (RFI ). They minimize any surges or interference present in the util- ity line and keep the sensitive [...]
-
Página 12
System Description 6 3.5 DC to DC Converter The DC-to-DC converter utilizes energy from the batte ry system and raises the DC voltage to th e opti- mum operating voltage for the inverter. This allows the inverter to operate co ntinuously at its opti- mum efficiency and volt age, thus incre asing reliability. 3.6 Battery The Liebert GXT2-10000RT2 08[...]
-
Página 13
Major Compo nents 7 4.0 M AJOR C OMPONENT S The Liebert GXT2-10000RT208 is composed of three major assemblies to pr ovide easier handling, installation a nd versatility. 4.1 Main Frame and Electronics This 6U cabinet arrive s without internal batteries to lighten the UPS for easier insta llation. Once the cabinet has been placed in its final floor [...]
-
Página 14
Major Compo nents 8 4.3 Input/Output T erminal Blocks a nd Optional Output Distribution The UPS is shipped with hardwire terminal blocks. For maximum flexibility, additional distributi on options are available that provide the be nefit of output receptacle convenience. Figure 3 Hardwire terminal blocks Figure 4 Optional output distribution modules [...]
-
Página 15
What’ s Included 9 5.0 W HAT ’ S I NCLUDED The Liebert GXT2-10000RT208 is shipped with these items: • UPS user manual • Vertical display overlay • Front bezels - 3 • Top bezels - 3 • Battery cover grille • Power Module cover grille • Battery pack brackets - 2 • Liebert MultiL ink software CD • Liebert MultiL ink serial cable, [...]
-
Página 16
Installation and Configurat ion 10 6.0 I NST ALLATION AND C ONFIGURATION This section includes instructions on how to install, configure and pe rform initial electrical checks of your UPS installation. DO NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 7.0 - Initial Startup and Elec[...]
-
Página 17
Installation and Config uration 11 6.1.2 Inst alling the Adjust able Rack-Mount Kit—Sold Sep arately This kit contains pa rts needed to mount several different mode ls of UPS an d external battery cabi- nets into EIA310-D standard four-post racks that are 18- 32" deep (457-813mm). The weight limit per pair of adjustable rack-mou nting bracke[...]
-
Página 18
Installation and Config uration 12 4. Ge t eight (8) M4 screws an d eight (8) M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action. Fasten the rear member and the front member together using[...]
-
Página 19
Installation and Config uration 13 6.2 External Battery Cabinet Inst allation Optional Liebert external battery cabinets may be connected to the UPS to prov ide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. The external battery cabinet frame and battery ki ts are [...]
-
Página 20
Installation and Config uration 14 6.3 Connect Input/Output Power The UPS has hardwire terminal blocks for input and output electrical connections. Optional output distribution modules permit connecting additional loads to the UPS. These optional plug-and-play distribution modules offer different ty pes and numbers of connection plugs. 6.3.1 Distri[...]
-
Página 21
Installation and Config uration 15 6.3.2 Input & Output T erminal Block Connections Conduit entry holes are provided on the rear and side of the box. Input and ou tput wiring should not share the same conduit. For best performance, distribute all L-N loads evenly between L1 and L2. T able 1 Electrica l requirement s Input Current Rating Recomme[...]
-
Página 22
Installation and Config uration 16 6.3.3 Add an Output Power Distribution Module—Optional To add an option al output distribution module to the Liebert GXT2 10000RT208: 1. Remove the four screws securing the blank output distribution cover plate to the rear of the UPS. The cover is at top left corner in the tower co nfiguration and at the bottom [...]
-
Página 23
Installation and Config uration 17 6.4 Inst all the Internal Battery Packs To facilitate ship ping and instal lation, the Liebert GXT2-10000RT208 ships without the internal bat- tery packs installed. Once the UPS is installed in place, the internal battery packs must b e installed. 1. Unpack the two internal battery packs from thei r shipping conta[...]
-
Página 24
Initial Startup and Electrical Checks 18 7.0 I NITIAL S T ARTUP AND E LECTRICAL C HECKS Initial Startup and the Configuration Program —The UPS ships with a default 120 VAC L-N setting. This is also the most robu st setting in that it can operate with either input phase angle (120 or 180 degrees). Perform initial system checks first. If the UPS co[...]
-
Página 25
Initial Startup and Electrical Checks 19 18. Press the On button for one seco nd. The bypass indi cator will ligh t for several seconds before the UPS On indicator turns on continuously. If th e batteries are charged above 90% of capacity, automatic battery test will run f or about 15 seconds. 19. Close the Output circuit breaker on the rear of the[...]
-
Página 26
Configuration Prog ram 20 8.0 C ONFIGURATION P ROGRAM The final step of installat ion may require custom conf iguration of yo ur UPS using the en closed config- uration program. Some configuratio n settings may be changed only whil e the UPS is off. These should be set before the UPS is put into full time service powering the critical load. For mos[...]
-
Página 27
Configuration Prog ram 21 8.3 Configuration Program—Inst allation An easy-to-use installation progra m streamlines the installation of the configuration program. If you have a previous version of this configuration program installe d, Liebert recommends uninstall ing it by using its Uninsta ll program before installing this updated version. 1. Us[...]
-
Página 28
Configuration Prog ram 22 If this message is displayed check the following items: • Verify that the serial communicati on cable is connected properly. • Verify that the COM port being us ed is designated COM1 or COM2. • Verify that the UPS is either in Inverter mode, Bypass mode, Battery mode, or Off with AC power available at the input (AC I[...]
-
Página 29
Configuration Prog ram 23 8.5.4 On-Screen Reminders As pending chan ges are selected, on-screen messages will remind the user if the UPS may be On, or mu st be Off, for the setting to be pro- grammed once the Apply or OK button is pressed. If there are no changes, these me s- sages are shaded. Values displayed will only be tran smitted to the UPS w[...]
-
Página 30
Configuration Prog ram 24 8.6 UPS T ab When the program starts, the foll owing window will open displayi ng the UPS model along with the current UPS settings. This information can be refreshed at any time using the REFRESH button. These illustration s show the factory default settings for 120VAC UPS at the left, and output L- N volt- ages availabl [...]
-
Página 31
Configuration Prog ram 25 8.6.3 Frequency Selection The UPS is normally designed for 50Hz or 60Hz operation. The fact ory default corresponds to the model. All models are cap able of being used as 50 Hz or 60Hz systems. The UPS will Auto-sense the utility frequency when fi rst plugged in and set the nominal freque ncy to match. Therefore, for all n[...]
-
Página 32
Configuration Prog ram 26 8.8 Options T a b Used With Earlier Liebert GXT2 Models This version of the configuratio n program will accompany Liebert GXT2 UPS models that support new programming features accessible using the Op tions Tab. If Version 1.6 (or later) is used wi th an earlie r Liebert GXT2 model (with an earlier UPS firmware version), th[...]
-
Página 33
Configuration Prog ram 27 8.9 Battery T ab Factory default settings illustrat ed. 8.9.1 Low Battery Time W arning The UPS will estimate remaining op erating time when on batteries. A low battery alarm is activated if the estimated time reaches the Low Battery Time. This may be chan ged to any value from 2 to 30 minutes. 8.9.2 Auto Battery T est Tim[...]
-
Página 34
Configuration Prog ram 28 8.10 About T ab Version number may be confirmed using the About Tab. DISCONTINUED P R O D U C T[...]
-
Página 35
Controls and Indica tors 29 9.0 C ONTROLS AND I NDICATORS Figure 8 Control and indicator overla ys, vertical and horizont al 9.1 ON/Alarm Silence/ Battery T est Button This button controls output power to co nnected load(s) a nd has three function s: • ON • Alarm Silence • Manual Battery Test ON - Pressing this button will start up the UPS in[...]
-
Página 36
Controls and Indica tors 30 9.3 L1 & L2 Load Level Indicators (T wo Rows of Indicators: 4 Green, 1 Amber) The Load Level indicators di splay the approximate elec trical lo ad placed upon bo th output legs of the UPS at all times. Each indicator represents an approximate 25 percent i ncrease in load. For optimum utilization of the UPS, distribut[...]
-
Página 37
Modes of Operati on 31 10.0 M ODES OF O PERATION 10.1 Normal Mode Operation During normal operation, uti lity power provides energy to the UPS. The filters, power fa ctor correction circuit and the inverter process this power to provide computer g rade power to connected loads. Th e UPS maintains the batteries in a fully charged state. The f our gr[...]
-
Página 38
Communications 32 11 . 0 C OMMUNICATIONS 1 1.1 Communications Interface Port The Liebert GXT2-1000 0RT208 UPS has a standard DB-9 serial port female co nnector locate d on the rear of the UPS unit. Seve ral signals are provid ed on this port and are assigned as follo ws: 1 1.1.1 DB-9 Interface Port Using the foll owing directions to attach the smal[...]
-
Página 39
Communications 33 1 1.1.2 Communications—Liebert SNMP/OCWEBCARD SNMP Adapter Attach the larger enclosed ferrite bead clamp to the network cable, see il lustration at right, u sing the following directions: 1. Open the ferrite bead. 2. Place the network cable inside the ferrite bead groov e. 3. Wra p the cable once aroun d the ferrite bead. 4. Pos[...]
-
Página 40
Communications 34 1 1.4 Remote Emergency Power Off The UPS is equipped with a Remote Emergency Power Off (REPO) connector. The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input fe eder breake r to remove a ll sources of po wer to the UPS and connected equipment to comply with national and local wirin[...]
-
Página 41
Maintenance 35 12.0 M AINTENANCE The Liebert GXT2-10000RT208 requires very little maintenance. The batteries are valve-regul ated, non-spillable, flame retardant, lead acid and should be kept charged to obtain their design li fe. The UPS continuously charges the batteries when connected to the utility supply. When storing the UPS for any length of [...]
-
Página 42
Maintenance 36 12.2 UPS Power Modu le Replacement To remove the UPS power module without shutting off power to the connected load: 1. Place the UPS on internal bypass. This may be d one by any of the three foll owing methods: a. Press the Off button on the front panel one time. b. Sli de the bracket away from th e manual bypass switch on the rear o[...]
-
Página 43
Maintenance 37 Figure 10 UPS back panel—cont rol location Figure 1 1 Power module replacement O utput Breaker 60A 250V~/T Input Breaker 60A 250 V~/T Inver ter Bypass I nput O ut put ! UPStatio n GXT ! Power module pulled out of UPS (Ret aining grilles removed for clarity) DISCONTINUED P R O D U C T[...]
-
Página 44
Trou bleshooting 38 13.0 T ROUBLESHOOTING The information below indicates va rious symptoms a user may enco unter in the event the Liebert GXT2-10000RT208 develops a problem. Use this information to determine whether external factors caused the problem and h ow to remedy the situation. 1. The Fault indicator will illuminate, indicating the UPS has [...]
-
Página 45
Trou bleshooting 39 Under fault condit ions, the Fault indicators will be illuminat ed indefinitely while the battery cha rger is operational, or for a maximum of 5 minute s while the battery charger is not operational. If a problem persists, consult your local dealer, Li ebert representative or contact the Liebert World- wide Support Group. Please[...]
-
Página 46
Trou bleshooting 40 T able 5 T roubleshooting guide Problem Cause Solution UPS fails to start when the ON button is pressed. UPS is short-circuited o r overloaded. Ensure the UPS is OFF. Disconnect all loads and ensure nothing is lodged in output receptacle s. Ensure the loads are not defective or shorted internall y. Battery indicator is illuminat[...]
-
Página 47
Trou bleshooting 41 Fault indicato r and diagnostic indicators B and C are illuminated. REPO is currently activated. UPS has shut down due to the REPO (Remote Emergency Power Off). The output cannot be started by any method. Fault indicato r and diagnostic indicators B and D are illuminated. UPS output is OFF from a previous REPO command. REPO is n[...]
-
Página 48
Trou bleshooting 42 Using the configuration program, the user may specify the number of GX T2-288VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries on ly. Table 6 shows estimated run ti mes at different loads. T able 6 Battery run times Battery/External Cabinets Load% 10000VA Run Time in [...]
-
Página 49
Trou bleshooting 43 13.1 Auto-Learning Battery Run Times As batteries age, the estimated run times may be come less accurate. The Liebert GXT2-10000RT 208 is programmed to “learn” from a full battery disc harge and modify the esti mated run time for the measured battery capacity. This can improve accuracy and compensa te for aging batteries or [...]
-
Página 50
Specifications 44 14.0 S PECIFICATIONS T able 7 UPS specifications Model Number Liebert GXT2-10000RT208 Model Rating 8000W/8660VA at 127/220 (120 or 240 degrees only) 8000W/8660VA at 120/208 (120 or 240 degrees) 8000W/10000VA a t 120/240 (180 d egrees) 8000W/10000VA at 115/230 (180 degrees only) 7200W/9000VA at 110/220 (180 degrees only) 6400W/8000[...]
-
Página 51
Specifications 45 Bypass Protection Limits Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage Re-enable Bypass Operation If input voltage returns to within ±10% of nominal o utput voltage Disable Bypass Operation When the input frequency prevents synchronous operation ENVIRONMENTAL Operating Temp +32°F to +104°F (0°C[...]
-
Página 52
Specifications 46 T able 10 Optional output distri bution specificat ions—PD-102 Model Number PD-102 DIMENSIONS , W x D x H Shipping, in. (mm) 8.86 x 10.43 x 7.87 (225 x 265 x 200) WEIGHT lb (kg) Unit 4.6 (2.1) Shipping 6.0 (2.7) ELECTRICAL SPECIFICA TIONS Amp Rating 60 Amps Input Power Connections Internal Anderson connectors Output Pow er Conne[...]
-
Página 53
Specifications 47 14.1 Product W arranty Registration To register for warranty protection: • Visit the Quick Links section of our Websit e at: http://www.liebert.com • Click on Product Warranty Registration and fi ll in the form . If you have any questions, please contact us at: US: 800-222-5877 Outside the US: 614-841- 6755 upstech@emersonnetw[...]
-
Página 54
Specifications 48 DISCONTINUED P R O D U C T[...]
-
Página 55
DISCONTINUED P R O D U C T[...]
-
Página 56
EmersonNetworkPower.com Ensuring The Hi gh Av aila bilit y 0f Mission-Critic al Dat a And Appli ca tions. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures net work resiliency and adaptabilit y through a family of technologies—inc luding Lieber t powe r and cooling technologies—that prot ect and supp[...]