Mitsubishi Electronics H2iSD-1 manual
- Consulta online o descarga el manual de instrucciones
- 38 páginas
- 3.37 mb
Ir a la página of
manuales de instrucciones parecidos
-
Marine Battery
Mitsubishi Electronics FR-E700
242 páginas 15.34 mb -
Marine Battery
Mitsubishi Electronics FR-D740-0.4K to 15K
52 páginas 4.76 mb -
Marine Battery
Mitsubishi Electronics FR-A500
257 páginas 5.26 mb -
Marine Battery
Mitsubishi Electronics FR-A500L
63 páginas 1.6 mb -
Marine Battery
Mitsubishi Electronics FR-E710W
59 páginas 5.64 mb -
Marine Battery
Mitsubishi Electronics FR-D710W-0.1K to 0.75K
52 páginas 4.76 mb -
Marine Battery
Mitsubishi Electronics FR-D720S-0.1K to 2.2K
52 páginas 4.76 mb -
Marine Battery
Mitsubishi Electronics FR-V540-1.5K to 55K
232 páginas 5.2 mb
Buen manual de instrucciones
Las leyes obligan al vendedor a entregarle al comprador, junto con el producto, el manual de instrucciones Mitsubishi Electronics H2iSD-1. La falta del manual o facilitar información incorrecta al consumidor constituyen una base de reclamación por no estar de acuerdo el producto con el contrato. Según la ley, está permitido adjuntar un manual de otra forma que no sea en papel, lo cual últimamente es bastante común y los fabricantes nos facilitan un manual gráfico, su versión electrónica Mitsubishi Electronics H2iSD-1 o vídeos de instrucciones para usuarios. La condición es que tenga una forma legible y entendible.
¿Qué es un manual de instrucciones?
El nombre proviene de la palabra latina “instructio”, es decir, ordenar. Por lo tanto, en un manual Mitsubishi Electronics H2iSD-1 se puede encontrar la descripción de las etapas de actuación. El propósito de un manual es enseñar, facilitar el encendido o el uso de un dispositivo o la realización de acciones concretas. Un manual de instrucciones también es una fuente de información acerca de un objeto o un servicio, es una pista.
Desafortunadamente pocos usuarios destinan su tiempo a leer manuales Mitsubishi Electronics H2iSD-1, sin embargo, un buen manual nos permite, no solo conocer una cantidad de funcionalidades adicionales del dispositivo comprado, sino también evitar la mayoría de fallos.
Entonces, ¿qué debe contener el manual de instrucciones perfecto?
Sobre todo, un manual de instrucciones Mitsubishi Electronics H2iSD-1 debe contener:
- información acerca de las especificaciones técnicas del dispositivo Mitsubishi Electronics H2iSD-1
- nombre de fabricante y año de fabricación del dispositivo Mitsubishi Electronics H2iSD-1
- condiciones de uso, configuración y mantenimiento del dispositivo Mitsubishi Electronics H2iSD-1
- marcas de seguridad y certificados que confirmen su concordancia con determinadas normativas
¿Por qué no leemos los manuales de instrucciones?
Normalmente es por la falta de tiempo y seguridad acerca de las funcionalidades determinadas de los dispositivos comprados. Desafortunadamente la conexión y el encendido de Mitsubishi Electronics H2iSD-1 no es suficiente. El manual de instrucciones siempre contiene una serie de indicaciones acerca de determinadas funcionalidades, normas de seguridad, consejos de mantenimiento (incluso qué productos usar), fallos eventuales de Mitsubishi Electronics H2iSD-1 y maneras de solucionar los problemas que puedan ocurrir durante su uso. Al final, en un manual se pueden encontrar los detalles de servicio técnico Mitsubishi Electronics en caso de que las soluciones propuestas no hayan funcionado. Actualmente gozan de éxito manuales de instrucciones en forma de animaciones interesantes o vídeo manuales que llegan al usuario mucho mejor que en forma de un folleto. Este tipo de manual ayuda a que el usuario vea el vídeo entero sin saltarse las especificaciones y las descripciones técnicas complicadas de Mitsubishi Electronics H2iSD-1, como se suele hacer teniendo una versión en papel.
¿Por qué vale la pena leer los manuales de instrucciones?
Sobre todo es en ellos donde encontraremos las respuestas acerca de la construcción, las posibilidades del dispositivo Mitsubishi Electronics H2iSD-1, el uso de determinados accesorios y una serie de informaciones que permiten aprovechar completamente sus funciones y comodidades.
Tras una compra exitosa de un equipo o un dispositivo, vale la pena dedicar un momento para familiarizarse con cada parte del manual Mitsubishi Electronics H2iSD-1. Actualmente se preparan y traducen con dedicación, para que no solo sean comprensibles para los usuarios, sino que también cumplan su función básica de información y ayuda.
Índice de manuales de instrucciones
-
Página 1
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-1 2010 H2i ® Y-SERIES SYSTEM DESIGN CITY MUL TI ® H2I ® Y -SERIES HYPER-HEA TING INVERTER SYSTEM DESIGN 1. ELECTRICAL WORK ........................................................................................................................................... H2iSD-2 1-1. General C[...]
-
Página 2
H2iSD-2 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK OK NO F ollow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power compan y. Wiring for control (hereinafter referred to as trans[...]
-
Página 3
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-3 2010 H2i ® Y-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK 1-2. Power Supply for Indoor and Outdoor Units 1-2-1. Electrical Characteristics of the Indoor Units Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load Amps IFM :Indoor Fan Motor Output : Fan motor rated output Model Indoor[...]
-
Página 4
H2iSD-4 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK Symbols: MCA : Min.Circuit Amps (=1.25xFLA) FLA : Full Load Amps IFM :Indoor Fan Motor Model Indoor Unit IFM Hz V olts V oltage range MCA(A) FLA(A) PCFY -P15NKMU-E 60Hz 208 / 230V 188 to 253V 0.44 / 0.44 0.35 / 0.35 PCFY -P24NKMU-E [...]
-
Página 5
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-5 2010 H2i ® Y-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK PUHY -HP-T(S)JMU Symbols: MC A : Min. Circuit Amps SC : Starting Current RLA 15 15 15 15 15 15 0.92 0.92 0.92 0.92 0.92 0.92 Model Outdoor Units V olts Hz Unit Combination V oltage range MOCP MCA(A) Compressor Output(kW) SC(A) Fan R[...]
-
Página 6
H2iSD-6 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-1. T ransmission Cable Length Limitations Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission. Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, [...]
-
Página 7
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-7 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-2. T ransmission Cable Specications T ype of cable Cable size Remarks Sheathed 2-core cable (unshielded) CVV 2 Shielding wire (2-core) CVVS, CPEVS or MVVS Transmission cable sM E Remote controller cables CVVS, MVVS : PVC insulate[...]
-
Página 8
H2iSD-8 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-3. System Conguration Restrictions Fo r each Outdoor unit, the maximum connecta bl e quantity of Indoor unit is specified at its Specifications ta bl e. A) 1 Group of Indoor units can ha ve 1-16 Indoor units; B) Maximum 2 remote [...]
-
Página 9
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-9 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL The power to System controller (excluding LMAP03-U) is supplied via M-NET transmission line. M-NET transmission line at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission l[...]
-
Página 10
H2iSD-10 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 1-phase 208-230V AC power supply is needed. The power supply unit P AC-SC51KUA is not necessary when connecting only the LMAP03U. Ye t, make sure to change the power supply changeover connector CN41 to CN40 on the LM adapter . 2-3-4.[...]
-
Página 11
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-1 1 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4. Address Setting Branch No. setting Unit address No. setting Rotary switch In order to constitute CITY MUL TI in a complete system, switch operation for setting the unit address No. and connection No. is required. À Address No.[...]
-
Página 12
H2iSD-12 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-2. Rule of setting address Unit Indoor unit ME, LOSSNA Y Remote controller (Main) ME, LOSSNA Y Remote controller (Sub) Address setting 01 ~ 50 52 ~ 99, 100 101 ~ 150 151 ~ 199, 200 Note Example The address of outdoor unit + 1 Ple[...]
-
Página 13
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-13 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-1. MA remote controller , Single-refrigerant-system, No System Controller Original switch setting of the outdoors, indoors, controllers and LMAP at shipment is as follows. Outdoor unit : Address: 00, CN41: U (Jumper), DipSW2-1:[...]
-
Página 14
H2iSD-14 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2. Address should be set to Indoor units and central controller. 3. For a system having more than 16 indoor unit, confirm the need of Booster at 2-3 "System configuration restrictions". NOTE: 1. Outdoor units OC and OS in o[...]
-
Página 15
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-15 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-3. MA remote controller , Multi-refrigerant-system, System Controller at TB7 side, Booster for long M-NET wiring *3 When multiple system controllers are connected in the system, set the controller with more functions than other[...]
-
Página 16
H2iSD-16 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-4. ME remote controller , Single-refrigerant-system, No system controller 2-4-3-5. ME remote controller , Single-refrigerant-system, System controller , LOSSNA Y 2. Address should be set to Indoor units, system controller and M[...]
-
Página 17
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-17 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-6. ME remote controller , Multi-refrigerant-system, System Controller at TB 7side, LOSSNA Y, Booster for M-NET wiring 2. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the[...]
-
Página 18
H2iSD-18 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-7. ME remote controller , Multi-refrigerant-system, No Power supply unit NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board (only one outdoor unit) when the group is set between other refrige[...]
-
Página 19
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-19 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-9. TG-2000A + AG-150A/GB-50A AG-150A can control max. 50 indoor units. AG-150A can control max. 150 indoor units via expansion controllers (P AC-YG50ECA). TG-2000A can control max. 40 pieces of AG-150A*1 or GB-50A; TG-2000A can[...]
-
Página 20
H2iSD-20 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3-10. LMAP LMAP(01) 24VDC ( L ON W ORKS adapter) PC L ON W ORKS card L ON W ORKS card L ON W ORKS card For other equipments (Lighting, security, elevator etc.) LMAP can transmit for max. 50 indoor units in single-refrigerant-syst[...]
-
Página 21
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-21 2010 H2i ® Y-SERIES SYSTEM DESIGN 2. M-NET CONTROL 2-4-3- 11 . BM ADAPTER BM ADAPTER(01) HUB For other equipments (Lighting, security , elevator etc.) BM ADAPTER can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system. 000 BAC net BM ADAPTER(02)[...]
-
Página 22
H2iSD-22 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 3-1. R410A Piping Material 3. PIPING DESIGN Refrigerant pipe for CITY MUL TI shall be made of phosphor us deo xidized copper , and has two types . A . Ty pe-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand. B . T[...]
-
Página 23
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-23 2010 H2i ® Y-SERIES SYSTEM DESIGN 3. PIPING DESIGN 3-2. Piping Design Ta ble3-2-1-6. R410A Joint selection rule To tal down-stream Indoor capacity Joint ~ P72 CMY -Y102S-G2 P 73 ~ P144 CMY -Y102L-G2 P 145 ~ P234 CMY -Y202-G2 P 235 ~ CMY -Y302-G2 *Concerning detailed usage of Joint pa[...]
-
Página 24
H2iSD-24 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 3. PIPING DESIGN T able3-2-2-4. R410A Joint selection rule To tal down-stream Indoor capacity Joint ~ P7 2C MY -Y102S-G2 P7 3~ P144 CM Y- Y102L-G2 P145 ~ P234 CM Y- Y202-G2 *First Joint is always CM Y- Y202-G2; *Concerning detailed usage of Joint par[...]
-
Página 25
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-25 2010 H2i ® Y-SERIES SYSTEM DESIGN 3. PIPING DESIGN 3-3. Refrigerant Charge Calculation (1) Calculation of additional refrigerant charge Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant line. Use the table to the bel[...]
-
Página 26
H2iSD-26 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 1. Do not install in an area where the unit could be subjected to direct heat. 2. Av oid installing the unit in a location where the operating sound could be an annoyance. 3. Av oid the sites where strong winds blow . 4. Ins[...]
-
Página 27
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-27 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 1000 [39-3/8] 240 [9-15/32] 45° 50 [1-31/32] <C> (Unit : mm [in.]) <B> 500 [19-11/16] H h h H 100* [3-15/16] 450* [17-23/32] 50* [1-31/32] 50* [1-31/32] <A> (1) If the distance is 300 mm [11-13/16 in.] or [...]
-
Página 28
H2iSD-28 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION In case of collective installation and continuous installation : : Wall height (H) (Unit : mm [in.]) A B C 30 450* 300* 100 450* 100* 450* 100* 450 450 15* 450 450 900 300* 300* 1000* 900 300* • When multiple units are ins[...]
-
Página 29
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-29 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-3. Piping Direction 4-3-1. Lifting method · When lifting the unit with ropes, run the ropes under the unit and use the lifting hole. · Support the unit at four points with two ropes, and avoid giving mechanical shock. ·[...]
-
Página 30
H2iSD-30 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-3-2. Installation 30mm [1-3/16in] Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure is securely supported. The brackets may bend if they are not securely suppor[...]
-
Página 31
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-31 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-3-5. Refrigerant pipe routing 4-3-4. Installation Installation base perpendicular to the unit’s front panel Installation base parallel to the unit’s front panel When the pipes and/or cables are routed at the bottom of [...]
-
Página 32
H2iSD-32 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-3-6. Tw inning on the outdoor unit side Reducer ± 15° The tilt angle of the reducer should be within ±15° with the horizontal plane. Note: See the following drawing for the fitting position of the twinning pipe. The ti[...]
-
Página 33
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-33 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION Field piping Field piping Tw inning kit The length of the straight pipe must be 500 mm [19 in. ] or longer See the fo llo wing dr aw ing for connecting the pipes between the outdoor units. <PUHY -HP144 TSJMU-A> <PUH[...]
-
Página 34
H2iSD-34 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-4. Weather Countermeasures • Snow hood Countermeasure to wind Outlet Inlet Referring to the figure shown below, take appropriate measures which will suit the actual situation of the place for installati on. Note: 1.Heigh[...]
-
Página 35
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-35 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION 4-5. Low Ambient Kit Application Guidelines General Unit Placement and Clearances • Outdoor units should be located in an area protected from prevailing winds. • In high wind locations, it may be advisable to insta[...]
-
Página 36
H2iSD-36 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 4. OUTDOOR INST ALLA TION Safety strap Prov ided by others Important! For al l roof t op installat ions, saf ety stra ps must be attac hed be tween t he hood(s ) and t he uni t mounti ng str ucture. Additional Rooftop Mounting Guidelines Ground-level[...]
-
Página 37
2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) H2iSD-37 2010 H2i ® Y-SERIES SYSTEM DESIGN 5. ST ANDARD AND SEACOAST (BS) PROTECTION TREA TMENT Component Base Material Standard Models Seacoast Protection Models (-BS) Surface T reatment Coating Thickness External Surface Internal Surface External Panel Base Alloyed Galvanized Steel Sheet ?[...]
-
Página 38
H2iSD-38 2010 Hyper-heating Y -SERIES SYSTEM DESIGN (Sept. 2010) 2010 H2i ® Y-SERIES SYSTEM DESIGN 6. CAUTIONS R410A refrigerant is harmless and incombustible. R410A is heavier than the indoor air in density . Leakage of the refrigerant in a room has possibility to lead to a hypoxia situation. Therefore, the critical concentration specified below [...]