York CHAMPION D2EB manuel d'utilisation
- Voir en ligne ou télécharger le manuel d’utilisation
- 16 pages
- 0.37 mb
Aller à la page of
Les manuels d’utilisation similaires
-
Air Conditioner
York YCAL0065
80 pages 1.86 mb -
Air Conditioner
York H*RD036 THRU 060
24 pages 0.24 mb -
Air Conditioner
York GFD
12 pages 0.27 mb -
Air Conditioner
York D1HE/D1HG036
28 pages 3.38 mb -
Air Conditioner
York 66441-YUM-D-1011
7 pages 0.31 mb -
Air Conditioner
York DJ 036
48 pages 0.68 mb -
Air Conditioner
York 10
12 pages 0.26 mb -
Air Conditioner
York SINGLE PACKAGE AIR CONDITIONING CU060
28 pages 3.64 mb
Un bon manuel d’utilisation
Les règles imposent au revendeur l'obligation de fournir à l'acheteur, avec des marchandises, le manuel d’utilisation York CHAMPION D2EB. Le manque du manuel d’utilisation ou les informations incorrectes fournies au consommateur sont à la base d'une plainte pour non-conformité du dispositif avec le contrat. Conformément à la loi, l’inclusion du manuel d’utilisation sous une forme autre que le papier est autorisée, ce qui est souvent utilisé récemment, en incluant la forme graphique ou électronique du manuel York CHAMPION D2EB ou les vidéos d'instruction pour les utilisateurs. La condition est son caractère lisible et compréhensible.
Qu'est ce que le manuel d’utilisation?
Le mot vient du latin "Instructio", à savoir organiser. Ainsi, le manuel d’utilisation York CHAMPION D2EB décrit les étapes de la procédure. Le but du manuel d’utilisation est d’instruire, de faciliter le démarrage, l'utilisation de l'équipement ou l'exécution des actions spécifiques. Le manuel d’utilisation est une collection d'informations sur l'objet/service, une indice.
Malheureusement, peu d'utilisateurs prennent le temps de lire le manuel d’utilisation, et un bon manuel permet non seulement d’apprendre à connaître un certain nombre de fonctionnalités supplémentaires du dispositif acheté, mais aussi éviter la majorité des défaillances.
Donc, ce qui devrait contenir le manuel parfait?
Tout d'abord, le manuel d’utilisation York CHAMPION D2EB devrait contenir:
- informations sur les caractéristiques techniques du dispositif York CHAMPION D2EB
- nom du fabricant et année de fabrication York CHAMPION D2EB
- instructions d'utilisation, de réglage et d’entretien de l'équipement York CHAMPION D2EB
- signes de sécurité et attestations confirmant la conformité avec les normes pertinentes
Pourquoi nous ne lisons pas les manuels d’utilisation?
Habituellement, cela est dû au manque de temps et de certitude quant à la fonctionnalité spécifique de l'équipement acheté. Malheureusement, la connexion et le démarrage York CHAMPION D2EB ne suffisent pas. Le manuel d’utilisation contient un certain nombre de lignes directrices concernant les fonctionnalités spécifiques, la sécurité, les méthodes d'entretien (même les moyens qui doivent être utilisés), les défauts possibles York CHAMPION D2EB et les moyens de résoudre des problèmes communs lors de l'utilisation. Enfin, le manuel contient les coordonnées du service York en l'absence de l'efficacité des solutions proposées. Actuellement, les manuels d’utilisation sous la forme d'animations intéressantes et de vidéos pédagogiques qui sont meilleurs que la brochure, sont très populaires. Ce type de manuel permet à l'utilisateur de voir toute la vidéo d'instruction sans sauter les spécifications et les descriptions techniques compliquées York CHAMPION D2EB, comme c’est le cas pour la version papier.
Pourquoi lire le manuel d’utilisation?
Tout d'abord, il contient la réponse sur la structure, les possibilités du dispositif York CHAMPION D2EB, l'utilisation de divers accessoires et une gamme d'informations pour profiter pleinement de toutes les fonctionnalités et commodités.
Après un achat réussi de l’équipement/dispositif, prenez un moment pour vous familiariser avec toutes les parties du manuel d'utilisation York CHAMPION D2EB. À l'heure actuelle, ils sont soigneusement préparés et traduits pour qu'ils soient non seulement compréhensibles pour les utilisateurs, mais pour qu’ils remplissent leur fonction de base de l'information et d’aide.
Table des matières du manuel d’utilisation
-
Page 1
GENERAL Model D2EB units are factory assembled cooling only air condi- tioners designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide electric heat combined with electric cooling. All units and heaters are certified by CSA. The units are completely assembled on rigid, but easil[...]
-
Page 2
LIMIT ATIONS These units must be installed in accordance with the following national and local safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions). 2. Local plumbing and waste water codes and other applica - ble local codes. Refer to T able 1 for unit application data and to T able [...]
-
Page 3
CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com - bustion, construction, servicing and proper unit operation. WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet. DUCT WORK These units are adaptable to downflow [...]
-
Page 4
POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFP A No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or , in their absence, with the N.E.C./C.E.C. V oltage toler - ances which must be maintained at the compressor terminals during[...]
-
Page 5
174065-YIM-A-0206 Unitary Products Group 5 MODEL DEB POWER SUP - PL Y VOL TAGE LIMIT ATIONS 1 COMPRESSOR COND. FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, AMPS 2 MAX. HACR BREAKER SIZE, AMPS UNIT POWER F ACTOR TRANSFORMER SIZE (V A) MIN. MAX. RLA LRA 018 208/230-1-60 187 253 9.0 48.0 1.1 2.6 14.9 20 20 .9[...]
-
Page 6
174065-YIM-A-0206 6 Unitary Products Group DEB POWER SUPPL Y COMPRESSOR COND. FA N MOTOR FLA SUPPL Y AIR BLOWER MOTOR, FLA ELECTRIC HEA T ACCESSORY MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, 1 AMPS MAX. HACR 2 BREAKER SIZE MODEL RLA LRA MODEL NO. ST AGE KW TOT AL AMPS 018 208/230-1-60 9.0 48.0 1.1 2.6 2NH04500506 2NH04500706 1 2 3.8/5.0 * 5.6/7.5 * [...]
-
Page 7
Checking Supply Air CFM T o check the supply air CFM after the initial balancing has been completed: 1.Remove the two ¼ inch dot plugs in the duct panel. 2.Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil. 3.Using an inclined manometer , determine the p[...]
-
Page 8
8 Unitary Products Group 174065-YIM-A-0206 T ABLE 7 - SUPERHEA T CHARGING T ABLE FOR MODEL D2EB024 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 13.5 15.0 16.5 18.0 19.6 21.1 22.6 23.9 25.3 26.6 27.9 70 10.1 1 1.8 13.5 15.2 16.9 18.6 20.3 21.9 23.4 [...]
-
Page 9
Unitary Products Group 9 174065-YIM-A-0206 T ABLE 10 - SUPERHEA T CHARGING T ABLE FOR MODEL D2EB042 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 20.3 21.9 23.5 25.0 26.6 28.1 29.7 30.6 31.6 32.6 33.6 70 16.7 18.5 20.3 22.1 23.9 25.7 27.5 28.6 29.[...]
-
Page 10
10 Unitary Products Group 174065-YIM-A-0206 FIG . 3 - DIMENSIONS AND CLEARANCES CLEARANCES (Minimum) Front 12" Back 0" Left Side (Filter Access) 24" Right Side 24" Below Unit 1 0" Above Unit 2 36" (For Condenser Air Discharge) Units may be installed on combustible floors made from wood or class A, B or C roof covering [...]
-
Page 11
Cooling The following sequences of operation are based on using a standard single-stage cooling thermost at. WITH POWER TO UNIT AND THERMOST A T IN COOLING MODE. 1. If the fan switch on the thermostat is in the “ON” position, the 24 volts at “G” will energize the “K1" relay on the fan control board, close the ”K1" relay contac[...]
-
Page 12
12 Unitary Products Group 174065-YIM-A-0206 NORMAL MAINTENANCE WARNING: Prior to any of the following maintenance proce - dures, shut off all power to the unit, to avoid per - sonal injury . Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil. FILTERS - Inspect once a month. Replace Disposable or c[...]
-
Page 13
Unitary Products Group 13 174065-YIM-A-0206 FIG . 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPL Y) POWER SUPPLY 208/230-1-60 USE COPPER CONDUCTORS ONLY SECONDARY POWER SUPPLY FOR DUAL POINT ELEC HEAT 208/230-1-60 USE COPPER CONDUCTORS ONLY (HTR5) (HTR4) (HTR3) (HTR2) (M1) 705/PR 708/PR 716/PR 713/PR 710/PR F6 F4 F2 (K6) (K4) (K5) (K3) (M1) 7[...]
-
Page 14
14 Unitary Products Group 174065-YIM-A-0206 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND CB CCH COMPR DS F1 F2 F3 F4 F5 F6 F7 F8 F9 F24 FS HP HTR 1 HTR 2 HTR 3 HTR 4 HTR 5 HTR 6 K1 K2 K3 K7 LP LS M1 M2 M3 PTCR RC1/RC2 RC1 RC2 RC3 RV S S2/P2 S3/P3 S4/P4 S3/P3 T1 TB2 CIRCUIT BREAKER 24V , 3 AMP CRANKCASE HEA TER (OPTIONAL) COMPRESSOR DE[...]
-
Page 15
Unitary Products Group 15 174065-YIM-A-0206 NOTES[...]
-