Mitsubishi Electronics PKH18FL manuale d’uso
- Visualizza on-line o scarica il manuale
- 53 pagine
- 1.41 mb
Vai alla pagina of
Manuali d’uso simili
-
Air Conditioner
Mitsubishi Electronics PKH18FL
53 pagine 1.41 mb -
Air Conditioner
Mitsubishi Electronics PKA-A36KA.TH
32 pagine 3.32 mb -
Air Conditioner
Mitsubishi Electronics PUH24EK
89 pagine 2.26 mb -
Air Conditioner
Mitsubishi Electronics PUHY-HP-THMU-A
36 pagine 3.81 mb -
Air Conditioner
Mitsubishi Electronics MSZ-FD09NA
40 pagine 2.71 mb -
Air Conditioner
Mitsubishi Electronics SKM35ZD-S
42 pagine 2.56 mb -
Air Conditioner
Mitsubishi Electronics PLFY-P-VLMD-E
15 pagine 0.74 mb -
Air Conditioner
Mitsubishi Electronics MSZ-GA24NA
32 pagine 4.4 mb
Un buon manuale d’uso
Le regole impongono al rivenditore l'obbligo di fornire all'acquirente, insieme alle merci, il manuale d’uso Mitsubishi Electronics PKH18FL. La mancanza del manuale d’uso o le informazioni errate fornite al consumatore sono la base di una denuncia in caso di inosservanza del dispositivo con il contratto. Secondo la legge, l’inclusione del manuale d’uso in una forma diversa da quella cartacea è permessa, che viene spesso utilizzato recentemente, includendo una forma grafica o elettronica Mitsubishi Electronics PKH18FL o video didattici per gli utenti. La condizione è il suo carattere leggibile e comprensibile.
Che cosa è il manuale d’uso?
La parola deriva dal latino "instructio", cioè organizzare. Così, il manuale d’uso Mitsubishi Electronics PKH18FL descrive le fasi del procedimento. Lo scopo del manuale d’uso è istruire, facilitare lo avviamento, l'uso di attrezzature o l’esecuzione di determinate azioni. Il manuale è una raccolta di informazioni sull'oggetto/servizio, un suggerimento.
Purtroppo, pochi utenti prendono il tempo di leggere il manuale d’uso, e un buono manuale non solo permette di conoscere una serie di funzionalità aggiuntive del dispositivo acquistato, ma anche evitare la maggioranza dei guasti.
Quindi cosa dovrebbe contenere il manuale perfetto?
Innanzitutto, il manuale d’uso Mitsubishi Electronics PKH18FL dovrebbe contenere:
- informazioni sui dati tecnici del dispositivo Mitsubishi Electronics PKH18FL
- nome del fabbricante e anno di fabbricazione Mitsubishi Electronics PKH18FL
- istruzioni per l'uso, la regolazione e la manutenzione delle attrezzature Mitsubishi Electronics PKH18FL
- segnaletica di sicurezza e certificati che confermano la conformità con le norme pertinenti
Perché non leggiamo i manuali d’uso?
Generalmente questo è dovuto alla mancanza di tempo e certezza per quanto riguarda la funzionalità specifica delle attrezzature acquistate. Purtroppo, la connessione e l’avvio Mitsubishi Electronics PKH18FL non sono sufficienti. Questo manuale contiene una serie di linee guida per funzionalità specifiche, la sicurezza, metodi di manutenzione (anche i mezzi che dovrebbero essere usati), eventuali difetti Mitsubishi Electronics PKH18FL e modi per risolvere i problemi più comuni durante l'uso. Infine, il manuale contiene le coordinate del servizio Mitsubishi Electronics in assenza dell'efficacia delle soluzioni proposte. Attualmente, i manuali d’uso sotto forma di animazioni interessanti e video didattici che sono migliori che la brochure suscitano un interesse considerevole. Questo tipo di manuale permette all'utente di visualizzare tutto il video didattico senza saltare le specifiche e complicate descrizioni tecniche Mitsubishi Electronics PKH18FL, come nel caso della versione cartacea.
Perché leggere il manuale d’uso?
Prima di tutto, contiene la risposta sulla struttura, le possibilità del dispositivo Mitsubishi Electronics PKH18FL, l'uso di vari accessori ed una serie di informazioni per sfruttare totalmente tutte le caratteristiche e servizi.
Dopo l'acquisto di successo di attrezzature/dispositivo, prendere un momento per familiarizzare con tutte le parti del manuale d'uso Mitsubishi Electronics PKH18FL. Attualmente, sono preparati con cura e tradotti per essere comprensibili non solo per gli utenti, ma per svolgere la loro funzione di base di informazioni e di aiuto.
Sommario del manuale d’uso
-
Pagina 1
TECHNICAL & SER VICE MANUAL SPLIT -TYPE, HEA T PUMP AIR CONDITIONERS CONTENTS 1. FEA TURES ·······························································2 2. P ART NAMES AND FUNCTIONS ····························3 3. SPECIFICA TIONS ··········?[...]
-
Pagina 2
2 1 FEA TURES Indoor unit Remote controller Models Cooling capacity / Heating capacity SEER PKH18FL 18,000 / 18,600 [25,100] Btu/h 1 1.1 PKH24FL 24,000 / 25,000 [31,500] Btu/h 10.2 PKH30FL 30,000 / 33,000 [40,500] Btu/h 10.6 PKH36FL 34,200 / 38,000 [45,500] Btu/h 10.5 1. COMP ACT DESIGN The PKH series models have been downsized and now require such[...]
-
Pagina 3
3 P ART NAMES AND FUNCTIONS 2 ● Wireless remote controller ● When cover is open. ON/OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODEL SELECT NOT AVAILABLE SWING CHECK FAN TEST RUN ˚F ˚C AMPM STOP START AMPM COOL DRY AUTO FAN HEAT V ANE CONTROL button Used to change the air flow direction. CLOCK butt[...]
-
Pagina 4
4 3 SPECIFICA TIONS FK 1 :48 -41 Capacity Moisture removal Power Consumption EER SEER HSPF COP INDOOR UNIT MODELS External finish Power supply Max.fuse size (time delay) Min.ampacity Fan motor Booster heater Airflow Hi-Lo Sound level Hi-Lo Unit drain pipe O.D. Dimensions Weight OUTDOOR UNIT MODELS External finish Power supply Max.fuse size (time de[...]
-
Pagina 5
5 D ATA 4 Models Models Outdoor intake air DB temperature ( ˚F ) PKH18FL 71 67 63 62.5 60 59 71 67 63 62.5 60 59 71 67 63 62.5 60 59 71 67 63 62.5 60 59 TC 21.0 19.5 18.2 18.1 17.2 16.8 27.9 26.1 24.3 24.1 23.0 22.5 34.9 32.6 30.4 30.2 28.8 28.2 39.8 37.1 34.7 34.4 32.8 32.2 SHC 14.4 16.0 17.4 15.5 15.1 14.5 16.1 18.5 20.5 18.0 17.6 17.0 21.5 24.5[...]
-
Pagina 6
6 Models Models Outdoor intake air WB temperature ( ˚F ) PKH18FL 75 70 65 75 70 65 75 70 65 75 70 65 CA 12.1 12.4 12.7 16.3 16.6 17.0 21.5 21.9 22.5 24.7 25.3 25.9 PC 1.20 1.16 1.1 1 1.82 1.76 1.69 2.32 2.24 2.15 2.71 2.62 2.53 CA 14.1 14.4 14.7 18.9 19.4 19.8 25.0 25.5 26.1 28.7 29.4 30.1 PC 1.34 1.29 1.24 2.03 1.96 1.89 2.59 2.50 2.40 3.04 2.93 [...]
-
Pagina 7
7 SHF=0.71 Does not include booster heater (1.9kW) T otal power consumption (kW) T otal capacity (x10 3 Btu/h) 30 35 24 18 12 3.0 2.5 2.0 1.5 15 25 35 45 55 65 T otal power consumption (kW) T otal capacity (x10 3 Btu/h) Outdoor intake air DB temperature ( F) Outdoor intake air WB temperature ( F) 36 30 24 18 12 3.0 2.5 2.0 1.5 63 67 71 63 67 71 02 [...]
-
Pagina 8
8 NOTES : A point on the curve shows the reference point. COOLING CAP ACITY HEA TING CAP ACITY COOLING CAP ACITY HEA TING CAP ACITY 71 67 63 71 67 63 42 36 30 24 4.0 3.5 3.0 2.5 2.0 SHF=0.75 Total capacity(x10 Btu/h) 3 Total power consumption(kW) Outdoor intake air DB temperature( ° F) 0 23 32 35 45 55 65 (67) 75 85 95 105 115 indoor intake air WB[...]
-
Pagina 9
9 3. CONDENSING PRESSURE AND SUCTION PRESSURE Data is based on the condition under indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. <PKH18FL> Data is based on the condition under outdoor humidity 75%. A point on the curve shows the reference point. 350 340 330 320 310 300 290 280 270 260 250 2[...]
-
Pagina 10
10 Data is based on the condition under indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. Data is based on the condition under outdoor humidity 75%. A point on the curve shows the reference point. 360 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 (psi.G) Condensing p[...]
-
Pagina 11
11 Data is based on the condition under indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. Data is based on the condition under outdoor humidity 75%. A point on the curve shows the reference point. 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 (psi.G) Condensing p[...]
-
Pagina 12
12 Data is based on the condition under indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point. Data is based on the condition under outdoor humidity 75%. A point on the curve shows the reference point. 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 (psi.G) Condensing p[...]
-
Pagina 13
13 4. ST ANDARD OPERA TION DA T A Models Item Electrical circuit Refrigerant circuit Indoor side Outdoor side V oltage Frequency T otal input Indoor fan current Booster heater current Outdoor fan current Comp. current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp.shell bottom temperature [...]
-
Pagina 14
14 Condition Standard temperature Maximum temperature Minimum temperature Maximum humidity Standard temperature Maximum temperature Minimum temperature 80 95 67 80 70 80 70 67 71 57 75 60 67 60 95 11 5 * 0 80 47 75 17 75 — — 75 43 65 15 Function Cooling Heating Model Airflow ( CFM ) Air speed ( ft/sec ) Coverage range ( ft ) 710 710 990 990 16.[...]
-
Pagina 15
15 6. NOISE CRITERION CURVES 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMA TE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC-60 NC-50 NC-40 NC-30 NC-20 NC-70 OCT A VE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR BAND CENTER FREQUENCIES, Hz Hi NOTCH Lo 49 SPL(dB) 44 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 200[...]
-
Pagina 16
16 5 OUTLINES AND DIMENSIONS 9-1/4 1-25/32 9-1/4 1-25/32 9-1/4 9-1/4 1-25/32 1/2 13-3/8 7-3/4 1-21/32 2-9/32 Top Front Right side Left side 55-1/8 42-15/16 Air intake 9-1/4 C Knock out hole for right piping Refrigerant pipe. Drain pipe Knock out hole for left piping Drain hose for left-hand side piping Drain hose Lower side Auto vane (Gas pipe) Dra[...]
-
Pagina 17
17 66-5/32 9-1/4 53-15/16 Air Intake Front Knock out hole Right side 9-1/4 7-3/4 C for right piping B A A B C 4-1/32 Liquid pipe 1/2F Gas pipe Sleeve > < 1 > < 1 Sleeves are available on the market. Through hole 3-1/2 3-1/2~ 4 3/4F Bolt Drain hose O.D.1-1/16(or 7/8) 19/32 or less 4-3/8 2-5/32(Gas pipe) T erminal block for control T ermi[...]
-
Pagina 18
18 Remote controller Pipe temperature thermistor / Liquid (RT2) Distributor Restrictor valve Capillary tube PKH18FL : ( { 0.126x { 0.071x19.7) PKH24FL : ( { 0.157x { 0.079x19.7) w Refrigerant pipe (option) { 3/8" (with heat insulator) Refrigerant pipe (option) { 5/8" (with heat insulator) Strainer Flared connection Flared connection w An [...]
-
Pagina 19
19 WIRING DIAGRAM 7 MODELS PKH18FL, PKH24FL, PKH30FL, PKH36FL WIRING DIAGRAM GR L1 L2 POWER SUPPLY ~(1PHASE) AC208/230V 60Hz GROUND 3 LED(HOT ADJUST) LED(RUN INDICATOR) LED1 LED2 WIRELESS REMOTE CONTROLLER W.R FS1,2 THERMAL FUSE 88H HEATER CONTACTOR HEATER THERMAL SWITCH HEATER 26H H HEATER 12 3 12 3 12 3 36FL OFF ON 30FL OFF ON MODELS 24FL 12 3 ON[...]
-
Pagina 20
20 8 OPERA TION FLOW-CHART START Power circuit breaker Check SW ON twice Operation SW ON “OFF” timer “ON” timer STOP Set time complete Set time complete 1 NO NO NO NO NO NO NO NO NO NO NO NO YES YES YES YES YES YES YES YES YES YES YES YES w 1 w 2 w 3 w 4 w 5 w 7 w 6 PROTECTION DEVICE SELF HOLD RELEASE Remote controller indicator lamp OFF Tr[...]
-
Pagina 21
21 COOL operation Four-way valve/OFF Initial COOLING NO NO NO NO NO YES YES YES YES YES YES NO YES YES YES YES YES YES YES YES YES YES YES NO NO NO NO YES NO NO NO NO NO NO NO NO NO w 8 w 9 Vane initial setting Vane 55 deg downward angle 70 deg downward angle Fan speed LOW Downward discharge 1 hour Vane setting notch Vane horizontal airflow Compres[...]
-
Pagina 22
22 w 8—9 Refer to page OC276-21. w 12 When room temperature is 64°F or below , the compressor cannot operate. When room temperature rises over 64°F the compressor starts after a 3-minute time delay . w 13 Compressor ON time is decided by room temperature. Refer to page OC276-30. w 14 In dry operation, compressor ON makes the fan speed LOW . Als[...]
-
Pagina 23
23 Heat operation initial HEATING Vane setting notch Vane initial setting defrosting Heating area Defrost release Defrost 30 min. elapse Outdoor unit trouble Four-way valve ON Hot adjust in process Compressor ON Compressor thermostat ON Allowance cancel Indoor piping 5 ° F or lower Outdoor unit trouble FAN SPEED Very low airflow Compressor OFF 1 3[...]
-
Pagina 24
24 9 MICROPROCESSOR CONTROL ● Compressor and outdoor fan : ON- OFF ● Operation mode change :COOL- HEA T . 1.OUTLINE OF MICROPROCESSOR CONTROL ● OFF-ON switching. ● COOL/DRY -AUTO-HEA T selector switching. ● Thermostat setting. ● TIMER mode selector-switching and T imer setting. ● HIGH-LOW fan speed switching. ● AUTO V ane selector ([...]
-
Pagina 25
25 2. INDOOR UNIT CONTROL 2-1 COOL operation <How to operate> 1 Press POWER ON/OFF button. 2 Press the MODE button to display COOL. 3 Press the TEMP( or ) button to set the desired temperature. NOTE : Set temperature changes 2°F when the TEMP( or ) button is pressed one time. Cooling 65 to 87°F . Minimum 3 minutes w 1 ON Thermostat Indoor f[...]
-
Pagina 26
26 (1) Compressor control 1 3-minute time delay T o prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when room temperature is higher than set temperature. The compressor stops when room temperature is equal to or lower than the set temperature. The compressor maintains the previous state when the ro[...]
-
Pagina 27
(3) Auto vane control Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remote controller . (a) V ane position set mode & swing mode. ( i ) Every time AIR DISCHARGE button is pressed, setting will be changed . ( ii ) Airflow direction can be changed with AIR DISCHARGE button. 27 1 F[...]
-
Pagina 28
28 (4) Detecting abnormalities in the outdoor unit After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW . Five minutes later , if the dif- ference is still out of RANGE C,the outdoor unit is [...]
-
Pagina 29
29 <DR Y operation time chart> Minimum 3 minutes w 1 ON Thermostat Indoor fan Auto vane Booster heater Compressor ON DRY MODE DRY MODE ON ON OFF OFF ON OFF OFF OFF OFF Operation starts by POWER button ON. Operation stops by POWER button OFF. Room temperature becomes equal to set temperature. Room temperature rises above set temperature. w 1 E[...]
-
Pagina 30
30 1) Compressor control 1 3-minute time delay T o prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when room temperature is higher than set temperature. The compressor stops when room temperature is equal to or lower than the set temperature. The compressor maintains the previous state when the roo[...]
-
Pagina 31
31 2-3 HEA T operation Minimum 3 minutes w 2 ON Thermostat Indoor fan Auto vane Booster heater Compressor Power ON lamp STAND BY lamp ON ON LOW or HIGH LOW or HIGH ON OFF OFF OFF Horizontal Horizontal OFF ON OFF ON OFF ON OFF LOW w 1 LOW w 1 Hot adjustment From POWER ON until warm begins to blow Hot adjustment Depends on remote controller setting D[...]
-
Pagina 32
32 (1) Compressor control 1 3-minute time delay T o prevent overload, the compressor will not start within 3 minutes after stop. 2 The compressor runs when the room temperature is lower than the set temperature. The compressor stops when the room temperature is equal to or higher than the set temperature. 3 The compressor stops in check mode or dur[...]
-
Pagina 33
33 (5) Detecting abnormalities in the outdoor unit When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code “ P8 ” will appear on the remote controller display . ( i ) During compressor ON while hot adjustment is set. 1 If the difference between the indoor coil temperature and room [...]
-
Pagina 34
34 2-4 AUTO operation (Automatic COOL/HEA T change over operation) (1) Initial mode 1 When AUTO operation starts after unit OFF . ● If the room temperature is higher than the set temperature, operation starts in COOL mode. ● If the room temperature is equal to or lower than the set temperature, operation starts HEA T mode. 2 When AUTO operation[...]
-
Pagina 35
35 <How to operate> T o change the air flow direction, press V ANE ( ) button. (1) COOL/DR Y operation At the start-up of COOL or DRY operation, the discharge direction in automatically set to 10°. After , it can be changed to another direction with V ANE ( ) button on the remote controller . <Auto return> When discharge 60° or 70° c[...]
-
Pagina 36
36 2-6 TIMER operation 2-7 T est run <Timer function> AUTO ST OP ·········The air conditioner stops after the set time lapses. AUTO ST ART ········The air conditioner starts after the set time lapses. AUTO OFF ············Timer is not active. <How to operate> 1 Push POWER ON/OFF button. 2 Check if or not the[...]
-
Pagina 37
37 (1) Indoor coil temperature code During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEA T operation. (2) T rouble during test run ● If the unit malfunctions during th[...]
-
Pagina 38
38 2-9 Dip switch and jumper connector functions. Each figure shows the initial factory setting. 2-9-1 On remote controller board (1). On indoor controller board 1. SW1 (Mode selector) SW1-1) Switch that changes between F AN mode and AUTO mode OFF:AUTO mode for models with heat pump ON:Fan mode for models without heat pump SW1-2) Switch for drain p[...]
-
Pagina 39
39 2-10 INDOOR F AN CONTROL Indoor fan relay output. (a) During fan ON The indoor fan relay turns ON. One second later , the phase control will start. (b) During fan OFF The phase control turns OFF . One second later , the indoor fan relay will turn OFF . 5. SW6 (Address selector) 1234 ON OFF 6. SW7 (Model selector) Switch to set the output of phas[...]
-
Pagina 40
40 2-1 1 Wireless remote controller pair number setting operation ON/OFF TEMP FAN VANE MODE CHECK LOUVER TEST RUN AUTO STOP AUTO START h min RESET SET CLOCK MODEL SELECT 4 A Model No. 3 2 , 5 1 T urn on the main power to the unit. 2 Press the SET button with the point of a ball-point pen or the like. Start this operation from the status of remote c[...]
-
Pagina 41
41 TROUBLESHOOTING 10 1. Self-diagnostic function Self-check 1 T urn on the main power to the unit. 2 Press the button twice continuously . (Start this operation from the status of remote controller display turned off.) A begins to light. B “00” begins to blink. 3 While pointing the remote controller toward the unit’s receiver , press the but[...]
-
Pagina 42
42 Check code Diagnosis of malfunction Cause Check points 4 Abnormality of drain sensor 1) Bad contact of transmission wire 2) Damaged thermistor 1) Check the connector . 2) Measure the resistance of the thermistor (between ➃ - ➄ of CN50). As for the normal resistance, refer to the case of 1. If the resistance is normal, replace the indoor con-[...]
-
Pagina 43
43 3. WRONG WIRING ON SITE 3-1 Between remote controller and indoor unit If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller when the POWER button is pressed. The beep sound will also not be heard. 3-2 Phenomenon due to wrong wiring between indoor and outdoor units Wrong wirin[...]
-
Pagina 44
44 4. HOW TO CHECK THE P ARTS Room temperature thermistor (RT1) Pipe temperature thermistor (RT2) Fan motor (MF) Disconnect the connector , then measure the resistance using a tester . (Surrounding temperature 50°F to 86°F) Measure the resistance between the terminals using a tester . (Refer to the thermistor) Normal 4.3k ' to 9.6k ' Ab[...]
-
Pagina 45
45 DISASSEMBL Y PROCEDURE 11 OPERA TING PROCEDURE PHOTOS&ILLUSTRA TION Metal fixture Screws 1. Removing the lower side of the indoor unit from the instal- lation plate (1) Remove the 2 screws. Hang the indoor unit hangers to the catches on the instal- lation plate. Hanger of indoor unit Catch of installation plate 2. Removing the right side pan[...]
-
Pagina 46
46 OPERA TING PROCEDURE PHOTOS&ILLUSTRA TION (8) Remove the screws of the indoor controller board case, and pull out the indoor controller board case. Then the transformer and the capacitor and relay can be serviced. 5. Removing the vane motor (1) Remove the right side panel. (2) Remove the screw of the electrical box cover , and remove the cov[...]
-
Pagina 47
47 OPERA TING PROCEDURE PHOTOS 8. Removing the line flow fan and the fan motor (1) Remove the left and right side panels. (2) Remove the grilles. (3) Remove the electrical box. (4) Remove the drain pan. (5) Loosen the screw that fixes the line flow fan to the fan motor . (See Photo 7. ) (6) Remove the 4 screws of the motor fixture, and remove the f[...]
-
Pagina 48
48 12 P ARTS LIST No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH FL FL FL 1 2 3 4 5 SLEEVE BEARING BEARING MOUNT LEFT LINE FLOW FAN LEFT LINE FLOW FAN RIGHT LINE FLOW FAN RIGHT LINE FLOW FAN HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER HEAT EXCHANGER 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 FL 1 1 1 1 1[...]
-
Pagina 49
49 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 DRAIN PAN DRAIN PAN CENTER COVER JOINT SHAFT AUTO VANE AUTO VANE DRAIN HOSE VANE MOTOR ROOM TEMPERATURE THERMISTOR PIPE TEMPERATURE THERMISTOR TERMINAL BLOCK TERMI[...]
-
Pagina 50
50 No. Parts No. Parts Name Specifications Remarks (Drawing No.) Wiring Diagram Symbol Q'ty / set PKH FL Part number that is circled is not shown in the figure. 1 2 3 4 5 6 7 8 9 10 11 12 LEFT SIDE PANEL UNDER PLATE UNDER PLATE NOSE NOSE FILTER W.A. CONT (A) RECEIVER RIGHT SIDE PANEL INTAKE GRILLE BACK PLATE BACK PLATE TOP PLATE TOP PLATE INTA[...]
-