Go to page of
Similar user manuals
-
Uninterruptible power supply (
APC ISXT110MD1RI
20 pages -
Uninterruptible power supply (
APC SUA1500I - KIT
18 pages -
Uninterruptible power supply (
APC MGE Galaxy 3500 15kVA 400V with 2 Battery Modules
40 pages -
Uninterruptible power supply (
APC BE450G-LM
6 pages -
Uninterruptible power supply (
APC Back-UPS ES 350
2 pages -
Uninterruptible power supply (
APC SMT2200I-BNDL
18 pages -
Uninterruptible power supply (
APC SUA3000JB
17 pages -
Uninterruptible power supply (
APC SURTA2200XL
18 pages
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of APC MGE Galaxy 5000, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of APC MGE Galaxy 5000 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of APC MGE Galaxy 5000. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of APC MGE Galaxy 5000 should contain:
- informations concerning technical data of APC MGE Galaxy 5000
- name of the manufacturer and a year of construction of the APC MGE Galaxy 5000 item
- rules of operation, control and maintenance of the APC MGE Galaxy 5000 item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of APC MGE Galaxy 5000 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of APC MGE Galaxy 5000, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the APC service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of APC MGE Galaxy 5000.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the APC MGE Galaxy 5000 item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
MGE Galaxy 5000 40-130 kV A 480 V Operation[...]
-
Page 2
[...]
-
Page 3
T able of Contents About This Manual ......................................................................................................... 1 Symbols Used ................................................................................................................... 1 Companion Manuals ........................................................[...]
-
Page 4
ii MGE Galaxy 5000 40-130 kV A 480 V 990-5219-001[...]
-
Page 5
About This Manual This manual describes the startup, shutdown, and normal operation of the MGE Galaxy 5000 with information on the user interface display and display menu structure. For maintenance the manual describes alarm conditions, UPS isolation operation and maintenance and safety information on servicing batteries for the MGE Galaxy 5000. Sy[...]
-
Page 6
Overview User Interface The UPS is operated using the control and display interface. A. Graphical Display B. Load protected LED C. Minor fault LED D. Major fault LED E. Help key F . Function keys. Each key corresponds to a function presented on the display . The function of each key changes depending on the menu displayed on the screen. G. Menu key[...]
-
Page 7
A Press the Menu key to access the Main Menu. B Press the Help key for information on the pictogram functions. The key must be held down. Measurements The Measur ements display screens consist of the following measurements screens: 1. Press the Menu key to return to the Main Menu. 2. Use the function keys ↑ or ↓ to highlight Measurements on the[...]
-
Page 8
Status The Status display screens consist of the following Status screens: 1. Press the Menu key to return to the Main Menu. 2. Use the function keys ↑ or ↓ to highlight Status on the display . 3. Press the function key ← to select Status . 4. Use the function keys ↑ or ↓ to select between the following two Status screens: • T ime stamp[...]
-
Page 9
• T ests LEDs • Buzzer OFF • Enable LCM indications • Disable LCM indications 5. Press the function key ← to select the required Controls screen. 990-5219-001 MGE Galaxy 5000 40-130 kV A 480 V 5[...]
-
Page 10
UPS Conguration Access to the Personalization Functions Caution: Personalization must be carried out with switches Q1 (8) and Q5N (1 1) open (OFF) and switch Q4S (9) closed (ON). 1. Press the menu key (A). 2. Select Settings , then Personalization using the function keys (B) ↑ or ↓. 3. Conrm by pressing the function key (B) ←). 4. Enter[...]
-
Page 11
Automatic Bypass Function Factory setting Options T ransfer to bypass AC source Enabled Disabled – disabled when limiting T ransfer to bypass with bypass AC source out of tolerances Enabled Disabled Battery Function Factory setting Options Low battery warning threshold if battery monitor inactive 40% remaining backup time 20 – 60 – 80 % remai[...]
-
Page 12
Operation Caution: All operations concerning system start-up and compliance with standards and regulations, including those related to the battery cabinet, must be carried out by trained and certied personnel before using the UPS. Operating Modes Normal (Double Conversion) Mode This is the standard operating mode, set by default in the factory .[...]
-
Page 13
3. Both normal and Bypass AC sources not available or out of tolerance: LED (B) is ON. The buzzer sounds intermittently . The load is supplied by the UPS from battery power . Note: The display indicates the UPS operating status conditions and the required actions. Load on Battery Power The load continues to be protected by the UPS when the normal A[...]
-
Page 14
Operation of Mimic-Panel LEDs The MGE Galaxy 5000 system is simple to operate and yet provides a wealth of continuous monitoring and diagnostic features to ensure proper operation. Operators gain access to information in the MGE Galaxy 5000 system through the display and its integrated LED mimic panel. The mimic diagram displays information directl[...]
-
Page 15
Operation Procedures Shut Down a Single UPS The UPS remains ener gized unless it is shut down. 1. Press a button to exit sleep mode. 2. Press the OFF button (A) for 3 seconds. The load is no longer protected by the UPS. It is supplied via the bypass. 3. Set the battery circuit breaker of the auxiliary cabinets to OFF . 4. Set the input switch Q1 (B[...]
-
Page 16
Restart a Single UPS Check that switches Q4S (B) and Q5N (C) are closed. If this is the case, continue with this procedure, otherwise refer to “Return to the Normal Operation, Single UPS“ . 1. Set the Normal AC source input switch Q1 (A) to the ON position. 2. W ait until the end of the start sequence. 3. Set the battery circuit breaker of the [...]
-
Page 17
Shut Down a Parallel Conguration 1. Press a button on each unit to exit sleep mode. 2. Press the OFF button (A) on each unit for 3 seconds. The load is no longer pr otected by the UPSs. It is supplied via the bypass. 3. Set the battery circuit breakers of the auxiliary cabinets to the OFF position. 4. Set the input switch Q1 (B) in each UPS to t[...]
-
Page 18
Restart a Parallel Conguration Check that switches Q4S (B) and Q5N (C) are closed. If this is the case, continue with this procedure, otherwise refer to “Return to Normal Operation, Parallel UPS“ . 1. Check that the output switch CB2 in the external system bypass cabinet is closed. 2. Check that the bypass switch CB1 in the external system b[...]
-
Page 19
Isolate UPS Isolate Single UPS T o isolate the UPS from the electrical power source and supply the load directly by the normal or bypass AC source, follow the instructions below: 1. Press a button to exit sleep mode. 2. Shut down the UPS by pressing the OFF button (A) for 3 seconds. The load is no longer pr otected by the UPS. 3. Set bypass switch [...]
-
Page 20
Isolate Parallel UPS Without External Bypass Cabinet Shut down and isolate the rst UPS: 1. Check that the two UPSs are operating. 2. Press a button to exit sleep mode. 3. Shut down the UPS by pressing the OFF button (A) for 3 seconds. 4. Set output switch Q5N (E) to OFF . 5. Set the battery circuit breakers of the auxiliary cabinets to OFF . 6. [...]
-
Page 21
Isolate Parallel UPS W ith External Bypass Cabinet Shut down and isolate one UPS: 1. Check that the total capacity of the remaining UPSs is suf cient to supply the connected load. 2. Press a button to exit sleep mode. 3. Shut down the UPS by pressing the OFF button (A) for 3 seconds. 4. Set output switch Q5N (E) to OFF . 5. Set the battery circu[...]
-
Page 22
Return to Normal Operation Return to Normal Operation, Single UPS 1. Check that bypass switch Q3BP (C) is ON and that all other switches are OFF . 2. Set switch Q4S (B) to ON. 3. Set output switch Q5N (D) to ON. 4. W ait until the display goes on and check that there are no faults on the static switch on the bypass line. 5. Set bypass switch Q3BP ([...]
-
Page 23
Return to Normal Operation, Parallel UPS Without External Bypass Cabinet Restart the UPS Unit for which Switch Q3BP (10) is ON and the Other Switches are OFF Caution: It is imperative to restart this UPS. Otherwise, load power is lost if the other UPS is shut down. 1. Set the input switch Q4S (B) to ON. 2. Set output switch Q5N (D) to ON. 3. Check [...]
-
Page 24
Restart the UPS for which All Switches are Set to OFF 1. Set the input switch Q4S (B) to ON. 2. Set output switch Q5N (D) to ON. 3. Check that all the UPS units present in the installation are included in the list on the display and conrm by pressing the function keys. 4. Set the input switch Q1 (A) to ON. 5. Set the battery circuit breaker of t[...]
-
Page 25
Return to Normal Operation, Parallel UPS W ith External Bypass Cabinet 1. Check that all switches on the UPSs are set to OFF . 2. Apply bypass and input power to UPSs. 3. Set switch Q4S (B) on each UPS to ON. 4. Set output switch Q5N (D) on each UPS and CB1 1–16, as applicable, to ON. 5. Check that all the UPSs present in the installation are inc[...]
-
Page 26
Operation of the Relay Communication Card (Dry Contacts) All systems are equipped with this remote transmissions card (also known as SECI). A complete specication exists for the card used in MGE Galaxy 5000. This card is used for the transmission of information between the system and the environment. T wo inputs and six outputs are available for[...]
-
Page 27
Programmable Mode This operating mode is specic to the MGE Galaxy 5000. Microswitch 3 on SA1 must be set to ON (if two SECI cards are installed in the unit, the second card must be identied differently . On the second card, microswitch 1 on SA1 must be set to ON). In this mode, it is possible to assign predened operating status conditions [...]
-
Page 28
Operating status conditions Description PFC F AUL T Neutral leg fault OR Neutral leg IGBT temperature outside tolerances OR - V oltage difference between 2 DC half-buses outside tolerances OR - T op DC half-bus voltage outside tolerances OR - Bottom DC half-bus voltage outside tolerances PFC fault OR - DC-bus voltage at end of CSR1 walk-in is lower[...]
-
Page 29
Operating status conditions Description BA TTER Y CIRCUIT BREAKER(S) OPEN One or two Battery circuit breakers is open. PHASE ROT A TION F AUL T Phase inversion on normal AC input OR Phase inversion on AC bypass. FUSES BLOWN Fuse blown at normal AC input OR Charger fuse has blown OR Power supply board fuse has blown OR Inverter phase-1 fuse has blow[...]
-
Page 30
Maintenance Life Cycle Monitoring (LCM) The “Life Cycle Monitoring” (LCM) function provides UPS maintenance advice to guarantee installation availability for the user . The display gives three messages enabling the following to be identied: Status Display Message The end of the contractual legal warranty End of warranty check recommended Reg[...]
-
Page 31
Servicing Batteries IMPORT ANT SAFETY INSTRUCTIONS FOR SER VICING BA TTERIES Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. When replacing batteries, use the same model and manufacturer of batteries. Caution: Do not d[...]
-
Page 32
T roubleshooting Identication of Alarms Alarm conditions are identied by LEDs (A), (B), (C) and the buzzer . LED (A) LED (B) LED (C) Buzzer Signicance - - Intermittent Normal AC source not available - - Intermittent UPS shut down following end of battery power - - Intermittent UPS shut down on fault requiring servicing by after -sales supp[...]
-
Page 33
Alarm or Status Display Messages List Display Message Level Abnormal bypass operation Internal and external switches Abnormal external bypass operation Internal and external switches Abnormal presence of output voltage Fault or state of load AC Bypass static switch thermal overload Fault or state on Bypass AC or Bypass Static Switch Battery circuit[...]
-
Page 34
Display Message Level External Q4S switch open (MBC CB3) Internal and external switches External Q5N switch open (MBC or SBC CB2) Internal and external switches Fan fault Major Fault on subassembly Installation overload Fault or state of installation Internal CAN communication fault Fault of downgraded mode Inverter and bypass desynchronized Fault [...]
-
Page 35
Display Message Level Not enough bypass static switches Fault or state of installation Not enough inverters for load connection Fault or state of installation Personalization does not match UPS Generic fault on equipment PFC fault Major Fault on subassembly PFC overload Fault or state for PFC PFC thermal overload Fault or state for PFC Power supply[...]
-
Page 36
Worldwide Customer Support Customer support for this or any other product is available at no charge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specic centers: go to www .apc.com/support/contact for contact information. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Indu[...]