Go to page of
Similar user manuals
-
Air Conditioner
Bard W42L2
11 pages 0.45 mb -
Air Conditioner
Bard W12A1-K
12 pages 0.12 mb -
Air Conditioner
Bard W18L1
25 pages 0.52 mb -
Air Conditioner
Bard WG4S1
12 pages 0.42 mb -
Air Conditioner
Bard W18L1
25 pages 0.34 mb -
Air Conditioner
Bard Q42A1
38 pages 0.93 mb -
Air Conditioner
Bard WG3S
15 pages 0.43 mb -
Air Conditioner
Bard PA13422-C
24 pages 0.71 mb
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of Bard WL602N, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Bard WL602N one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of Bard WL602N. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of Bard WL602N should contain:
- informations concerning technical data of Bard WL602N
- name of the manufacturer and a year of construction of the Bard WL602N item
- rules of operation, control and maintenance of the Bard WL602N item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Bard WL602N alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Bard WL602N, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Bard service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Bard WL602N.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the Bard WL602N item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS WL4822 WL4823 WL6022 WL6023 WL602N Manual : 2100-351D Supersedes: 2100-351C File: V olume III T ab 16 Date: 09-20-01 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2001[...]
-
Page 2
Contents Figures Figure 1 Unit Dimensions ..................................... 3 W A602N, WA6023, W A4823 Figure 2 Unit Dimensions ..................................... 4 W A6022, WA4822 Figure 3 Mounting Instructions ............................. 8 W A602N, WA6023, W A4823 Figure 4 Mounting Instructions ............................. 9 W A6022, WA[...]
-
Page 3
Manual 2100-351 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ........................ ANSI/NFPA 70[...]
-
Page 4
Manual 2100-351 Page 2 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE WL 60 2 3 A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building. TABLE 1 ELECTRIC HEAT TABLE WL4822A, WL4822B, WL4823A, WL4823B, WL6022A, WL6022B are not approved [...]
-
Page 5
Manual 2100-351 Page 3 FIGURE 1 UNIT DIMENSIONS WL602N, WL6023, WL4823 ONLY MIS-1451[...]
-
Page 6
Manual 2100-351 Page 4 FIGURE 2 UNIT DIMENSIONS WL6022, WL4822 ONLY MIS-1452[...]
-
Page 7
Manual 2100-351 Page 5 TABLE 2 ELECTRICAL SPECIFICATIONS j k l Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All Wiring must conform to NEC and all local codes. These “ minimum Circuit Ampacity ” values are to be used for sizing the field power conductor[...]
-
Page 8
Manual 2100-351 Page 6 A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 3A for further details. Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity. Some[...]
-
Page 9
Manual 2100-351 Page 7 INST ALLA TION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 1 or 2. Figure 1 is for models WL4823, and WL6023. Figure 2 is for Models WL822 and WL6022. 2. On wood frame walls, the wall construction must be strong and rigid enough to [...]
-
Page 10
Manual 2100-351 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WL602N, WL6023, WL4823 ONLY MIS-1349[...]
-
Page 11
Manual 2100-351 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WL6022, WL4822 ONLY MIS-1444[...]
-
Page 12
Manual 2100-351 Page 10 FIGURE 5 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is [...]
-
Page 13
Manual 2100-351 Page 11 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 MIS-948 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. RETURN AIR OPENING SUPPLY AIR OPENING WALL STRUCTURE[...]
-
Page 14
Manual 2100-351 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS MIS-550[...]
-
Page 15
Manual 2100-351 Page 13 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of el[...]
-
Page 16
Manual 2100-351 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS-1373A[...]
-
Page 17
Manual 2100-351 Page 15 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. CRANKCASE HEATERS These units are not provided with crankcase heat. These units utilize scroll compressors which do not require crankcase heat in this application. HIGH PRESSURE SWITCH The models are suppl[...]
-
Page 18
Manual 2100-351 Page 16 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number. Low Pressure Switch, Bypass, an[...]
-
Page 19
Manual 2100-351 Page 17 The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle. REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles.[...]
-
Page 20
Manual 2100-351 Page 18 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Values shown are for units equipped with standard 1 ” throwaway filters or 1 ” washable filters. Derate ESP by .15 for 2 ” pleated filters. S L E D O MP S E - 3 2 0 6 L W Y L N O 5 0 A 0 1 A 9 0 B 4 . 3 . 3 . Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Ta[...]
-
Page 21
Manual 2100-351 Page 19 TABLE 11 OPTIONAL ACCESSORIES WL6023A. WL6022A WL6023B, WL6022B WL4823A, WL4822A WL4823B, WL4822B t r a P r e b m u Nn o i t p i r c s e D 5 1 - C M Ct i K t r a t SX X A 9 0 - B C M W B 7 0 - B C M W A 8 0 - B C M W B 5 0 - B C M W t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u c r i C t i K r e k a e r B t i u[...]