Go to page of
Similar user manuals
-
Uninterruptible power supply (
BlueWalker PowerWalker VI 650 SE
98 pages -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 1500RT LCD
44 pages -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 10000P/RT LCD
65 pages -
Uninterruptible power supply (
BlueWalker PowerWalker VFI 2000RT LCD
44 pages -
Uninterruptible power supply (
BlueWalker 10120176
64 pages -
Uninterruptible power supply (
BlueWalker VI 750 PSW
64 pages -
Uninterruptible power supply (
BlueWalker VFI 2000R LCD
98 pages -
Uninterruptible power supply (
BlueWalker VFI 1500R LCD
97 pages
A good user manual
The rules should oblige the seller to give the purchaser an operating instrucion of BlueWalker PowerWalker VFI 40000TP 3/3 BE, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.
What is an instruction?
The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of BlueWalker PowerWalker VFI 40000TP 3/3 BE one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.
Unfortunately, only a few customers devote their time to read an instruction of BlueWalker PowerWalker VFI 40000TP 3/3 BE. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.
What should a perfect user manual contain?
First and foremost, an user manual of BlueWalker PowerWalker VFI 40000TP 3/3 BE should contain:
- informations concerning technical data of BlueWalker PowerWalker VFI 40000TP 3/3 BE
- name of the manufacturer and a year of construction of the BlueWalker PowerWalker VFI 40000TP 3/3 BE item
- rules of operation, control and maintenance of the BlueWalker PowerWalker VFI 40000TP 3/3 BE item
- safety signs and mark certificates which confirm compatibility with appropriate standards
Why don't we read the manuals?
Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of BlueWalker PowerWalker VFI 40000TP 3/3 BE alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of BlueWalker PowerWalker VFI 40000TP 3/3 BE, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the BlueWalker service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of BlueWalker PowerWalker VFI 40000TP 3/3 BE.
Why one should read the manuals?
It is mostly in the manuals where we will find the details concerning construction and possibility of the BlueWalker PowerWalker VFI 40000TP 3/3 BE item, and its use of respective accessory, as well as information concerning all the functions and facilities.
After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.
Table of contents for the manual
-
Page 1
PowerW alker VFI 3/3 Series VFI 30000TP/40000TP 3/3 BE/BI 380/400/415V 50/60Hz (3-phase input/output) User Guide[...]
-
Page 2
[...]
-
Page 3
EN ©2013 BlueW alker GmbH All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care has been taken to ensure the accuracy of the information contained in this manual, but no liability can be accepted for any errors or omission. The right to mak[...]
-
Page 4
4.1 De li v e ry ch e ck …………………………………………………… ………………… 4 .2 U n p ac k in g an d visual i ns p ec ti on … … ……… … …… … …… … ……… … …… 4. 3 P lann i n g be fo re install ati on ………………… …… ……… …… ……… ………… 4 .4 C a b inet i[...]
-
Page 5
EN R ec ycli n g th e us ed U PS o r ba tte ry …… ………… …… …… …… ………… …… Maint en an ce ………………… ………… ………… …………………… ………… …… P arall el syste ms … …… …… . … … …… …… …… ……… …… …… …… …… … …… 8. 9. 10. Elec t[...]
-
Page 6
1 1 Safety instructions W arning! Operations inside the UPS must be performed by a service engineer from the manufac- turer or from an agent authorised by the manufacturer . 1.1 Safety caution Use the optional Maintenance Bypass Switch (MBS) for service inside the UPS when in - stalled to the system. Remember to open battery cabinet(s) breaker . Al[...]
-
Page 7
2 EN 1.3 CE marking The product has the CE marking in compliance with the following European directives: L VD Directive (Safety) 2006/95/EEC EMC Directive 2004/108/EEC The only user operations permitted are: Start up and shut down the UPS, excluding the commissioning start-up.Use of the LCD con - trol panel and Emergency Power Off (EPO) switch.Use [...]
-
Page 8
3 1.5 Environment The UPS must be installed according to the recommendations in this manual.Under no cir - cumstances the UPS should be installed in an airtight room, in the presence of ammable gases, or in an environment exceeding the specication.Excessive amount of dust in the operating environment of UPS may cause damage or lead to malfunc[...]
-
Page 9
4 EN 2 Introduction 2.1 System description PowerW alker VFI 3/3 Series products are high-efficiency and high-performance, double conversion, pure-online and three phase input and three phase output UPS, with unit capacity ranging between 20KV A-40KV A. Categorized by capacity , the products can be further divided into 20KV A, 30KV A and 40KV A. Thi[...]
-
Page 10
5 2.2 Basic system conguration 2.3 Panel gure[...]
-
Page 11
6 EN 2.4 Exterior view ① AC: This light and inverter light will turn "green" when UPS is powered by Rectier Input; ② Inverter: This light will turn "green" when UPS load is through the inverter; ③ Battery: This light will turn "yellow" when UPS is powered by batteries; ④ Bypass: This light will turn "gr[...]
-
Page 12
7 CHGR F AN Front view(door open) Battery trays[...]
-
Page 13
8 EN W × D × H (mm) 3 T echnical data 3.1 Standards Product IEC62040-3:1999 and EN62040-3:2001 UPS VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Safety IEC62040-1:2008,EN62040-1:2003 and EN60950-1:2005 EMC IEC62040-2:2006 and EN62040-2:2005 3.2 Environment 0 ℃ ~ +40 ℃ (with batteries) Working T emperature 0 ℃ ~ +40 ℃ Storage T emperatur[...]
-
Page 14
9 3.5 AC input 3.4 Characteristics VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Noise (ISO 7779) <57dB at 75% load Efciency-nominal load Up to 92% V oltage (L-N) 121V -274 V olts without using battery Rectier input 3 phases + N Bypass input 3 phases + N Frequency 40-70 Hz Rated input voltage 380V/400 V/415V Power factor 0.99 Input distortio[...]
-
Page 15
10 EN 3.7 AC output 3.8 Battery and Charger Internal battery package Panasonic LC-RW 1245W / CSB HR 1234WF2 Dimensions 94*151*64.5/pc(Panasonic) 94*151*65/pc(CSB) Strings 2 x 16 Charger Input Protection 8 A fuse Rated Charge V oltage ± 216V Default for Integrated bettery Initial Charging Current 4.5A Battery Leakage < 3.5mA Battery protection 1[...]
-
Page 16
11 4 Mechanical installation 4.1 Delivery check The UPS and accessories are delivered on a specically designed pallet that is easy to move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not stack the pallets. The UPS is delivered with the following items: 1. Winpower disc 2.RS-232 seri[...]
-
Page 17
12 EN Check the information on the type designation label of the equipment to verify that the unit is of the correct type. The type designation label includes ratings, a CE marking, a type code, a part number and a serial number . The serial number is important when making inquiries. It allows individual recognition of the equipment.[...]
-
Page 18
13 Preparation for installation. 1. A void extremes of ambient temperature; excessive dust, moisture or vibration; ammable gases; and corrosive or explosive atmospheres. 2.Altitude for normal UPS function should not exceed 1000m. 3.The battery cabinet should work within a temperature range from15 ℃ to 25 ℃ . 4.The maximum ambient temperature[...]
-
Page 19
14 EN Caution! UPS cabinet(s) can fall over if the installation brake pads are not used. Both rear and front pads must be used to secure the UPS cabinet to the oor . Use a 19mm wrench in clockwise direction to screw the brake pad down to the ground, keeping the machine from moving. 4.5 Maintenance Bypass Switch(MBS) The operation of the MBS is a[...]
-
Page 20
15 The normal positions of the MBS switches. The switching sequence for circuit breaker from normal position to maintenance position:[...]
-
Page 21
16 EN The maintenance positions of the MBS switches 2.Use LCD to turn the UPS from normal mode to bypass mode: Switch-off action (press ESC to exit above picture) T ransfer UPS from normal mode to maintenance bypass mode: 1.The normal start position should be following:[...]
-
Page 22
17 1)Switch-off picture 2)If it is in single machine mode, the following will appear Remember to verify the transfer before proceeding the next step. 3.Remove the locking plate of maintenance switch. 4.T urn OFF the Rectier Input switch and battery breaker. 5.T urn the Maintenance switch to “ MAINTENANCE ” side. 6.T urn OFF the Bypass Input [...]
-
Page 23
18 EN 7.UPS is now in the maintenance bypass mode, see below (Note: the Serv disconnect i.e. battery breaker must be turned off): T ransfer UPS from maintenance bypass mode to normal mode: 1.The normal start position should be following: When the LED of bypass turns green,the UPS enters into bypass mode. 3.T urn the Maintenance switch to “ UPS ?[...]
-
Page 24
19 Then the UPS turn to bypass mode. 4.T urn ON the Rectier Input switch and battery breaker. 5.Use LCD to turn the UPS from bypass mode to normal mode: Switch-off action (press ESC to exit above picture) 1)Switch-on picture 2)Press ENTER[...]
-
Page 25
20 EN 6.UPS is now in the normal mode,see below: 7.Remount the locking plate of maintenance switch to the position to prevent the use of it.[...]
-
Page 26
21 5 Electrical installation 5.1 Electrical Preparations The UPS unit has the following power connections: Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the rectier input. Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the bypass input ( N is INTERNALL Y common for rectier and b[...]
-
Page 27
22 EN 1.If UPS rectier input and bypass input are supplied from two mains: Connect the mains 1 supply cables to the UPS rectier input terminals L1, L2, L3, N and PE. Connect the mains 2 supply cables to the UPS bypass input terminals L1, L2, L3, N and PE. 8 blue wires (B14, B15, B16, and B18) for BA TN connection; 56 black wires (B1) with an [...]
-
Page 28
23 T erminal block diagram W arning! High touch current earth connection essential before connecting supply . 2.If UPS rectier input and bypass input are supplied from one mains only: Connect the mains supply cables to the UPS rectier input terminals L1, L2, L3, N and PE . The following three jumpers must be xed between the rectier and [...]
-
Page 29
24 EN The conductor cross sections apply for maximum currents: (1) For PVC-insulated copper cables (at 70 ℃ ) (2) When routed in conduits for electrical installations (3) When air temperature surrounding the conduits does not exceed 30 ℃ (4) For cable lengths up to 30 m Connect the Protective Earthing (PE) cable rst. Connect other cables as [...]
-
Page 30
25 Routing of communication cables or data lines should be kept separate from the UPS input, output, and external battery cables. Use cable cross section and protective device specication Model VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI Rectier Input L1, L2, L3, N, Bypass Input L1, L2, L3, N, min. conductor cross section[mm ] 10 16 max. poss[...]
-
Page 31
26 EN Notice! The following label must be displayed on all switching devices installed in the same electrical system as the UPS, even when these are located at a distance from the area in which it is located (according to European standard EN 62040-1). W arning! ENSURE THA T THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLA TED BE - FORE WORKING ON THIS CI[...]
-
Page 32
27 Step1: Put batteries into the trays (see Fig. 2). Fig. 2 3. Assemble the battery packs.There are eight batteries in each battery pack, four packs in each shelf and total is four shelves. Step2: connect the wires between the batteries (see Fig. 3). Fig. 3 Front Back[...]
-
Page 33
28 EN Step3: Install the top tray downward, and fold both the top and bottom tray anges (see Fig 5). Fig. 5 Please refer to the following gure(Fig.4) for wire connections of the four battery packs. Fig. 4[...]
-
Page 34
29 Step4: T ape two sides (see Fig.6 ).Make sure the cable is placed between the tray edges during tape mounting. Fig. 6 Front Back Battery Pack Assembly Step5: Paste the labels to the battery packs (see Fig. 7). Fig. 7[...]
-
Page 35
30 EN 4. Put the battery packs into the enclosure from left to right and bottom to top and cover each shelf with a x-plate(see Fig. 9) (please refer to Fig.4 for correspending battery packs). Fig. 9 Make sure to paste the correct label to each battery pack and the battery packs are placed conformably with the labels, i.e. the battery terminals a[...]
-
Page 36
31 5. Connect the cables to each shelf respectively (see Fig. 10). REMARK: MAKE SURE TO CONNECT WIRES WITH THE SAME COLOR. Fig. 10[...]
-
Page 37
32 EN Fig.1 1 6. Secure each x-plate with four screws (see Fig. 1 1). 7. T ie up the wires properly(see Fig. 12). Fig.12[...]
-
Page 38
33 8. Reinstall the battery cover and secure it with the eighteen screws. 8 8[...]
-
Page 39
34 EN Notice! The most common battery type used in UPS installations is the valve regulated bat - tery . V alve regulated cells are not sealed. The amount of gas given off is less than for ooded cells, but when planning the battery installation, allowance must be made for adequate ventilation and heat dissipation. V alve regulat ed cells are not[...]
-
Page 40
35 5.6 Connections between battery cabinet and UPS Make sure the Protective Earthing (PE) connected rst. External Battery Cabinet Connections Notice! The requirements of the EC directives are satised when battery cabinet are used with original accessories. If alternative batteries are used, you must ensure that the appli - cable EC directives[...]
-
Page 41
36 EN Exchanging batteries W arning! If a battery cabinet has been disconnected and is to be reconnected, the battery isola - tor may only be reconnected after you have made certain that voltage with the correct polarity is present on both sides of isolating device. Connecting external battery cabinet W arning! Before replacing batteries, make sure[...]
-
Page 42
37 6 Software and connectivity The Series provide Intelligent Slot, Expanded Slot, P ARALLEL, AS400, EPO, RS485 and RS232 as well as SERVICE Supervising Communication Interface exclusively available to PowerW alker technical personnel. 2 6 8 1 5 P ARALLEL Intelligent slot Expanded slot AS400 EPO SERVICE RS485 RS232 3 4 7 P ARALLEL 1. Intelligent sl[...]
-
Page 43
38 EN RS232 port RS485 port[...]
-
Page 44
39 AS400 port Note! The UPS have to be manually reset if remote shutdown occurs.[...]
-
Page 45
40 EN 7 User operations 7.1 Single machine operation W arning! High touch current earth connection essential before connecting supply . The only user operations permitted are: Start up and shut down the UPS, excluding the commissioning start-up. Use of the LCD control panel and Emergency Power Off (EPO) switch. Use of optional connectivity modules [...]
-
Page 46
41 3)Press ESC to access or automatically within 1min with no button being pressed 4)Press ▼ to obtain the below informa - tion Remark: the following drawing takes PowerW alker VFI 30000TP 3/3 BE/BI as an example and statistics are only for reference. 1)Power on 2)Automatic access within about 4s 36 POWERWALKER VFI 3 0000TP 3/3[...]
-
Page 47
42 EN 5)Press ▼ again to obtain the below 6)Press ▼ again to obtain the below information information 7)Press ▼ again to obtain the below 8)Press ▼ again to obtain the below information information VFI 3 0000TP 3/3[...]
-
Page 48
43 1)Switch-on picture 2)Press ENTER 4. Start-up action (press ESC to exit the above picture) Note! If malfunction occurs, “x” will appear at the lower right corner of the display ,while a warning occurs, “ ” will appear at the same position (as illustrated in the below pic - ture with battery mode as an example).[...]
-
Page 49
44 EN 3)Select “Y es, Conrm” to switch on 4)Normal Switch-on the machine 5)Battery power supply (switch off line input switch)[...]
-
Page 50
45 3)If it is in parallel machine mode, the 4)Press ENTER following will appear 5. Switch-off action (press ESC to exit above picture) 1)Switch-off picture 2)If it is in single machine mode, the following will appear[...]
-
Page 51
46 EN 5)Select “Y es, Conrm” to switch of f 6)Normal Switch-off the machine Note! If you intend to switch off only one set of UPS among the parallel machine system, se - lect “single machine switch-off”; if switch-off is intended for the entire parallel machine system, select “parallel machine switch-off”. 6. Help 1)Help picture 2)Pr[...]
-
Page 52
47 3)Enter respective password 4)Select action item 8. The Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply . DC switch-on and off are available by following instruc - tions appearing in the pictures. 1)Action display (bypass power supply) 2) Press ▼ 7. Conguration (press ESC to[...]
-
Page 53
48 EN 9. Procedures of DC switch-on: Activate DC switch-on function set under UPS bypass mode Make sure that “+”, “-” and “N” wires of batteries are properly connected to UPS Switch on batteries Lightly touch ENTER Manually conduct switch-on order within about 1min after LCD self-inspection 7.2 Parallel machine operation Redundancy intr[...]
-
Page 54
49 Parallel machine wire connection drawing(one battery supply) Parallel machine wire connection drawing(separate battery supply)[...]
-
Page 55
50 EN Single machine wire connection drawing[...]
-
Page 56
51 PowerW alker VFI 30000TP , 40000TP 3/3 BE/BI requires minimum maintenance. 1. If battery is switched off, loaded equipments will not be covered for power-of f protection. 2. Make sure UPS vent are properly ventilated and clean side frames and fan vents from dusts every half a year (switch off AC, battery cabinet and internal battery fuse prior t[...]
-
Page 57
52 EN Remark: A. Prior to battery replacement, switch off UPS and remove it from AC and battery , take of f internal battery breaker . B. T ake off metallic articles such as rings and watches. C. Use screw drivers equipped with insulated handles and do not place tools or other metal - lic substances on the batteries. D. Short circuit or reverse con[...]
-
Page 58
53 8.2 Regular service/intervals The UPS requires very little maintenance if installed in an appropriate environment. In order to ensure maximum availability of the UPS, manufacturer recommends signing a proactive service agreement with a local authorised service provider . Batteries test 18 months Maintenance Interval Batteries change 3-5 years or[...]
-
Page 59
54 EN 9 Parallel systems Parallel is only connected to identical ports for the UPS of same models and kV A rating. 1) Follow installation instructions for general installation requirements. 2)V entilation spacing between machines should allow for service access. 3) Input wiring for each set of UPS should follow the requirements for that of single u[...]
-
Page 60
55 Note! Parallel signal cable should be connected as a loop.[...]
-
Page 61
56 EN 1 1 Display reference T able[...]
-
Page 62
57 Should any display or warning message excluded in the above table be found,please con - tact distributor or call PowerW alker Hot line for advice. ● Indicator light is on ★ Indicator light ashes Warning include one or more than one of these: 1.EPO active 2.Line loss 3.Neutral loss 4.Line phase error 5.Bypass loss 6.Bypass phase error 7.Ba[...]
-
Page 63
[...]
-
Page 64
614-01719-00[...]