Emerson NXL 250 manual

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

Go to page of

A good user manual

The rules should oblige the seller to give the purchaser an operating instrucion of Emerson NXL 250, along with an item. The lack of an instruction or false information given to customer shall constitute grounds to apply for a complaint because of nonconformity of goods with the contract. In accordance with the law, a customer can receive an instruction in non-paper form; lately graphic and electronic forms of the manuals, as well as instructional videos have been majorly used. A necessary precondition for this is the unmistakable, legible character of an instruction.

What is an instruction?

The term originates from the Latin word „instructio”, which means organizing. Therefore, in an instruction of Emerson NXL 250 one could find a process description. An instruction's purpose is to teach, to ease the start-up and an item's use or performance of certain activities. An instruction is a compilation of information about an item/a service, it is a clue.

Unfortunately, only a few customers devote their time to read an instruction of Emerson NXL 250. A good user manual introduces us to a number of additional functionalities of the purchased item, and also helps us to avoid the formation of most of the defects.

What should a perfect user manual contain?

First and foremost, an user manual of Emerson NXL 250 should contain:
- informations concerning technical data of Emerson NXL 250
- name of the manufacturer and a year of construction of the Emerson NXL 250 item
- rules of operation, control and maintenance of the Emerson NXL 250 item
- safety signs and mark certificates which confirm compatibility with appropriate standards

Why don't we read the manuals?

Usually it results from the lack of time and certainty about functionalities of purchased items. Unfortunately, networking and start-up of Emerson NXL 250 alone are not enough. An instruction contains a number of clues concerning respective functionalities, safety rules, maintenance methods (what means should be used), eventual defects of Emerson NXL 250, and methods of problem resolution. Eventually, when one still can't find the answer to his problems, he will be directed to the Emerson service. Lately animated manuals and instructional videos are quite popular among customers. These kinds of user manuals are effective; they assure that a customer will familiarize himself with the whole material, and won't skip complicated, technical information of Emerson NXL 250.

Why one should read the manuals?

It is mostly in the manuals where we will find the details concerning construction and possibility of the Emerson NXL 250 item, and its use of respective accessory, as well as information concerning all the functions and facilities.

After a successful purchase of an item one should find a moment and get to know with every part of an instruction. Currently the manuals are carefully prearranged and translated, so they could be fully understood by its users. The manuals will serve as an informational aid.

Table of contents for the manual

  • Page 1

    AC P ow er For Business-Criti cal C on tinuity™ Li eber t ® NXL ™ Install ation M anual – 250-400kV A, 60Hz, Three Pha s e Single-Module[...]

  • Page 2

    C ONT ACTING L IEBERT FOR S UPPORT To contact Liebert Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-54 3-2378). Liebert Services offe rs a complete range of start-up services, repair services, preventive maintenanc e plans and service contracts. For repair or mainten ance service ou tside the 48 co ntigu[...]

  • Page 3

    i T ABLE OF CONTENTS C ONT ACTI NG L IEBERT FOR S UPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER I MPORT ANT S AFE TY I NSTRUC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 S INGLE -M ODULE M ECHANICA L I NST ALLA TION . . . . . . . . . . . . . .[...]

  • Page 4

    ii FIGURES Figure 1 Cabinet arrangement—Liebert NXL, battery cabinets, maintenance bypass cabinet . . . . . . . . . . 5 Figure 2 External Interface Board connections layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Figure 3 Main components locatio n, 250kVA Liebert NXL UPS . . . . . . . . . . . . . . . [...]

  • Page 5

    1 I MPORT ANT S AFETY I NSTRUCTIONS SA VE THESE INSTRUCTIONS This manual co ntains important ins tructions that should be followed during installation of your Liebert NXL ™ UPS.Read this ma nual thoroughly, paying spec ial attent ion to the sections that apply to your installation, befo re working with the UPS. Retain this manual for use by insta[...]

  • Page 6

    2 NOTICE This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These li mits provide reasona ble protection against ha rmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruc[...]

  • Page 7

    Single-Module Mechanic al Installation 3 1.0 S INGLE -M ODULE M ECHANICAL I NST ALLATION 1.1 Introduction This following se ction describes the requiremen ts th at must be taken into account when p lanning the positioning and cabling of the Liebert NXL uni nterruptible power supply and relat ed equipment. This chapter is a guide to general procedur[...]

  • Page 8

    Single-Module Mechanic al Installation 4 1.3.2 Storage Should the equipment not be installed immed iately, it must be stored in a room for protection ag ainst excessive humidity and or heat sources (see Environmental Parameters in Table 6 ). 1.4 Positioning The cabinet is structurally desi gned to handle lifting fr om the base. Access to the power [...]

  • Page 9

    Single-Module Mechanic al Installation 5 1.6 Cable Entry Cables can enter the UPS cab inet from bottom or t o p into the Input/Output (I/O) section of the unit, see the figure s in 4.0 - Installation Drawings . Figure 1 Cabinet arrangement —Liebert NXL, battery cabinet s, maintenance byp ass cabinet Note: If a m aintenance bypass cabi net is used[...]

  • Page 10

    UPS Electrical Installation 6 2.0 UPS E LECTRICAL I NST ALLATION This chapter provid es guidelines fo r qualified install ers who must have knowledge of local wiring practices pertaining to the equipment to be installed. 2.1 External Protective Devices For safety, it is necessary to install circuit breake rs in the input AC supply and external batt[...]

  • Page 11

    UPS Electrical Installation 7 The following are guidelines only and superseded by local regulations and codes of practice where applicable: • Take special care when determin ing the size of the neutral cable (grounded conductor), because current circulating on the neutra l cable may be greater than nomi nal current in the case of non- linear load[...]

  • Page 12

    UPS Electrical Installation 8 Bottom Cable Entry When making the power connections for bottom cable entry, the recomme nded order of pull- ing and installi ng cables is to start from the bottom connections to the top connections. The cables must be routed around the fault braces (see Detail in Figure 9 ). This is to prevent the cables from contacti[...]

  • Page 13

    UPS Electrical Installation 9 2.3.1 Dry Cont act s Volt-free and isolated contacts are used for interf acing to customer connections external to the NXL unit. These circuits use at least 8mA of current at +24V. EPO Input Dry Cont act Control St atus Inpu t s Dry Cont act The following inputs can sense either a no rmally open or normally closed cont[...]

  • Page 14

    UPS Electrical Installation 10 Switch Auxiliary Input s Dry Cont acts Control St atus Output Dry Cont acts Status signals are outputs through volt-free, normally open and norm ally closed contacts. 2.3.2 Load Bus Synch Connection T able 3 Circuit breaker or sw itch auxiliary contact Input s Item Terminal Block Pin Connects to (description of extern[...]

  • Page 15

    Optional Equipme nt 11 3.0 O PTIONAL E QUIPMENT 3.1 Single-Module System Options 3.1.1 Matching Maintenance Byp ass Cabinet A matching Liebert NXL Main tenance Bypass cabinet is available. See Maintenance Bypass Ca binet Installation Manua l (SL-24532) for more d etails. 3.1.2 Battery T emperature Sensor The optional external battery temp erature s[...]

  • Page 16

    Installation Drawings 12 4.0 I NST ALLATION D RAWINGS Figure 3 Main component s location, 250kV A Liebert NXL UPS HMI Scr ee n EMO But ton (optional) Lieb ert Inte llislot Bay s ® Custo mer Interface Boa rd Main Input Circuit Breaker (C B1) Module Output Circ uit Break er (CB2) Backfeed Breaker (BFB ) Option B ox (6 sl ots avai lable ) Input/Outpu[...]

  • Page 17

    Installation Drawings 13 Figure 4 Outline drawing, 250kV A Liebert NXL UPS 71.8" (1823mm) 34.8" (884mm) 33.5" (850mm) 76.8" (1950mm) 17.6" (448mm) 56.8" (1443mm) 8.5 (2 16) 8.5 ( 216) 26.1 (664mm) 27" (685mm) 9.8" (2 50) 9.8" ( 250) 9.8" (2 50) 9.8" (2 50) 3.1" ( 80) ( ty p) 4.5 (1 1 5) 4.[...]

  • Page 18

    Installation Drawings 14 Figure 5 Main component s location, 300kV A Liebert NXL UPS HMI Scre en EMO Bu tt on (optional) Lieb ert Intellis lot Bays ® Cust ome r Interface Boa r d Main Input Circu it Break er (CB 1) Module Ou tput Circ uit Break er (CB2) Bac kf ee d Br e ak er (BFB) Option Box (6 slots available) Input/Ou tput Cabi net CB Interf ac[...]

  • Page 19

    Installation Drawings 15 Figure 6 Outline drawing, 300kV A Liebert NXL UPS[...]

  • Page 20

    Installation Drawings 16 Figure 7 Input/output conduit det ail dr a wing, 250-300kV A Liebert NXL UPS OUTP U T NEUTRA L INNER PANE L REMOVED FOR CLARIT Y SHO WN IN EXTE NDED POS IT IO N DC (2) 3" CONDUI T NOTES: 1. ALL D IM ENSI O NS AR E I N i nches (m m). 2. 24 " MINIMUM CL EA RANCE A BOV E UNIT REQUIRE D FOR AIR EXHA UST . 3. KE EP CAB[...]

  • Page 21

    Installation Drawings 17 Figure 8 T op cable entry routing and inst allation order The cables must be rout ed around the fault braces. This is to prevent the cables from coming in cont act with other busbars. F AU L T BRACE OUTPU T F AU L T BRACE RECTIFIER INPU T F AU L T BRACE BYP ASS INPU T BYP ASS NEUT RA L DC (POSITIVE) DC ( NEG A TIVE) GROUND [...]

  • Page 22

    Installation Drawings 18 Figure 9 Bottom cable entry routing and in st allation order SIDE VIEW F AU L T BRACE OUTPU T F AU L T BRACE RECT IFI ER INPU T F AU L T BRACE BYP ASS INPU T BYP ASS NEUT RA L DC (POSITIVE) DC ( NEG A TI VE) GROU ND ( T OP ENT RY ) BYP ASS INPU T RECTIFIER INPU T OUTPU T OUTPU T NEUTRA L GROUND (BOT T OM ENT RY) FRONT VIE W[...]

  • Page 23

    Installation Drawings 19 Figure 10 Input/output terminal det ail, 400kV A Liebert NXL UPS NOTES: 1. ALL DI MEN SIO N S ARE I N inc hes (mm) . 2. 2 4" MI NI MUM CLEAR ANC E ABO VE U NI T REQ UI RED FO R AIR EXHA US T . 3. KE EP CAB IN ET WIT HI N 15 DEG R EES O F VERTI CAL . 4. T OP AN D BO TTO M C ABLE ENT R Y A V AILABLE T HRO UG H R EMOV ABL[...]

  • Page 24

    Installation Drawings 20 Figure 1 1 Main component s, 40 0kV A Liebert NXL UPS HMI SCREEN MAIN INPU T CIRCUI T BREA KER (CB1) BACKFEED BREAKE R (BF B) EMO BUT TON OPTIONA L EXTERNA L INTER F ACE BOARD (EIB ) MODULE OUT PU T CIRCUI T B REAKER (CB2) OPTION BO X (6 SLO TS) FRON T DOORS REM OVED DOORS AND INNER SK INS REM OVED[...]

  • Page 25

    Installation Drawings 21 Figure 12 Outline drawing, 400kV A Liebert NXL UPS 3.7 (9 5 ) 10.6 ( 269 ) 12.4 (3 1 6 ) 12.4 ( 316 ) 10.6 ( 269 ) 3.1 (8 0 ) TY P 32.9 (8 3 5 ) 39.4 ( 1000 ) 14.5 ( 368 ) 76.8 ( 1950 ) 29.5 ( 749 ) 25.8 ( 655 ) 78.5 ( 1995 ) FRON T ACCESS PLA TE ACCESS PLA T E CONDUI T LAND ING ARE A (NOTE 4) CONDUI T LAND ING AREA (NOTE4 [...]

  • Page 26

    Installation Drawings 22 Figure 13 Ground strap location for connected ca binet s REFERENC E OF CORNER-PO ST OF CONNECTE D CABINETS Cabinet- to-Cabinet Bolting I nstruct ions T ypical Ground Str ap Installat ion FRONT SIDE OF UNITS ( Use for all connected units exc ept battery cabinet ) A Detail A[...]

  • Page 27

    Specifications 23 5.0 S PECIFICATIONS T able 6 Liebert NXL UPS specif ications 250 300 400 Input Parameters Input Voltage to Rectifie r, VAC 480V 3-phase, 3-wire Input Voltage to Bypass, VAC 480V 3-phase, 3-wire or 4-wire Input Voltage Range, VAC +10% to -15 -15% to -20%* -20% to -30%** <-30%*** Input Frequency, Hz 60 Permissible Input Frequency[...]

  • Page 28

    Specifications 24 Physical Parameters and Standards, in (mm) Width, With Side Panels 71.8 (1823) 78.5 (1993) 78.5 (1993) Depth 33.5 (850) 33.5 (850) 39.4 (1000) Height 76.8 (1950) Weight, Unpackaged, l b (kg) appr ox. 3965 (1798) 4690 (2127) 5250 (2381) Max heat Dissipation, Full Loa d, BTU/hr 49,877 58,819 75,676 Cooling Air CFM 4750 4750 7250 Col[...]

  • Page 29

    Specifications 25 Notes on T ables 1. Nominal input current (considered continuous) is based on full -rated output load. Maxi mum current includes nominal input current and ma ximum battery recharge current (considered noncontinuous). Continuous and noncontinuous cu rrent are defined in nec 100. Maxi mum input current is controlled by the cu rrent [...]

  • Page 30

    Specifications 26 T able 12 Recommended conduit and cable sizes Rectifier Input UPS Rat ing Voltag e (VAC) Nominal Selection Alternate Selection Top Cable Entry Input Wire & Condu it Ph, G THW / FMC Bottom Cable Entry Input Wire & Conduit Ph, G THW / RNC Top Cabl e Entry I nput Wire & Conduit Ph, G THW / FM C Bottom Cable Entry Input Wi[...]

  • Page 31

    Specifications 27 T able 13 Recommended lug sizes Cable Size T&B Series 54000 One Hole T&B Series 54000 Two Hole #8 AWG 54930BE 54850BE #6 AWG 54905BE 256-30695-868 #4 AWG 54906BE 256-30695-733 #2-3 AWG 54942BE 54811BE #1 AWG 54947BE 54857BE #1/0 AWG 54950BE 256-30695-593 #2/0 AWG 54951BE 54862BE #3/0 AWG 54965BE 54864BE #4/0 AWG 54970BE 54[...]

  • Page 32

    EmersonNetworkPower.com Ensuring The Hi gh Av ai lab ilit y 0f Mission-Critic al Dat a And App lic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures network resilienc y and adaptability through a family of technologies—inc luding Liebert power and cooling technologies—that prot ect and suppor[...]